Oilon CUBE Series Leitfaden

M8006 2123EN
10 June 2021
CUBE and ECO
INSTALLATION AND
COMMISSIONING


Contents
1 Introduction
1.1 Heat pumps covered in this manual...........................................................3
1.2 Instructions and diagrams...........................................................................3
1.3 Safety notice and warnings........................................................................ 3
1.4 Transportation and storage.........................................................................5
1.5 Scope of delivery........................................................................................ 6
1.6 Accessories................................................................................................. 7
2 Installation
2.1 Installation site.......................................................................................... 10
2.2 Dimensions, connections, and components............................................. 11
2.3 Outdoor temperature sensor (CUBE, ECO)............................................. 13
2.4 In-line heater (CUBE, ECO)..................................................................... 13
2.5 Bleeding the domestic hot water coil (CUBE).......................................... 15
2.6 Thermostatic mixing valve assembly (CUBE, optional)............................ 16
2.7 Change-over valve (ECO, optional)..........................................................18
2.8 DHW tank sensor (ECO).......................................................................... 18
2.9 Electrical connections, covers, and cable management...........................19
2.10 Pipe joints................................................................................................. 20
2.11 Removing the compressor unit from the frame (CUBE)........................... 20
3 Heating circuits
3.1 Buffer tank.................................................................................................22
3.2 Buffer tank sensor (CUBE, ECO)............................................................. 22
3.3 Flow temperature sensor for heating circuit 1 (CUBE, ECO)................... 23
3.4 Heating water temperature, return to condenser (ECO)...........................25
3.5 Heating circuit’s control valve...................................................................25
3.6 Heating circuit pump................................................................................. 28
3.7 Heating circuits 2 and 3............................................................................30
4 Commissioning
4.1 General......................................................................................................31
4.2 Signing in as a service level user............................................................ 31
4.3 Initial setup settings.................................................................................. 32
5 Operation
5.1 Heat pump operation................................................................................ 38
6 Technical data
6.1 Technical data...........................................................................................40
6.2 Compressor units......................................................................................45
6.3 Performance data......................................................................................46
M8006 2123EN 1 (54)

6.4 Condenser circuit flow.............................................................................. 47
6.5 Brine circuit flow........................................................................................47
6.6 Pumps....................................................................................................... 48
6.7 EU Product Data.......................................................................................51
2 (54) M8006 2123EN

1 Introduction
1.1 Heat pumps covered in this manual
Heat pump models with EasyAce control Designation Refrigerant
CUBE 6 EasyAce CUBEH607 R-410A
ECO 6 EasyAce ECO607 R-410A
CUBE 8 EasyAce CUBEH807 R-410A
ECO 8 EasyAce ECO807 R-410A
CUBE 10 EasyAce CUBEH1007 R-410A
ECO 10 EasyAce ECO1007 R-410A
CUBE 13 EasyAce CUBEH1307 R-410A
ECO 13 EasyAce ECO1307 R-410A
ECO 17 EasyAce ECO1707 R-410A
ECO 21 EasyAce ECO2107 R-410A
1.2 Instructions and diagrams
Document Designation
CUBE and ECO
Installation and commissioning
M8006
This manual
ECO and CUBE
Electric diagram
34793610 (110974)
ECO
Piping diagram
34793609
CUBE
Piping diagram
34793607
EasyAce
Quick guide
M8007
EasyAce
Installation and initial setup
M8005
EasyAce
User manual
M8004
1.3 Safety notice and warnings
Any maintenance and service procedures described in this manual should be
performed by competent and appropriately trained maintenance personnel only. The
unit contains no user-serviceable parts.
M8006 2123EN 3 (54)

Electrical safety
Once powered on, some of the unit’s components carry a hazardous
voltage. Always pay attention to electrical safety when working with or
near electrical components.
Before any maintenance or servicing, switch off electricity using the
main switch and ensure that there is no voltage present in the unit’s
components.
Refrigerant
Refrigerant leaking from an open or broken circuit may cause
asphyxiation, severe frost damage, arrhythmia, or neurological
symptoms. If you suspect a refrigerant leak, leave the area immediately,
and seek fresh air. Help and warn others.
The unit includes a hermetically sealed refrigerant circuit filled with refrigerant R-410A.
Refrigerant R-410A is a mixture of two refrigerants: HFC-32 (R-32, difluoromethane)
and HFC-125 (R-125, pentafluoroethane).
Refrigerant R-410A is a fluorinated greenhouse gas and, consequently, subject to the
EU F-gas Regulation. Please recover the refrigerant as required by law, and transfer
the refrigerant for recycling or disposal as required by applicable laws, rules and
regulations.
The refrigerant is heavier than air. The refrigerant may accumulate in enclosed spaces,
especially at or below the floor level (for example, in basements). Ventilate the spaces
by opening the space’s doors and windows from the outside. Use fans, if necessary.
Do not enter any space where you suspect there to be leaked refrigerant present.
Lifting and handling
The weight of the unit presents a crush hazard. Use safe work methods
when lifting and handling the unit.
Safety devices
Do not bypass, disable, or damage any of the unit’s pressure switches or other
safeguards with tools, by accessing the system’s software, or by any other means.
Bypassing the unit’s safeguards may lead to equipment failure, damage to property or
injury to people.
Wireless touch screen
Use the wireless touch screen provided with the unit only for operating the unit’s
automation system. Using the touch screen for any other purpose may cause
slowdowns or interference in the use of the unit’s automation system, or prevent the
system from being used altogether.
4 (54) M8006 2123EN

1.4 Transportation and storage
Storage
Store the unit upright in a warm, dry place. Protect the device against water and dust.
Do not stack goods on the unit.
Transportation
Transport the unit upright and protected against water and dust. Do not stack goods
on the unit. Use only safe lifting and handling methods when moving or lifting the
unit. After lifting, lower the unit carefully down onto the floor. Hard impacts can cause
equipment damage.
When lifting the unit, grab the unit by the frame. Do not lift the heat pump from the
bottom of the compressor unit.
● The unit’s exterior panels may be removed to make it easier to carry and move the
unit.
● The unit can be carried short distances by the side bars.
● If necessary, the compressor unit can be detached from the frame of the heat pump
before carrying or tilting the unit.*
● Do not lift or move the unit with the domestic hot water tank filled.*
*Applicable to heat pumps with an integrated DHW tank.
The compressor unit can be tilted up to 45 degrees from horizontal. If you need to tilt
the heat pump beyond 45 degrees, remove the compressor unit.
● If the unit is tilted beyond 45 degrees, the compressor may not receive proper
lubrication at startup. As a result, the compressor may become damaged.
● If the unit has been accidentally tilted beyond 45 degrees, leave the unit in vertical
position for at least three hours before starting the compressor.
M8006 2123EN 5 (54)

1.5 Scope of delivery
Equipment and components
Item PCS Oilon
designation
Wireless touch screen
● For using the EasyAce control
app to control the heat pump’s
automation system
1 378810400
Wireless touch screen ver. 1
Outdoor temperature sensor
● Sensor ID is TE0.
● Connect the sensor to the
cable TE0–W1.
1 36217543
Outdoor temperature sensor ver. 1
Shut-off valve
● Install the valves in the heat
pump’s brine and heating
water connections.
4 34033361
Shut-off valve ver. 1
Compressor fitting, 28 mm
● 1" external thread
● CUBE: install the parts in
heating circuit connections.
● ECO: install the parts in
heating circuit and brine circuit
connections.
2 34245086
Compression fitting ver. 1
Gasket
● Install the gaskets between
the brine circuit’s corrugated
hoses and shut-off valves.
CUBE:
2
ECO:
4
34797278
Gasket ver. 1
Torx T25 key
● Provided for opening the
device’s Torx T25 screws.
1 34798044
Torx T25 ver. 1
6 (54) M8006 2123EN

Sensors and actuators
EasyAce ECO CUBE
BRINE CIRCUIT
TE101 Brine circuit in (evaporator in) S S
TE102 Brine circuit out (evaporator out) S S
P101 Brine pump (evaporator circuit pump) S S
HEATING
TE201 Heating water in (condenser in) S S
TE202 Heating water flow (condenser out) S S
P201 Heating pump (condenser circuit pump) S S
EB203 In-line heater, condenser circuit O S
TE255 Buffer tank temperature (tank upper section) S O
TE266 Domestic hot water tank temperature (tank lower
section)
S S
FV202 Change-over valve O S
TE0 Outdoor temperature S S
HEATING CIRCUIT 1
TE212 Heating circuit 1 flow temperature S O
P221 Heating circuit 1 pump O O
FV222 Heating circuit 1 control valve O O
TE213 Room temperature 1 O O
HEATING CIRCUIT 2
TE222 Heating circuit 2 flow temperature OA OA
P221 Heating circuit 2 pump OA OA
FV222 Heating circuit 2 control valve OA OA
TE223 Room temperature 2 OA OA
HEATING CIRCUIT 3
TE232 Heating circuit 3 flow temperature OA OA
P231 Heating circuit 3 pump OA OA
FV232 Heating circuit 3 control valve OA OA
TE233 Room temperature 3 OA OA
REFRIGERANT CIRCUIT
COMP1 Compressor S S
TE2 Hot gas temperature S S
PS1 Low pressure switch S S
PS2 High pressure switch S S
DATA HUB
HUB Connection device for the EasyAce system
(EasyAce Hub)
S S
S: Standard equipment
O: Optional accessory, can be connected to the heat pump’s automation system and enabled without
additional equipment.
OA: Optional equipment that requires an auxiliary controller kit (controller + enclosure) for installation.
1.6 Accessories
For a full list of available accessories, please refer to brochures and price lists. Storage
tanks are presented in a separate storage tank brochure.
M8006 2123EN 7 (54)

Accessories
Accessory Auxiliary controller with enclosure
Designation 32586192
Description An enclosure containing an auxiliary controller for regulating heating circuit 2 and 3
or increasing the number of I/O slots for different functions. Installed on top of the
heat pump unit (ECO) or in the upper part of the heat pump frame (CUBE). 24 V
input from the heat pump, 230 V input from the building’s distribution board.
Documents Electric diagram: 34793611 (110992), manual 34793612
Accessory Temperature sensor NTC10k 5 m
Designation 36217266
Description Sensor with flexible cable (length: 5 m), metallic probe (diameter: 6mm, length: 50
mm), 1xNTC 10 kOhm, 2 wires, B(25/85)=3976, t0,9 7 s
Intended use Buffer tank temperature TE255
Heating circuit flow temperature TE212, TE222, TE232
Accessory Sensor pocket 6x200 G1/2
Designation 34021268
Description For 6 mm sensor probes, with cable gland, depth: 200 mm, G1/2" outer thread,
brass
Intended use Sensor pocket for buffer tanks and heating circuits
Compatible
equipment
36217266
Accessory Heating circuit control valve actuator, 3-point, 230 V
Designation 36962089
Description Esbe ARA651 12101200, 3-point SPDT, 230 V, 3 wires, 60 s 90°
Valve 34034065, 34034067, 34034068, 34034467
Accessory Heating circuit control valve actuator, 0–10 V 24 V
Designation 36962220
Description Esbe ARA639 12520100 (12520117 OEM), 0–10 V, 4–20 mA, 24 V AC/DC, 3wires,
15/30/60/120 s 90°, pre-set to 60 s (DIP switch 2 ON), pre-set to OPEN (with
increasing signal) counterclockwise CCW (DIP switch 6 ON)
Valve 34034065, 34034067, 34034068, 34034467
Accessory 3-way valve for heating circuit, DN 20-6.3
Designation 34034068
Description Esbe VRG131 11600900, DN20, Kvs 6.3, Rp 3/4"
Actuator 36962089, 36962220
Accessory 3-way valve for heating circuit, DN25-10
Designation 34034065
Description Esbe VRG131 11601100, DN25, Kvs 10, Rp 1"
Actuator 36962089, 36962220
Accessory 3-way valve for heating circuit, DN25-6.3
Designation 34034067
Description Esbe VRG131 11601100, DN25, Kvs 6.3, Rp 1"
Actuator 36962089, 36962220
8 (54) M8006 2123EN
Dieses Handbuch passt für folgende Modelle
21
Inhaltsverzeichnis
Andere Oilon Wärmepumpe Handbücher
Beliebte Wärmepumpe Handbücher anderer Marken

Mitsubishi Electric
Mitsubishi Electric PUZ-SWM60VAA Bedienungsanleitung

Dimplex
Dimplex LI 16I-TUR Benutzerhandbuch

Carrier
Carrier WSHP Open v3 Kurzanleitung zur Einrichtung

TGM
TGM CTV14CN018A Bedienungsanleitung

Carrier
Carrier 38MGQ Series Bedienungsanleitung

Kokido
Kokido K2O K880BX/EU Fehlerbehebungshandbuch