00 No safety device in alarm state and no limit switch activated.
21
STOP contact (N.C.) open.
Jumper the STOP contact.
Release handle or lock open.
Barrier inspection hatch open.
23 Sensing edge contact COS (N.C.) is open. Check connection. If sensing edge is
not installed, disable with 73 00.
24 Photocell contact FT (N.C.) is open. Check connection. If photocell is not installed,
disable with 50 00.
br Shatter-proof system enabled, or not connected or incorrectly connected.
rs (rS) STOP contact active for MASTER barrier (message shown on SLAVE controller
displayed).
4. Before starting ...
d) Move the barrier boom into the completely CLOSED position.
c) Check the spring balance setting and the mechanical stop setting.
See the installation manual for the barrier.
e) Press TEST Possible alarms and safety device messages:
PROG TEST
+
-
TEST
PROG TEST
+
-
SEE ACQUISITION PROCEDURE
a) IMPORTANT: Select the length of the boom with the parameter A1.
It is very important that this parameter is selected correctly. An incorrect setting may cause severe damage or injury.
b) Select the position of the barrier in relation to the gate, using
parameter 71.
The factory setting of the parameter is with the barrier installed on
the right (7101) and the boom opening/closure gate on the left
(seen from the inspection hatch side).
If the installation position is changed from the right to the left, the position of
the spring(s) must also be changed.
IMPORTANT! Lubricate the pivot points with lithium
based grease
AG/004
KB/004
BI/004HP up to 3 m
BI/004 up to 3 m
AG/004
KB/004
BI/004HP from 3 m to 4,5 m BI/004 from 3 m to 4 m
AG/006
KB/006
BI/006 from 4,5 m to 6 m BI/008 up to 8 m
45° >45°
IMPOSTAZIONE DI FABBRICA
FACTORY SETTING