SJE®5VFDC-3000 Controller User Manual
CONTROLLER SETPOINTS LIST
STATION NAME
START UP DATE
CONTROLLER REVISION
SETTING MIN MAX UNITS DEFAULT USER SETTING
BASIC SETTINGS
Setpoint Pressure 0.0 *1 PSI 60.0
Sleep Frequency 0.0 *2 Hz 35.0
Sleep Delay Time 0.0 999.9 Seconds 10.0
Minimum Frequency 0.0 *2 Hz 30.0
Maximum Frequency 0.0 65.0 Hz 60.0
Lead Pump Start Dierential Pressure *1 0.0 PSI -5.0
Lag Pump Start Dierential Pressure *1 0.0 PSI -7.0
Lag Pump Stop Dierential Pressure 0.0 *1 PSI 7.0
Alternation Alternate/P1 Lead/P2 Lead/P3 Lead Alternate
Alternation Time 1.0 999.9 Hours 24.0
Low Pressure Alarm 0.0 *1 PSI 15.0
Low Pressure Alarm Delay Time 0.0 999.9 Seconds 20.0
Low Pressure Alarm Reset Delay Time 0.0 999.9 Minutes 0.0
High Pressure Alarm 0.0 *1 PSI 75.0
Low Water Delay Time 0.0 999.9 Seconds 10.0
PUMP SETTINGS
Acceleration 0.0 3600.0 Seconds 3.0
Deceleration 0.0 3600.0 Seconds 3.0
Thrust Bearing Frequency 0.0 *2 Hz 0.0
Thrust Bearing Acceleration 0.0 3600.0 Seconds 2.0
Pump 1 Overload Amps 0.0 999.9 Amps *3
Pump 1 Motor Voltage 0.0 999.9 Volts *3
Pump 2 Overload Amps 0.0 999.9 Amps *3
Pump 2 Motor Voltage 0.0 999.9 Volts *3
Pump 3 Overload Amps 0.0 999.9 Amps *3
Pump 3 Motor Voltage 0.0 999.9 Volts *3
ADVANCED SETTINGS
Sensor Range 1.0 999.9 PSI 200.0
Sensor Oset -999.9 999.9 PSI 0.0
PID Proportional Term 0 999 70
PID Integral Term 0 999 35
PID Derivative Term 0 999 1
Setpoint Pressure 2 0.0 *1 PSI 40.0
Pipe Fill Frequency 0.0 *2 Hz 30.0
Pipe Fill Time 0.0 999.9 Seconds 0.0
Low Suction Delay Time 0.0 999.9 Seconds 10.0
Low Suction Reset AUTO/MANUAL AUTO
Low Suction Reset Delay Time 0.0 999.9 Seconds 10.0
Idle Prevention Exercise Schedule 0.0 999.9 Days 0.0
Pump 1 Jockey ENABLED/DISABLED DISABLED
Jockey Pump Stop Delay Time 0 999 Seconds 0
Number of Pumps 1 3 3
Maximum Pumps On 1 3 3
Relay 1 Function *4 GEN. ALARM
Relay 2 Function *4 HIGH PRESS
Relay 3 Function *4 LOW PRESS
Relay 4 Function *4 P1 RUN
Relay 5 Function *4 P2 RUN
Relay 6 Function *4 P3 RUN
VFD 1 Hand Speed 0.0 *2 Hz 45.0
VFD 2 Hand Speed 0.0 *2 Hz 45.0
VFD 3 Hand Speed 0.0 *2 Hz 45.0
Language ENGLISH/ESPAÑOL ENGLISH
*1 - Value based on “Sensor Range” setting
*2 - Value based on “Maximum Frequency” setting
*3 - Value based on output rating of variable frequency drive
*4 - Settings include: P1 Run, P2 Run, P3 Run, P1 Fault, P2 Fault, P3 Fault, High Press, Low Press, Low Suction, Low Water, General Alarm