connecti ng 15 instrument s
[3] Support single-point and multi-point mode at the side of HART
[4] Single-point mode, support data burst operation of slave device
[5] Support all commands of the HART protocol
[6] Each HART command can be configured for change-of-state output, polling
output, initialization output or disable output
[7] HART per channel supports up to 128 user command s , HART output data buffer
up to 1000 bytes, and t he input data buffer up to 1600 bytes .
[8] Can choose to use an internal or external sampling resistor
[9] Serial RS232, RS485, RS232 optional , baud rate: 300K, 600K, 1200K, 2400K,
9600K, 19.2 K, 38.4K, 57.6K, 115.2Kbps optional
[10] Serial side can be configured for MODBUS slave, support function code: 03H,
04H, 06H, 10H .
[11] MODBUS slave support RTU and ASCII communication .
[12] The serial port can be configured as universal mode, and achieve transparent
data transmission with HART slave device s.
[13] Power: 24VDC (9V~30V), 80 mA (24VDC );
[14] Working circumstance temperature: -20~60 ℃, Humidity: 95%;
[15] External dimensions: (Width )40mm* (Height )125mm* (Depth)110mm;
[16] Installation: 35mm DIN RAIL;
[17] Protection Level: IP20;