Opera 6000 series Bedienungsanleitung

Version 6.2
OPERATION MANUAL
Digital Gas Monitor/Controller

TABLE OF CONTENTS
1.0 General Description
1.1 Applications
1.2 Features
1.3 Specications
1.4 User Interface
2.0 Model Selection Guide
3.0 Installation
3.1 Monitor Placement
3.2 Wiring
3.3 Installation Check List
4.0 Operation
4.1 Screen Display
4.2 Default Settings
4.3 Changing Settings
4.4 List of Settings
4.5 Sequence of Operation
5.0 Network Conguration
5.1 Using CAN Network, Central Controller
5.2 Using CAN Network No Central Controller
5.3 Defaults Conguration
5.4 Creating Zones or Groups
5.5 Addresses
5.6 Output Relays
6.0 Maintenance Guide
6.1 Calibration Procedure
7.0 BACnet Network Conguration

6000 Series Digital Gas Monitor/Controller
Important Information !
This manual provides information required to install, operate and
maintain the series 6000 gas monitoring system. Read and study
before attempting to install or operate monitors. Installation
and operation not in accordance with this manual can result in a
hazardous situation or harm. Relay connections may be used to
control 120 Vac equipment. Ensure power is disconnected from
relays before attempting to service this unit.
1.0 General Description
Series 6000 gas monitors provide air quality monitoring for
commercial properties. Close monitoring of indoor air-born
pollutants and automatic fresh air controls improve the health and
well being of occupants and, also minimize excess ventilation,
reducing both energy costs and maintenance costs. The key to
maintaining this balance is a high level of precision coupled with a
robust design suited to tough commercial applications.
Each 6000 monitor can measure one or two gases and control
ventilation directly. They communicate with each other (up to 32)
via the chain network, so some monitors activate the ventilation
and others send the commands. The monitors are easily assigned
to groups on site for ventilation zoning on the same network. This
reduces control wiring signicantly.
The use of this peer-to-peer CAN network eliminates the need for a
costly controller on smaller projects. For the larger ones, a 6000-B
controller or addressable relay units can be added where starters
are centralized in the mechanical room. The monitors can also be
tied into a BACnet building automation system by simply connecting
an MS/TP cable to any monitor or 6000 controller on the CAN
network. The gas readings from all the monitors will display on the
BMS and the BMS can over-ride output relays on the monitor it is
connected to.

6000 Series Digital Gas Monitor/Controller
1.1 Applications:
• Vehicle emissions in indoor parking garages
• Municipal maintenance facilities
• Bus terminals
• Automobile dealerships
• Hospital parking for ambulances and visitors
• Volatile organic vapor control from soil contamination
• Refrigerant Gas Leak Monitoring
• CO2 demand control ventilation for meeting rooms
• Warehouse ventilation Control
1.2 Features:
• Stand-alone operation with adjustable alarm relays,
indicators and strobe
• BACnet Laboratory (BTL) listed Smart Sensor
• BACnet MS/TP RS485 interface
• CAN network master-slave operation or central control via
6000-B controller.
• Pre-calibrated plug-and-play sensor modules avoid the
need to recalibrate when upgrading expired sensors.
• Impact resistant, water resistant enclosure, with top wire
entry and drip proof wire guide.
• Binary input for conrmation of external action (fan on or
damper open)
1.3 Specications
• Supply 24 vac 50/60 hz (17-28 vac) 0.21 amps, 5 va
• Relays (1 or 2) SPDT, 5 amp @ 125 vac, non-inductive
On delay; 0-999 seconds (16 minutes)
Off delay; 0-999 seconds (16 minutes)
• Operating temperature -20 ºC to 40 ºC (-4 ºF to 104 ºF)
• For indoor use
• Flame resistant Polycarbonate ABS enclosure rated UL94
V0, 5VB, and 5VA
• Standards. Listed to CSA C22.2. no. 205-17.
Conforms to CSA C22.2 61010-1.
• Analogue 4-20 ma or 2-10v (model 6000-A)

1.0 General Description
• Pollution degree 2
• Installation catagory II
• Altitude 2000 m
• Humidity max 80% rh. 80% to temperatures up to 31 ºC
88 ºF, decreasing linearity to 50% rh at 40 ºC (104 ºF)
1.4 User Interface:
• Back lit LCD display shows gas concentration, user
settings, calibration controls
• Red LED alarm indicators, gas level 1 and 2
• High intensity white LED strobe on level 3
• Audible alarm, 85 db at 1 meter
• 4 pushbutton user keypad
• Password control for settings

6000 Series Digital Gas Monitor/Controller
2.0 Model Selection Guide
6000-B _
• 2 relays
• no analogue outputs
6000-A
• 1 relays
• 2 analogue outputs
6002-14-B _6002-14-A
Controller Only
Example: Monitor for CO + NO2
Gas Type
(see chart)
Gas type
if second
sensor
installed
55-xx
Controller with
Sensor(s) inside
Sensor Replacement
Module
Gas Type
(see chart)
Gas Type
(see chart)
Gas type
if second
sensor
installed

2.0 Model Selection Guide
Gas Type Range
-Controller only, no sensor 00
NH3Ammonia 04 0-250 ppm
Ar Argon (O2depletion) 23 0-50% O2
CO2Carbon dioxide (air quality) 15-2000 0-2000 ppm
CO2Carbon dioxide (compressed) 15-5000 0-5000 ppm
CO Carbon Monoxide 02 0-100 ppm
CO Carbon Monoxide 02-250 0-250 ppm
CO nil H2Carbon Monoxide nil H2 effect 02nilH2 0-100 ppm
CL2Chlorine 17 0-10 ppm
C2H5OH Ethanol 07 0-50% LEL
HCFCs 13
HFCs 20
He Helium (O2depletion) 23 0-25% O2
H2O in air Humidity (relative) 25 0-100% RH
H2Hydrogen 08 0-50% LEL
H2S Hydrogen Sulde 16 0-50 ppm
CH4Methane 05 0-50% LEL
CH3OH Methanol 07 0-50% LEL
N2Nitrogen (oxygen depletion) 23 0-50% O2
NO2Nitrogen Dioxide 14 0-10 ppm
VOCs Organic Vapors 01 0-1000 ppm
O2Oxygen Leak 22 0-50% O2
O2Oxygen Depletion 23 0-50% O2
C3H8Propane 06 0-50 % LEL

6000 Series Digital Gas Monitor/Controller
3.0 Installation
3.1 Monitor Placement
Coverage
Guidelines for placement of diffusion type monitors are based on
the reasonable delay for gas to get from the source to the sensor.
All monitor sensors combinations are created equal in this regard.
• For air quality control of exhaust emissions and
accumulations of toxic gases the generally acceptable
maximum radius of coverage is 50 feet (15 meters).
Approximately 7500 square feet (700 square meters).
• For leak detection of combustible gases, ammonia,
refrigeration gases the maximum radius is 30 feet (10 meters).
The radius of coverage of any monitor does not extend beyond
any obstruction that impedes natural circulation of air. This
includes walls, stairs, elevators, shelving with solid ll, tool
chests, etc. The sensor must “see” the area of coverage; if not,
additional monitors are required.
Mounting Heights
Mounting heights for gas monitors are based on their density,
relative to air. There are three groups;
1. Lighter than air and will be more concentrated near the
ceiling; hydrogen, methane (natural gas), ammonia.
Install at 1 to 3 feet from ceiling.
2. Similar density to air and will be diluted in air equally at
all levels; - carbon monoxide, nitrogen dioxide, hydrogen
sulde, oxygen, carbon dioxide. Install from 3 feet (1
meter) off oor to one half of the ceiling height. For vehicle
emissions carbon monoxide sensors combined with nitrogen
dioxide sensors are installed at 3 to 5 feet (1 to 2 meters)
from the oor when the ceiling height is 7 to 10 feet. If the
ceiling height is higher than 10 feet, example- for heavy
equipment, the carbon monoxide monitors are installed

at 3 to 5 feet (1 to 1.5 meters) from the oor as per the
requirements of the Canada building codes and the nitrogen
dioxide monitors should be installed at 50% of the ceiling
height and above the vehicle height. If the exhaust pipes
of diesel vehicles are below the vehicles, then the nitrogen
dioxide monitors should be installed at 3 to 5 feet (1 to 1.5
meters) from the oor. In all cases the monitors must be
installed above obstructions blocking circulation of air in
front of the monitors; example, maintenance garages in
automobile dealerships where tool chests, work tables and
storage racks typically line all walls.
3. Heavier than air and will concentrate near the oor; - HFCs,
HCFCs, propane, chlorine, most organic vapors (consult
Opera). Install 1-2 feet (30cm to 50cm) from oor.
For all types of monitors avoid drafts, obstacles, aerosols, silicones.
Place sensors in the center of its coverage area as much as
possible.
3.0 Installation

6000 Series Digital Gas Monitor/Controller
3.2.1 Wiring Model 6000-A
ac
Supply
Independant
Circuit
120 Vac
To magnetic starter coil or
control relay coil for ventilation
Transformer
120/24 Vac
To Other
units
BACnet
MSTP
network
CAN
network
Binary
input
to limit
switch
see 4.4 #32
End of line jumper
CAN bus
Down = Off
Up for rst and last
unit on cable
Up Position 4-20Ma
or
Down Position 2-10V EOL BACnet
5 Va for
each unit
NO COM
Relay 1
NC ANA1 G
Analogue Output
ANA2
–
+
SHIELD
(no connect)
High (H)
Low (L)
Shield
(on 1rst unit only)
to other
units