Control Unit
GFCD 16
www.simatek.com
Hotline: +45 4046 7525
Rev.:
7.2 Parameters selection
Connecting the power supply [4]:
L = phase, N = neutral
On/off switch [1] on 1. The display [7] will indicate for a few seconds the release code of Simatek GFCD 16. Once the
code disappears the display [7] will show the letter P followed by the ΔP value of the filter.
LED OK [18] is on:
LED Auto [16] if Simatek GFCD 16 is in automatic mode
or LED Pause [12] if Simatek GFCD 16 is in manual mode
ATTENTION!The display [7] must show a ΔP value of “0” kPa when the fan is switched off. Otherwise adjust the zero
ΔP as indicated in paragraph 13, page 9.
1) Press SELECT MENU [9]:
The no. 1 will flash on the display [7]:
Using keys “+/–” [10] select Manual or Automatic mode. (0 = Manual, 1 =
Automatic).
2) Press SELECT MENU [9]:
The no. 2 will flash on the display [7]:
Using keys “+/–” [10] select the No. of valves you wish to connect (example:
if you wish to connect 4 valves to Simatek GFCD 16, select 4). When skipping
this step of the menu the Simatek GFCD 16 will automatically set the No. of
valves as if they were all connected (if your model is Simatek GFCD 16: 4),
then 4 valves will be recognized, (if your model is Simatek GFCD 16: 12),
then 12 valves will be recognized.
3) Press SELECT MENU [9]:
The no. 3 will flash on the display [7]:
Using keys “+/–” [10] select Pulse Time.
(0.01-9.99s).
4) Press SELECT MENU [9]:
The no. 4 will flash on the display [7]:
Using keys “+/–" [10] select Pause Time in Manual mode. (1-999 sec).
Caution: if you have selected Automatic in step 1) of the menu you have to
select Pause Time in Shut down cleaning.
5) Press SELECT MENU [9]:
The no. 5 will flash on the display [7]:
Using keys “+/–” [10] select Pause Time in Automatic mode.
(1-999s).
Caution: skip this step if you have selected Manual in step 1).
6) Press SELECT MENU [9]:
The no. 6 will flash on the display [7]:
Using keys “+/–” [10] select operating ΔP.
(0.01–3.00 kPa).
Each time the ΔP of the filter exceeds the Operating ΔP, filter cleaning will
begin. As soon as ΔP of the filter goes below the Operating ΔP, filter cleaning
will be interrupted (with differential of – 0.05 kPa).
7) Press SELECT MENU [9]:
The no. 7 will flash on the display [7]:
Using keys “+/–” [10] select Set Delta-P Alarm.
(0.01-3.00 kPa).
If the Delta-P Alarm value is reached in the filter, Simatek GFCD 16 gives an
alarm. Display shows “PP1”. It is possible to have signalling if you connect
relay’s terminals C and NC [24].
8) Press SELECT MENU [9]:
The no. 8 will flash on the display [7]:
Using keys “+/–” [10] select No of cycles of Shut down cleaning.
(0-99).
(Select 0 if you do not wish to have Shut down cleaning).
Shut down cleaning starts automatically when the ΔP of the filter goes below
0.10 kPa and Fan contact is open.
Caution: Shut down cleaning will start only when MPS is working in automatic
mode
9) Press SELECT MENU [9]:
The no. 9 will flash on the display [7]:
Using keys “+/–” [10] select ΔP Pre-coating.
(0.01–3.00 kPa).
Both in Automatic and Manual mode the cleaning of the filter will start only