Firefly Manual with Four Channel Control_Revision 00_05_16_2017
Sigma Services, Inc. 813-737-1904
NOTE: When connecting the ESTOP control cable to the controller,
make note of the channel of the burner head to which the propane
tank/ESTOP valve is connected to; i.e. CH#1, Ch#2, Ch3. The channel
to which the Burner Head is connected should also be the channel to
which the ESTOP cable is connected.
NOTE: There is one 4-pin ESTOP valve control cable required for
each propane tank installed. For 4 channel controllers, this can be
up to 4 tanks while for 8 channel controllers this can be up to 8 tanks.
•
Connect the regulator to the propane tank fitting (NOTE: propane tanks
use left-handed threads)
NOTE: There is one regulator required for each propane tank. The
regulator is included as part of the standard Sigma Services ESTOP
control cable assembly.
•
Connect the gas hose from the burner head to the ESTOP valve assembly.
NOTE: A small ball valve located on the quick-connect fitting
prevents the hose from being attached or detached while the valve is
open. Close valve to attach the hose.)
•
At each installed propane tank, open the supply valve.
•
At each installed ESTOP valve assembly, open the manual isolation valve.
WARNING: Using an approved leak detection method, verify no gas
leaks are detected between each propane tank and connected ESTOP
valve assembly before proceeding!!!!
•
At each Installed Burner Head, Open the manual isolation valve.
•
At the flame control panel, connect a 120Vac, 60Hz power source.
•
At the flame control panel ,use the Sigma Services provided key to place
the MODE switch in desired operational mode (MANUAL, OFF, or DMX are
the available modes).
•
At the flame control panel, use the Sigma Services provided key to release
the ESTOP Switch; Verify the ESTOP valve assembly is energized.
WARNING: Using an approved leak detection method, verify no gas
leaks are detected between each ESTOP valve assembly and
connected Burner Head assembly before proceeding!!!!
•
At the ESTOP valve assembly, check the pressure regulator is set to the
desired operating pressure (20psi is the nominal factory setting); adjust the