7User Guide DP300E
7OA0001 GB rev.09
Programming parameters
NOTE:
The system must not run in
bypass mode for longer
periods of time as the
batteries will not be re-
charged
4.0 Programming parameters
4.1 General
Some operating parameters can be programmed directly from the keyboard, but
this has already been done during the commissioning. Unless you are quite sure of
the consequence of changing the following parameters, then let it be a task for your
local dealer, if needed.
Parameters are programmed as shown in the example 4.2.3.
4.2 Parameters
4.2.1
Parameter Setting* Comments
Bypass YES, NO “YES” will switch the system into
bypass mode
Language GB, D, F, Language of text in display
DK, S, SF
NL, PL, CZ
E, P, SK, H
Autostart YES, NO Automatic restart by mains return.
Ensures quick battery recharge.
Remote shutdown YES, NO Shutdown of UPS by remote signal
active
Remote shutdown HIGH, LOW Nature of remote shutdown signal polarity
Remote shutdown time 0, 1, 2, 3, 4 Time delay on remote shutdown of UPS
5, 6, 7, 8, 9
10 min.
Battery capacity test - Initiates check of back-up time.The
measured time is from start until it reaches
low DC warning level (See section 8.4)
Battery monitor test** - Initiates check of battery condition by
25% discharging.
Automatic battery test** NO, 3, 6 Activates the battery monitor test in cyclic
intervals (Unit - months)
Battery monitor reset** - Pressing the and key after
selecting this parameter resets alarms
and flushes messages in the alarm stack
Boost charge YES, NO “YES” results in boost charge (10 hours)
Autoboost charge YES, NO “YES” results in boost charge after battery
operation (10 hours)
Enter new date YYMMDD Local date can be entered
Enter new time HHMMSS Local time can be entered
*Text in bold letters are the standard setting
** Only for systems with Battery Monitor active