OSPWT225-EN
6/8
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HANDLING & STORAGE
HANDLING
Do not drop or throw the product as it may break.
STORAGE
• Store away from dust, moisture and direct sunlight.
If possible, store in the original package.
• Do not remove a dust proof cap until the piping.
CHECKING
• Check the product code before installation.
• Make sure that the bolts are not loose.
INSTALLATION
PRECAUTIONS
• Flush the pipeline carefully before installing the
damper. Foreign particles, such as sand or pieces of
welding electrode, will damage the disk and seats.
• For dampers with specified flow direction (WT),
check the arrows on the product before piping.
• Damper is shipped closed. (TAC is closed with a
manual unit. Without a manual is open.)
• The butterfly damper should be piped upstream of
the elbow. When piping downstream from the elbow,
considered a straight line that is at least five times
the length of the pipe.
• The damper stem should be mounted perpendicular
to the flow for biased fluid.
• Disc interference may also occur when damper is
installed in pipeline with smaller than normal inside
diameter such as thick wall pipe, or lining pipe.
Suitable corrective measurement must be taken
(taper boring the pipe or pipe liner, etc.)
PIPING FLANGES
• Gasket should be selected appropriately to suit the
fluid, pressure and temperature.
Use spring washer to prevent from decreasing
surface pressure gasket when the temperature
change happens frequently.
• Wafer type butterfly damper is put between two
seats of flanged-end and tightened with long bolts.
• Before bolts are tightened, damper should be
centered within the bolts to prevent possible disc
interference or damage by contact with the pipe or
flange.
• Tighten all bolts using crossover method to load the
joint evenly.
ENVIRONMENT
• Do not install in place where corrosive gas is present
or where vibration is heavy (0.5 G or more).
• When radiant heat causes the surface temperature
of the control unit to exceed 50 °C, provide an
appropriate shielding plate.
• If there is a possibility that the fluid and drive part
freeze, please take measures to prevent freezing.
• For single-acting type, prevent water and dust from
coming into air exit.
POSITIONING
Should be positioned through 90° upward from
horizontal. Provide space around the product to
allow manual operation, inspection and replacement
work.
INSULATION WORK
• For maintenance of gland packing, insulation should
be below the ground part.
• The upper part of the ground plate part is a heat
dissipation part, do not insulate it.
Slow Fast Slow Fast