1 Overview - Power supply for use with wired handheld scanner Zone 1 2
2 Overview - Power supply for use with Bluetooth scanner Zone 1 3
3 Important Notes on the Operating Instructions 4
3.1. Safety information ......................................................................................... 4
3.2 Notes on the Operating Instructions ......................................................................................... 5
3.3 General Caution ......................................................................................... 6
4 Product Information 8
4.1 Explosion protection ....................................................................................... 8
4.2 Technical Data explosion protection ....................................................................................... 8
4.3 Type Numbers ...................................................................................... 12
4.4 Serial Numbers ...................................................................................... 12
4.5 Application ...................................................................................... 12
5 Introduction to Operation of the Power Supply 13
5.1 Information on the design of the power supply ................................................ 13
5.2 Pin assignment in the Ex-e connection box RS232 and USB ................................................ 14
5.3 Pin assignment in the Ex-i connection box RS232 ................................................ 15
5.4 Pin assignment in the Ex-i connection box USB ................................................ 16
6 Attachment 17
6.1 EC type examination certificate SDVM125ex ................................................................... 17
6.2 Certificate of Confirmity power supply SDVM125ex ................................................................... 23
7 Contact 30

SDVM125ex_BA_en_003 2
1 Overview - Power supply for use with wired handheld scanner Zone 1

SDVM125ex_BA_en_003 3
2 Overview - Power supply for use with Bluetooth scanner Zone 1

SDVM125ex_BA_en_003 4
3Important Notes on the Operating Instructions
3.1 Safety information
Warnings are highlighted by a special symbol and a different font colour.
Danger
Non-compliance may result in life-threatening situations.
This warning must be heeded.
Warning
This type of warning concerns dangerous situations that may result in light or small inju-
ries.
Info
Important and helpful notes and information.

SDVM125ex_BA_en_003 5
3.2 Notes on the Operating Instructions
Before starting up the equipment please read the Manual thoroughly.
The Operating Instructions contain important information on functionality as well as safety rules. If these
are not heeded, normal operations within hazardous areas cannot be guaranteed.
The notes contained in this manual are important for starting up and operating the product.
These instructions may be updated at any time. Sigmann DELTA GmbH reserves the right to make changes to
this document.
Before using the product, users must ensure that they have the most up-to-date version of the operating instruc-
tions. To be sure this is the case, please check Sigmann DELTA's website at www.Sigmann-DELTA.de or contact
one of the company's staff.
The drawings contained in these operating instructions are for illustration purposes only and may differ somewhat
from the actual design.
No changes may be made to the device that were not intended or approved
by Sigmann DELTA.
Incorrect handling of the device may result in the termination of the operating permit for hazardous areas.
Non-adherence to the instructions will void any warranty.

SDVM125ex_BA_en_003 6
3.3 General caution
Caution / Notes
The devices may only be operated when fully assembled.
The device must be switched off immediately if it is likely that as a consequence
of damaging impact or general peculiarities the device can no longer be safely
operated. (e.g. ingress of water or other fluids, temperatures outside of the
specified range,...)
General statutory requirements or health and safety rules and accident preven-
tion guidelines and environmental laws must be adhered to (e.g. the German
Occupational Health and Safety regulation).
Users must not open the device.
Users must not make any changes to the device. Components may not be ex-
changed or replaced. If non-specified components are used, explosion protec-
tion is no longer guaranteed.
If the enclosure is in any way damaged, the device must be removed from the
hazardous area immediately.
In accordance with IEC 60079-19 and IEC 60079-17, operators of electric
plants in hazardous areas are obliged to have them serviced by qualified elec-
tricians.
Do not insert any sharp objects into the enclosure or any other openings of the
power supply. Any openings at the device must not be covered or blocked.
The device and any accessories must be properly disposed of, i.e. as legally
specified, for example by a certified company.
Notes on installation
Electrical plants are subject to certain regulations concerning installation and
operation (e.g. RL 99/92/EG, RL 94/9EG, or the national rules such as
IEC 60 079-14 and VDE 0100).
In the hazardous area it is the operator's responsibility to carry out any repair
and maintenance in compliance with applicable rules.

SDVM125ex_BA_en_003 7
Maintenance
Provided the device is operated and assembled according to instructions and
the ambient requirements are being met continuous maintenance is not neces-
sary.
Servicing
Operators of electric equipment in hazardous areas are obliged to have them
serviced by qualified electricians (IEC 60079-19 and IEC 60079-17).
Repairs
Repairs may only be carried out by the manufacturer or by persons trained and
commissioned for this purpose by the manufacturer.
The device is closed ex-factory. It may only be opened in the factory by specifically trained personnel.
Operation
Before operating the device you must ensure that all necessary components are
available.

SDVM125ex_BA_en_003 8
4Product information - SDVM125ex Type SD.211XXX1.00
SDVM215ex Power Supply
4. Explosion
protection
II 2G Ex eb qb [ib IIC/IIB] IIC T4
II 2D Ex tb [ib] IIIC T135°C
II 2G Ex e q [ib IIC/IIB] IIC T4 Gb
II 2D Ex tb [ib] IIIC T135°C Db
-25°C ≤ Ta ≤ +60°C
Certification
IBExU09ATEX1051
IECEx IBE 15.0018
Protection category
IP65
Manufacturer
Sigmann DELTA GmbH
Hauptstraße 53
74928 Hüffenhardt
Germany
4.2 Technical data explosion protection
Non-intrinsically safe supply circuit
SD.211.1XX1.00
Rated voltage UNDC +12 V ± 10 %
Power input P = ca. 3,3W (max. 6,6W)
SD.211.2XX1.00
Rated voltage UNDC +24 V ± 25 %
Power input P = ca. 3,7W (max. 7,1W)
SD.211.3XX1.00
Rated voltage UNAC 90 V to 253 V, 50 - 60 Hz
Power input P = ca. 4W (max. 16W)
Non-intrinsically safe data circuit
SD.211.XXX1.XX
RS232
RS422
USB
±12 V / 4 mA
+12 V / -7 V / 4 mA
+5 V / 68 mA