REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-02T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Setting the speed for the
stroke
This setting is used for setting a % of the actuator stroke during which it will
slow down before reaching the setpoint value position.
Range: 0.1-20% - Value by default = 10%
Redefining the 4 mA
position
Used to set another position than 0% for the 4 mA value. This function is
useful for valves with an opening angle different from 90°.
Range: -50% +80% - Value by default = 0.0%
Redefining the 20 mA
position
Used to set another position than 100% for the 20 mA value. This function
is useful for valves with an opening angle different from 90°.
Range: 20% +220% - Value by default = 100.0%
Modification of the 4 mA
output signal
If a deviation is found on the 4mA output signal, this function is used to
adjust it. If the number is increased, the current is higher. If the number is
decreased, the current is lower.
Range: 000_481_A –Value by default 191_A
NB: always limit the lower value to 20 mA
Modification of the 20mA
output signal
If a deviation is found on the 20mA output signal, this function is used to
adjust it. If the number is increased, the current is higher. If the number is
decreased, the current is lower.
Range: 191_1000_A –Value by default 909_A
Used to set the response speed of the valve. The smaller the value, the less
sensitive the control. The bigger the value, the more sensitive it is. Increase
the value when the response speed is too low.
Setting range: 1x20x –Value by default 3x