Skyworth SUV2-H18/3CFA-N Bedienungsanleitung

MODELS:
SUV2-H18/3CFA-N
SUV3-H24/3CGA-N
SUV4-H28/3CGA-N
SUV4-H36/3CHA-N
SUV5-H42/3CHA-N
(Refrigerant R32)

CONTENT
1. Safety Precautions...................................................................................... 1
2. Specifications.............................................................................................. 3
2.1 Unit Specifications..................................................................................................... 3
2.2 Operation Characteristic Curve ............................................................................. 13
2.3 Capacity Variation Ratio According to Temperature ............................................ 13
2.4 Noise Curve .............................................................................................................. 14
3. Construction Views................................................................................... 15
3.1 Outdoor Unit ............................................................................................................. 15
4. Refrigerant System Diagram.................................................................... 18
5. Schematic Diagram................................................................................... 18
5.1 Electrical Wiring ....................................................................................................... 18
6. Installation Manual.................................................................................... 22
6.1 Standard Accessory Parts....................................................................................... 22
6.2 Installation Location and Matters Needing Attention .......................................... 23
6.3 Check after installation........................................................................................... 31
6.4 Test operation.......................................................................................................... 31
6.5 Conf guration of connection pipe.......................................................................... 32
6.6 Pipe expanding method.......................................................................................... 33
7. Exploded Views and Parts List ................................................................ 34
7.1 Outdoor Unit ............................................................................................................. 34
8. Troubleshooting ........................................................................................ 46
8.1 PCB Printed Diagram............................................................................................... 46
9. Removal Procedure .................................................................................. 50
9.1 Removal Procedure of Outdoor Unit(18K)............................................................. 50
9.2 Removal Procedure of Outdoor Unit(24K、28K)................................................... 56
9.3 Removal Procedure of Outdoor Unit(36K、42K)................................................... 62

Summary and Features
Outdoor Unit
18K
24K、28K

36K/42K

1
Safety Precautions
1. Safety Precautions
Installing, starting up, and servicing air conditioner can behazardous due to system pressure, electrical components, and
equipment location, etc.Only trained, qualied installers and service personnel areallowed to install, start-up, and service this
equipment.Untrained personnel can perform basic maintenance fun-ctions such as cleaning coils. All other operations should be
performed by trained service personnel.When handling the equipment, observe precautions in themanual and on tags, stickers,
and labels attached to theequipment. Follow all safety codes. Wear safety glasses andwork gloves. Keep quenching cloth
and re extinguisher nearby when brazing.Read the instructions thoroughly and follow all warnings orcautions in literature and
attached to the unit. Consult localbuilding codes and current editions of national as well as local electrical codes.
Recognize the following safety information:
◆ Make sure the outdoor unit is installed on a stable, level surface with no accumulation of snow, leaves, or trash beside.
◆ Make sure the ceiling/wall is strong enough to bear the weight of the unit.
◆ Make sure the noise of the outdoor unit does not disturb neighbors.
◆ Follow all the installation instructions to minimize the risk of damage from earth quakes, typhoons or strong winds.
◆ Avoid contact between refrigerant and re as it generate spoisonous gas.
◆ Apply specied refrigerant only. Never have it mixed with any other refrigerant. Never have air remain in the refrigerant line as
it may lead to rupture and other hazards.
◆ Make sure no refrigerant gas is leaking out when installation is completed.
◆ Should there be refrigerant leakage, the density of refrigerant in the air shall in no way exceed its limited value, or it may lead
to explosion.
◆ Keep your ngers and clothing away from any moving parts.
◆ Clear the site after installation. Make sure no foreign objects are left in the unit.
◆ Always ensure effective grounding for the unit.
Incorrect handling could result inpersonal injury or death. Incorrect handling may result inminor injury,or damage to product
or property.
Warning Caution
Warning Caution
All electric work must be performed by a licensed technician
according to local regulations and the instructions given in
this manual.
Before installing, modifying, or servicing system,
mainelectrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
Never supply power to the unit unless all wiring and tubing
are completed, reconnected and checked.
This system adopts highly dangerous electrical voltage.
Incorrect connection or inadequate grounding can cause
personal injury or death. Stick to the wiring diagram and all
the instructions when wiring.
Have the unit adequately grounded in accordance with local
electrical codes.
Have all wiring connected tightly. Loose connection may lead
to overheating and a possible re hazard.
All installation or repair work shall be performed by your
dealer or a specialized subcontractor as there is the risk of
re, electric shock, explosion or injury.
Never install the unit in a place where a combustible gas
might leak, or it may lead to re or explosion.
Make a proper provision against noise when the unit is
installed at a telecommunication center or hospital.
Provide an electric leak breaker when it is installed in a
watery place.
Never wash the unit with water.
Handle unit transportation with care. The unit should not be
carried by only one person if it is more than 20kg.
Never touch the heat exchanger ns with bare hands.
Never touch the compressor or refrigerant piping without
wearing glove.
Do not have the unit operate without air lter.
Should any emergency occur, stop the unit and disconnect
the power immediately.
Properly insulate any tubing running inside the room to
prevent the water from damaging the wall.

2
Safety Precautions
Safety Precautions
Please read this operating manual carefully before operating the unit.
Appliance filled with flammable gas R32.
Before use the appliance, read the owner's manual first.
Befoer install the appliance,read the installation manual first.
Befoer repair the appliance ,read the service manual first.
The figures in this manual may be different with the material objects ,please refer to the material objects for reference.
To realize the function of the air conditioner unit, a special refrigerant circulates in the system.The used refrigerant is the fluoride
R32,which is specially cleaned.The refrigerant is flammable and inodorous. Furthermore,it can leads to explosion under certain
condition.But the flammability of the refrigerant is very low. It can be ignited only by fire.
Compared to common refrigerants, R32 is a nonpolluting refrigerant with no harm to the ozonosphere.The influence upon the
greenhouse effect is also lower. R32 has got very good thermodynamic features which lead to a really high energy efficiency. The units
therefore need a less filling.
The Refrigerant
WARNING:
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture.Should repair
be necessary, contact your nearest authorized Service Center.
Any repairs carried out by unqualified personnel may be dangerous.
The appliance shall be stored in a room without continuously operating ignition sources.
(For example: open flames, an operating gas appliance or an operating electric heater.)
Do not pierce or burn.
Appliance shall be installed, operated and stored in a room with a floor area larger than
"X"m2(see table 1).(only applies to appliances that are not fixed appliances)
Appliance filled with flammable gas R32. For repairs,strictly follow manufacturer's
instructions only.
Be aware that refrigerants not contain odour.
Read specialist’s manual.

3
Specifications
Specifications
2. Specifications
2.1 Unit Specifications
Model -SUV2-H18/3CFA-N
Product Code -KEJ001W0170
Cooling Capacity KW 5.2
Heating Capacity KW 5.2
EER W/W 3.71
COP W/W 4.16
SEER 6.10
SCOP(Average) 4.00
Energy Class A++/A+
Sound Pressure Level dB(A) 54
Sound Power Level dB(A) 62
Rated Voltage V 220-240
Rated Frequency Hz 50
Phases 1
Min/Max. Voltage V~ 184/264
Cross-sectional Area of Power Cable Conductor mm21.50
Recommended Power Cable(Core) 3
Fuse Current A 16
Cooling Power Input KW 1.40
Heating Power Input KW 1.25
Cooling Rated Power Input KW 2.50
Heating Rated Power Input KW 2.25
Cooling Current Input A 6.21
Heating Current Input A 5.55
Cooling Rated Current Input A 11.09
Heating Rated Current Input A 9.98
Compressor Trademark PANASONIC
Compressor Manufacturer PANASONIC WANBAO APPLIANCES COMPRESSOR
(GUANGZHOU) CO.,LTD.
Compressor Model 9RD132ZAA21
Compressor Type1 Inverter Rotary
Compressor Capacity W 3615
Compressor Power Input W 1330
Compressor Rated Load Amp (RLA) A 6.7
Compressor Locked Rotor Amp (L.R.A) A 23
Compressor Thermal Protector KSD301-11.5/10BC22X2-S4
Compressor Crankcase W 20
Chassis Electrical Heater Power Input W 72
Chassis Electrical Heater Current A 0.32

4
Specifications
Specifications
Model -SUV2-H18/3CFA-N
Fan Type Axial-flow
Fan Diameter-height mm 522-140
Fan Diameter-height inch 20.6-5.5
Motor Model SGW60M-ZL
Motor Type DC motor
Motor Insulation Class E
Motor Safe Class IP44
Motor Full Load Amp(FLA) A 1.03
Fan Motor Type DC motor
Fan Motor Speed rpm 750
Fan Motor Power Output W 60
Fan Motor Power Input W 85
Condenser Material Aluminum Fin-copper Tube
Condenser Face Area m20.55
Condenser Pipe Diameter mm φ7
Condenser Number of Rows 1.5
Condenser Tube Pitch(a)×Row Pitch(b) mm 22×19.05
Condenser Fin Pitch mm 1.4
Condenser Length(L) × Height(H) × Width(W) mm 875×660×38.1
Permissible Excessive Operating Pressure for the
Discharge Side MPa 4.3
Permissible Excessive Operating Pressure for the
Suction Side MPa 2.5
Cooling Operation Ambient Temperature Range ℃-15~55
Heating Operation Ambient Temperature Range ℃-20~30
Maximum drive IDU NO. unit 2
Defrosting Method Automatic Defrosting
Isolation I
Moisture Protection IP24
Overload Protector /
Climate Type T1
Refrigerant R32
Refrigerant Charge kg 1.10
Throttling Method Electron expansion valve
Dimension of Outline(W) mm 960
Dimension of Outline(D) mm 396
Dimension of Outline(H) mm 700
Connection Pipe Max. Height Distance(indoor and
indoor) m4
Max. equivalent connection pipe length(outdoor to
last indoor) m10
Connection Pipe Max. Length Distance(total
lenght) m20

5
Specifications
Specifications
Model -SUV3-H24/3CGA-N
Product Code -KEJ001W0180
Cooling Capacity KW 7.00
Heating Capacity KW 7.00
EER W/W 3.68
COP W/W 4.12
SEER 6.10
SCOP(Average) 4.00
Energy Class A++/A+
Sound Pressure Level dB(A) 55
Sound Power Level dB(A) 68
Rated Voltage V 220-240
Rated Frequency Hz 50
Phases 1
Min/Max. Voltage V~ 184/264
Cross-sectional Area of Power Cable Conductor mm22.50
Recommended Power Cable(Core) 3
Fuse Current A 25
Cooling Power Input KW 1.90
Heating Power Input KW 1.70
Cooling Rated Power Input KW 3.30
Heating Rated Power Input KW 3.20
Cooling Current Input A 8.43
Heating Current Input A 7.54
Cooling Rated Current Input A 14.64
Heating Rated Current Input A 14.20
Compressor Trademark PANASONIC
Compressor Manufacturer PANASONIC WANBAO APPLIANCES COMPRESSOR
(GUANGZHOU) CO.,LTD.
Compressor Model 9RD160ZAA21
Compressor Type1 Inverter Rotary
Compressor Capacity W 4550
Compressor Power Input W 1645
Compressor Rated Load Amp (RLA) A 6.9
Compressor Locked Rotor Amp (L.R.A) A 25
Compressor Thermal Protector KSD301-11.5/10BC22X2-S4
Compressor Crankcase W 20
Chassis Electrical Heater Power Input W 96
Chassis Electrical Heater Current A 0.4

6
Specifications
Specifications
Model -SUV3-H24/3CGA-N
Fan Type Axial-flow
Fan Diameter-height mm 21.6-4.9
Fan Diameter-height inch SGW120M-ZL
Motor Model DC motor
Motor Type DC motor
Motor Insulation Class E
Motor Safe Class IP44
Motor Full Load Amp(FLA) A 0.96
Fan Motor Type DC motor
Fan Motor Speed rpm 750
Fan Motor Power Output W 120
Fan Motor Power Input W 165
Condenser Material Aluminum Fin-copper Tube
Condenser Face Area m20.73
Condenser Pipe Diameter mm φ7
Condenser Number of Rows 2
Condenser Tube Pitch(a)×Row Pitch(b) mm 22×19.05
Condenser Fin Pitch mm 1.4
Condenser Length(L) × Height(H) × Width(W) mm 970×748×38.1
Permissible Excessive Operating Pressure for the
Discharge Side MPa 4.3
Permissible Excessive Operating Pressure for the
Suction Side MPa 2.5
Cooling Operation Ambient Temperature Range ℃-15~55
Heating Operation Ambient Temperature Range ℃-20~30
Maximum drive IDU NO. unit 3
Defrosting Method Automatic Defrosting
Isolation I
Moisture Protection IP24
Overload Protector /
Climate Type T1
Refrigerant R32
Refrigerant Charge kg 1.50
Throttling Method Electron expansion valve
Dimension of Outline(W) mm 990
Dimension of Outline(D) mm 426
Dimension of Outline(H) mm 790
Connection Pipe Max. Height Distance(indoor and
indoor) m5
Max. equivalent connection pipe length(outdoor to
last indoor) m20
Connection Pipe Max. Length Distance(total
lenght) m60
Dieses Handbuch passt für folgende Modelle
4
Inhaltsverzeichnis
Andere Skyworth Klimaanlage Handbücher

Skyworth
Skyworth SMVH09D-1B1A3NA Bedienungsanleitung

Skyworth
Skyworth SMVH24A-5C1A3NG Bedienungsanleitung

Skyworth
Skyworth SMVH09B-2A2A3NG Bedienungsanleitung

Skyworth
Skyworth SAVH12A-A1NAO Bedienungsanleitung

Skyworth
Skyworth SDVH12M-A1NBI/P Bedienungsanleitung

Skyworth
Skyworth SKVH09A-A3NAI Bedienungsanleitung

Skyworth
Skyworth SDVH12M-A3NAI Bedienungsanleitung