Schwank ThermoControl Plus 4 Bedienungsanleitung

ThermoControl Plus 4
Eight controller circuits 1-stage
Four controller circuit 2-stage
Operating and
Installation Manual
Schwank Group
P.O.Box 988 2 Schwank Way @ Hwy. 56N
Tel:1-877-446-3727 Fax: 1-866-361-0523
www.schwankgroup.com IM100630
RL:2
JUNE2010

- 2 -
Content:
1 INTRODUCTION ............................................................................................... 4
2 SAFETY ............................................................................................................. 5
3 Display and Button Function .............................................................................. 6
4 OPERATION ..................................................................................................... 7
4.1 Basic operation .......................................................................................... 7
4.1.1 Further display information ........................................................................ 7
4.1.2 Selection of a control zone ......................................................................... 8
4.1.3 Activation and deactivation of a control-zone ............................................. 8
4.1.4 Special information in the base display ...................................................... 8
4.2 Display and change of occupied / unoccupied temperature ....................... 9
4.3. Display and modify time and date ............................................................ 10
4.4 Circuit/Zone Times ................................................................................... 12
4.4.1 How to display and read a zone time program ......................................... 12
4.4.2 How to clear a switch point ...................................................................... 13
4.4.3 How to clear a time program .................................................................... 13
4.4.4 How to protect the time program .............................................................. 13
4.4.5 Program the switch points ........................................................................ 14
4.5 Holiday program ....................................................................................... 15
4.6 Manual operation
FI
X
............................................................................ 16
4.7 Button for service maintenance mode ...................................................... 16
5 SET UP THE OPERATING PARAMETERS .................................................... 17
5.1 Enter the number of control zones ........................................................... 17
5.2 Set up system operation parameters ....................................................... 18
5.3 Adaptive heat recovery time .................................................................... 19
5.4 COPY ....................................................................................................... 20
5.5 Securely save or reload all parameters .................................................... 20
6 INSTALLATION ............................................................................................... 21
6.1 Electrical Supply ...................................................................................... 21
6.2 Sensor Connections ................................................................................. 22
6.3 Heater Connection ................................................................................... 22
Zone Configuration Diagrams
6.4 Standard Tube Heaters (single fire rate) .................................................. 22
6.5 Two-stage Tube Heaters ......................................................................... 23
6.6 Luminous Heaters .................................................................................... 23
6.6.1 Luminous Heaters - Jumper P1 ............................................................... 24
6.6.2 Luminous Heaters - Jumper P2 ............................................................... 25
6.6.3 Luminous Heaters - Jumper P3 ............................................................... 26
6.6.4 Luminous Heaters - Jumper P4 ............................................................... 27
6.6.5 Luminous Heaters - Jumper P5 ............................................................... 28

- 3 -
6.7 Exhaust Fan Output - Two-stage Luminous Zones .................................. 29
6.8 Alarm Contact Input ................................................................................. 29
6.9 Remote-Control .................................................................................. 29
6.10 Signal input fault ...................................................................................... 29
6.11 Temperature display ºF / ºC selection ...................................................... 29
6.10 Communication connection (CM232, CM485) ......................................... 30
6.11 Common fault signals .............................................................................. 30
7 TECHNICAL PARAMETERS ........................................................................... 31
8 WIRING DIAGRAMS ....................................................................................... 33
8.1 Standard Tube Heaters: single- and two-stage zones ............................. 33
8.2 Two-stage Tube Heaters: two-stage zones ............................................. 34
Two-stage Tube Heaters: Internal Burner Wiring ..................................... 35
8.3 Luminous Heaters: single-stage zones .................................................... 36
8.4 Luminous Heaters: two-stage zones ........................................................ 37
8.5 Wiring Diagrams: Overrides, Humidity Control, Temp. Averaging ........... 38
8.6 Temperature Sensor Characteristics ....................................................... 39

- 4 -
1 Introduction
The Schwank ThermoControl Plus 4 is suitable for single or two-stage gas-infrared heating
systems.
Dependant upon its operation the controller has one or two controller circuits.
Please read this manual carefully before installing or using the control-unit. Failure to follow the
notes and warnings will affect your guarantees. They are also a prerequisite for a professional
installation and correct handling.
Please pay special attention to chapter 2 “Safety“.
The ThermoControl Plus 4 is designed to be used for industrial/commercial building infrared
heating systems only. Other or further uses are not suitable.
Schwank will not be held responsible for any damages whatsoever resulting from incorrect use.
The controller measures the radiant and ambient temperatures in the space and switches the
heater(s) on/off by relays.
The controller features different operating programs.
-P1…P5: single- or two-stage controller for luminous gas-infrared heaters and tube heaters
Override day temperature mode +h
Available as a special optional feature is a setback override bu tton that manually extends the
programmed heating period. This bu tton is installed parallel to th e sensor. By pushing the button
(~1 sec.), the nominal value of the programmed temperature in t he selected control circuit is
maintained for an additional programmable time period. (Default 1h)
Programmed temperature values and operating programs
The temperatures and operating programs of each single control circuit are independently
selectable.
- Day- , night- or anti-freezing temperature , selected by a week program
- Continuous day-( FIX) night-( FIX) or anti freezing temperature ( FIX).
- Holiday program: the controller is able to save eight holiday periods, which are programmed
according to the calendar.
Other Tools/Features:
– Illuminated display
– Selectable ºF / ºC temperature display
– Button for service maintenance operation mode
– Real-time clock with calendar, including automatic summer / winter time correction
– Outdoor temperature sensor (SA)
– ‘Smart’ adaptive recovery: based on outdoor temperature, adjusts system ramp-up to ensure the
desired occupied temperature is achieved at the programmed time.
– Remote controlled day-mode operation
– ‘On’ cycle record at each output
– Error-relay: relay switches on in any case of error

- 5 -
2 Safety
This is a 24VAC Class 2 low voltage
(24Vac) temperature controller. Use
only Class 2 rated power supply. Do
not install on voltages higher than
30Vac.
Read all information in this manual
before installing or programming the
appliance. Electrical installation and
wiring must conform to local and
national building and electrical
codes. Check the electrical
equipment regularly. Defective wire
etc. must be replaced immediately.
Be sure that power routed to the
controller has been powered ‘off’
before beginning installation or
installation of communication
modules. Lock out the power supply.
The Schwank ThermoControl Plus 4
must be mounted where it is not
affected by vibration or shock.
The feed/supply line must be
protected by the installer with a fuse
of maximum 16 A.
Install the ThermoControl Plus 4
ensuring conformity to the wiring
diagram located in the switchboard.
Minimum Wiring Connection:
It is the installer’s responsibility
to ensure that wire gauge is
sufficient to provide 24Vac from
the transformer to the controller,
and from the controller 24Vac
outputs to the external relays
that power heaters and exhaust
fans. The distance between the
power source and equipment
must be considered.
24Vac power from 100VA
transformer to the controller
with minimum 16 AWG wire
24Vac from controller outputs
to equipment power relays
with minimum 16 AWG wire
Connect sensor to controller
with minimum 18 AWG wire
Install the IR temperature sensor
between the radiant area of two
heaters at a height of 6 ft (2 m)
above floor. In this location the
controller receives the optimal
value of the comfort temperature
(radiant temperature plus
ambient temperature).
NOTE: If heating zones are dimensionally
large in size or there are extreme
temperature gradiants within the
zone, temperature averaging can
be achieved using four IR sensors
wired in parallel-series for each
zone.

- 6 -
3 Display and Button Function
Front panel layout:
1. I/O Main switch on / off
2. LCD Display: All functional and operating information is shown in the base display mode
(upper picture). If no button is pushed for more than one minute, the control unit
switches back to the base display.
3. Push the button or the button to display the day or night set value. Use the +/-
buttons to modify the values.
4. + / - With these buttons the display values can be increased or decreased.
5. DISP “Display-button“: To change the di splay. This button also offers the ability to switch back
to the main menu immediately.
6. SEL “SELECT”: This button allows selection of a certain parameter shown in the display. The
chosen/selected parameter can be modified using the +/- buttons.
7. Clock-button: display and modify time and date.
8.
FI
X
Toggles between programmed and FIXED modes.
9. PR To check and modify the weekly time program in the displayed control circuit.
10. CLR “Clear-button“: To delete a switch-point or a complete time program.
11. Copy This button can be used to copy time- and temperature programs.
12. ERROR The system-error lamp flashes for any kind of error. An flashing sign will provide
information about the cause.
13. ZONE To switch between different control circuits.
14. To turn on/off the single control circuit.
15. SERVICE “Maintenance”: If this appears, please call your service professional.
16. Button to program holiday operation mode.
17. Button for service maintenance operation mode: all control circuits heat full load.

- 7 -
4 Operation
4.1 Basic operation
When starting the ThermoControl wit h the I/O -button an automatic disp lay-test is activated. The
controller starts with the factor y default program. The display then switches to the base-program,
which shows all the important operation information.
4.1.1 Further display information
Actual control mode, in
this case: day
mode Present status of the heater zone:
full load
partial load (only 2-stage control)
heater is turned off
Measured temperature
in the space/zone
(18.2°C)
The exhaust fan is
working (optional)
Indication of the
chosen control circuit
Indication of which relay output and which
sensor inputs are used in the specific
control circuit.
Display of the outside te mperature (only if an
outdoor temperature sensor SA is connected).
‘On’ cycle counter: The 2-stage control shows the
circuit time of both stages.(1,2).
Push the SEL button to
switch between the
stages. The data cannot
be deleted, after 999999
hours the display
switches back to zero.
The main/base display give s all important operating
data, further information can be received by pushing
the DISP button.
Value of the entered freeze protection temperature .
The displayed value can be changed by the +/-
buttons. Range of setting: +3 ... +20 °C / 37 ...68 ºF

- 8 -
4.1.2 Selection of a control zone
4.1.3 Activation and deactivation of a control-zone
To stop heating in a certain zone: select the zone, and push the button. The symbol will
indicate the deactivation of the zone. In the deactivated zone only temperature measurement and
display continue to work. Activate the control zone again by pushing the button.
4.1.4 Special information in the base display
The controller display and its usage is
based on the display of the control
circuit. The control zone can be
selected by pushing the ZONE
button. All settings of the control zone
can be managed.
During adaptive heat recovery (optimised heat time) the
OPT symbol appears. The activati on time of a specific
zone is dependent on the hi story of preheating
performance compared to the entered heating time. This
function can be deactivated onl y in the setup-menu. An
outside sensor SA is required for this feature.
While using the holiday-mode the
symbol will
appear.
To stop or modify the holiday program push the
button (chapter 4.5).
Option: By pushing the override button the occupied
temperature mode starts for a pre-programmed time (0:00-
24:00h; default 1h). The +h symbol will appear. The
override mode can be stopped by using the
FI
X
button.

- 9 -
4.2 Display and change of occupied/unoccupied temperature
The desired temperature for each control circuit can be programmed separately
The temperatures can be
changed within the range:
+3…+35 °C / 37 ...95 ºF
Push the DISP button to switch the current display
back to the main displa y (automatic after one
minute if no button pushed).
The current
occupied/unoccupied
temperatures can be
displayed by pushing or
button.
The values can be modified
by pushing +/-.
All modifications are saved
immediately.

- 10 -
4.3. To display or modify the base time and date of the controller
Cycle through the base time and date of the controller with the button. Modify any time or date
using +/-.
This function affects the base controller clock (all control circuits have a separate time program).
Push the button to display/modify time of day (in the picture: 14:03). Push the button again
to display/change the year (2007). Push the button a third time and the month and day (in this
case: 3rd month = March, 21 st day) is displayed. In the upper display, “3 Day” indicates the third
day in the week, or “Wednesday”. ( 1= Monday, etc.)
Push the button once more to switch the display back to the full normal clock display.
Press the DISP button to return to the base display,.
Setting the time and date
NOTE: symbols or figures, shown framed are blinking!
Month Day of
Month
Day of Week
To change the time
press the SEL button.
First the minutes start to
blink (03). Modified
using +/-.
After pushing the SEL
button again, the hours
will start to blink. (14)
The hour can also be
changed with the +/-
buttons.
The time of day setting
is completed using the
button.
The display returns to
the year.