When sufficient smoke has entered the chamber, an
alarm signal will take place by indicating with a
continuous illumination of the LED. After it alarms,
Reset each detector and/or control unit before
attempting to test the additional detectors in the same
zone. If the alarm fails in this step, it indicates a
defective unit, which requires service.
HEAT SENSOR TESTING
The detector to be tested should be subject to a flow of
warm air at a temperature between 140 and 180 .℉℉
Some domestic hair dryers can meet such requirement.
Proceed as follows:
1. Switch on the warm airflow and check that temperature
is correct and stable.
2. From a distance of inches, direct the airflow at the
guard protecting the thermistor. The detector should
alarm within 30 seconds.
3. When alarm is on, immediately remove the heat
source and check that the detector’s red LED is lit.
Reset the detector from the control panel.
4. If the detector fails to go into alarm within 30 seconds it
is too insensitive and needs to be returned to the
distributor for servicing.
5. After testing check that the system is set for normal
operation and notify the appropriate authorities that the
testing operation is complete and the system is active
again.
NOTES FOR USING DETECTOR
The National Fire Protection Association (NFPA)
states that duct smoke detector must not used as a
substitute for open area smoke detector. Duct smoke
detector is solely intended to use in the air handing
equipments for such purposes like dampers or
shutting down the air handing units.
NOT SUITABLE FOR INSTALLATION IN
AREAS WHERE AIR VELOCITIES EXCEED
300 ft/min.
MAINTENANCE
The recommended minimum requirement for detector
maintenance consists of an annual cleaning of dust from
the detector head by using a vacuum cleaner cleaning
program should be agreed to the individual environment
in conformance with NFPA-72A standard.
CAUTION: DO NOT ATTEMPT TO REMOVE THE
SCREWS, WHICH HOLD THE ASSEMBLY OF
SMOKE-SENSING CHAMBER AND PRINTED CIRCUIT
BOARD (PCB). THIS ASSEMBLY IS SEALED FOR
YOUR PROTECTION AND IS NOT INTENDED TO BE
SEPARATED FOR SERVICING BY USERS. OPENING
SUCH ASSEMBLY WILL VOID THE WARRANTY.
REFER TO THE TECHNICAL BULTTIN ISSUE NO.
STSD20080702S01, REV.D, Jul 02, 2008
SPECIFICATION
Model 2/4
wire
Heat
Sensor
Setting
Voltage
DC
(Max./Min.)
Standby
Current
(Max.)
Alarm
Current
(12/24V)
Surge
Current
(Max.)
Start-Up
Time
(Max.)
Permissible
Current
(Max.)
Cycle
Time Alarm contact Base
Model No. Safety
SD119-2 2 - 10.8~33V 80μA 22/55mA 160μA 30 Sec. 80mA 1-3 Sec. — 852001
SD119-2L 2 - 10.8~33V 80μA 22/55mA 160μA 30 Sec. 80mA 1-3 Sec. — 854001 EN54-7
SD119-2H 2
135±5℉10.8~33V 80μA 22/55mA 160μA 30 Sec. 80mA 1-3 Sec. — 852001
SD119-2HL 2
135±5℉10.8~33V 80μA 22/55mA 160μA 30 Sec. 80mA 1-3 Sec. — 854001
EN54-7
EN54-5
SD119-4(12V) 4 - 12V 80μA 30mA - 30 Sec. - 1-3 Sec. Form A 854001
SD119-4(24V) 4 - 24V 80μA 45mA - 30 Sec. - 1-3 Sec. Form A 854001 EN54-7
SD119-4H(12V) 4
135±5℉12V 80μA 30mA - 30 Sec. - 1-3 Sec. Form A 854001
SD119-4H(24V) 4
135±5℉24V 80μA 45mA - 30 Sec. - 1-3 Sec. Form A 854001
EN54-7
EN54-5
SD119-4AR 4 - 12/24V 80μA 30/45mA - 30 Sec. - 1-3 Sec. Form A/Auto Reset 854001
SD119-4ARB 4 - 12/24V 80μA 30/45mA - 30 Sec. - 1-3 Sec. Form A/Auto Reset 854001
SD119-4HAR 4
135±5℉12/24V 80μA 30/45mA - 30 Sec. - 1-3 Sec. Form A/Auto Reset 854001
SD119-4HARB 4 135±5℉12/24V 80μA 30/45mA - 30 Sec. - 1-3 Sec. Form A/Auto Reset 854001
SD119-4HB 4
135±5℉12/24V 80μA 30/45mA - 30 Sec. - 1-3 Sec. Form A/Auto Reset 854001
SD119-4B 4 12/24V 80μA 30/45mA - 30 Sec. - 1-3 Sec. Form A/Auto Reset 854001
Remark: L- remote indicator output; H-Heat sensor; AR-Auto-reset; B-Sound,Alarm contact with Form B (NC) available
LIMITED WARRANTY STATEMENT
SENTEK ELECTRONICS INC. declares that this product is free from defects in material and workmanship. And it will repair
or replace any product or part thereof which proves to be defective in workmanship or material for a period of twelve (12)
months from the date of purchase but not to exceed eighteen (18) months after shipment by the manufacturer. For a full
description of SENTEK’S LIMITED WARRANTY, which, among other things, limits the duration of warranties of
merchantability and fitness for a particular purpose and excludes liability for consequential damages. Please read the entire
LIMITED WARRANTY on the SENTEK quotation. Acceptance of order and/or original invoice which will become part of your
sales agreement. Please contact SENTEK directly for a return merchandise authorization (RMA) number before returning
goods to the factory in Ningbo, China, Shipment must be prepaid and SENTEK will repair or replace your returned detector.
SDMI119080702, REV C
Sentek Electronics Co., Ltd.
448 Yingchun road, Wangchun Industril zone, Ningbo City
315175, Zhejiang, China
Manufacturer:
Tel: 86-574-8715 3117 Fax: 86-574-8715 5951