NexSens TS210 Bedienungsanleitung

1
Title Page

i
About NexSens
NexSens is a US-based company specializing in the design and manufacture
of real-time environmental measurement systems. Recent data logger,
sensor and web developments simplify collecting and sharing project data.
Environmental measurement systems are constructed with standard
components. Data is transmitted by WiFi, cellular, satellite or radio and
shared on a real-time datacenter.
Planning
Component and system drawings are available online
Integration
Systems are pre-constructed, tested and documented prior to shipment
Field Services
Installation support and setup ensure successful deployments
Training
Factory or onsite training ensure successful startup and operation
Repair
Technicians inspect and recondition equipment for reliable performance
Support
Online knowledge base, phone and email support are readily available

ii
Table of Contents
Overview ......................................................................1
What’s Included ............................................................2
Common Accessories .................................................................................... 2
Specifications................................................................3
General.......................................................................................................... 3
Temperature ................................................................................................. 3
Getting Started .............................................................4
Multi-Point Temperature String Assembly ................................................... 4
Connecting to an SDL500 Data Logger.......................................................... 6
Connecting to an iSIC Data Logger................................................................ 7
Connecting to an RS485 Modbus RTU Device .............................................. 8
UW-R FL Cable Connections...................................................................... 8
Sensor Information ................................................................................... 9
Register Information ................................................................................. 9
Universal Address ................................................................................... 10
Pre-Deployment Check ............................................................................... 11
Connector Signals........................................................13
Maintenance...............................................................14
Cleaning....................................................................................................... 14
Storage ........................................................................................................ 14
Calibration ..................................................................14
Troubleshooting..........................................................15
Warranty and Service..................................................16

Overview
1
Overview
The NexSens TS210 Thermistor String provides high precision
temperature measurements for profiling in lakes, streams, and
coastal waters. It features an integral titanium thermistor secured
and epoxied in a protective housing for underwater deployments. A
marine-grade cable with braided Kevlar core help ensure reliability
in extreme environments.
Each sensor is accurate to +/-0.075 C for high-precision
measurements. The exposed titanium thermistor makes direct
contact with water, allowing readings to stabilize within 60 seconds.
Temperature data is transmitted on a RS-485 Modbus RTU string
bus for integration with data loggers and SCADA systems. The
string is powered by 4-28 VDC for operation on a 12 or 24 VDC
power supply.
TS210 strings are available standard with 1m spacing or at custom
intervals to meet project requirements. Cable lengths are available
up to 1,219 meters (4,000 feet) with a maximum 250 nodes.
Strings terminate in a NexSens UW plug and receptacle connector,
allowing additional sections or sensors to be added as required.
Optional accessories include a bottom pressure sensor, cable
clamps, stainless steel mooring line, and communication adapters.
Figure 1:
Typical TS210
Temperature
String

What’s Included
2
What’s Included
Each TS210 Water Temperature Sensor includes the UW
underwater plugs required for temperature string terminations and
O-rings for preventing leakage at these connections.
Common Accessories
Table 1: Accessories commonly used with TS210 temperature sensors
Part Number
Description
Details
UW-FLxR
Underwater to
flying lead cable
adapter
Used to connect
TS210 temperature
sensor string to a
NexSens iSIC data
logger
TS-Clamp
TS210 mooring
clamp
Used to secure
TTS210 strings along
a mooring line
SS187-x
Stainless steel
mooring line
Used for buoy and
sensor mooring
systems
RS485-RS232
Signal adapter
RS-485 to RS-232
signal adapter
NOTE
TS210 sensors use
unique NexSens UW
Underwater Connectors
for interfacing with
accessories.

Specifications
3
Specifications
General
Table 2: NexSens TS210 temperature sensor general specifications
Length
3.0 in (76.2 mm)
Diameter (OD)
1.4 in (35.6 mm)
Weight
0.3 lbs
Housing
Acetal Copolymer
Polyvinylchloride (PVC)
Operating Temp Range
0 to 45ºC
Operating Depth Range
4000 ft
Sensor Capacity
250 nodes
Output
RS-485 Modbus RTU
sensorBUS Signals
SDI-12, RS-232
Power Requirements
Voltage: 5 to 16 VDC
Power Consumption
1.3mA active; 0.35mA sleep;
0.05mA deep sleep (per node)
Temperature
Table 3: NexSens TS210 temperature sensor temperature specifications
Range
0 to 45ºC
Accuracy
±0.075ºC
Resolution
0.01ºC
Unit of Measure
Celsius

Getting Started
4
Getting Started
Multi-Point Temperature String Assembly
Multi-point strings are used to determine temperature at various
locations. Typically of interest are temperature distributions
vertically in a water column or horizontally along a stream or
riverbed.
To add the sensors in the Sensor Properties of the iChart Setup
Device Wizard, highlight the appropriate sensor in the Available
Parameters list. TS210 strings typically begin with Temp00 as the
first node. Click Add to add the number of TS210 devices that are
included in the string. Enter the correct Modbus address of the first
node under Modbus Settings (Default is 1). The software
automatically assigns the addresses of the remaining sensors.
If the sensors are to be connected to Port P1, P2 or T (See
Connecting to an SDL Data Logger below) click Show Detail.
Under Switch Power, select SW.A (12V,200mA). Enter 10 in the
Duration (sec) box.
Click OK to finish.
Figure 2: TS210 sensors must be added individually
WARNING
All o-rings must be
clean and dry before
being used to secure
watertight connections.
NOTE
Always check each
mating connector for an
o-ring before securing
any UW underwater
connection.

Getting Started
5
Figure 3: Typical temperature data display in iChart

Getting Started
6
Connecting to an SDL500 Data Logger
UW underwater connectors provide a plug-and-play interface for
connection to NexSens SDL500 Submersible Data Loggers.
The SDL500 sensor bulkhead includes sensor connection ports
identified as T, P1, P0, A and D.
Figure 4: SDL500 sensor bulkhead
TS210 sensors and strings can be connected to Ports P0, P1, T, or
D. It is recommended to connect to port P1 or T to allow for power
to be removed from the TS210 sensors between readings. If this is
done, ensure Switch Power is setup correctly in iChart (See Multi-
Point Temperature String Assembly above).

Getting Started
7
Connecting to an iSIC Data Logger
TS210 sensors can be connected to any iSIC data logger using a
UW receptacle to flying lead cable assembly.
Figure 5: UW Receptacle to Flying Lead Cable
First, plug the temperature string into the adapter’s UW connector.
Run the cable through a gland fitting on the bottom of the iSIC
enclosure. Then, wire flying lead end of the cable into the iSIC
digital terminal strip per the wiring diagram shown in Table 4.
Table 4: iSIC Digital Terminal Strip Wiring Table
Wire
Signal
Pin
Brown
SDI-12
1. SDI
Red
5-16V+
2. SW.A
Black
Ground
4. GND
Yellow
Rx
5. P1.Rx
Orange
Tx
6. P1.Tx
Green
485-A
11. P3.Rx
Blue
485-B
12. P3.Tx
Inhaltsverzeichnis
Beliebte Temperaturregler Handbücher anderer Marken

Swegon
Swegon LUNAd MB Bedienungsanleitung

Lucky Reptile
Lucky Reptile Thermo Control II Bedienungsanleitung

SENSORMETRIX
SENSORMETRIX Argon 100 Bedienungsanleitung

Fuji Electric
Fuji Electric PXE4 Bedienungsanleitung

Yuyao gongyi
Yuyao gongyi XMT-808 series Bedienungsanleitung

Selec
Selec TC544C Bedienungsanleitung