Sola HD STFE Elite Series Bedienungsanleitung

Active Tracking® Filters
STFE Elite Series
Instruction Manual

STFE Elite Instruction Manual • ii
While every precaution has been taken to ensure accuracy and completeness in this
manual, EGS Electrical Group, LLC. assumes no responsibility, and disclaims all liability for
damages resulting from use of this information or for any errors or omissions.
The SolaHD and Emerson logos are registered in the U.S. Patent and Trademark Ofce. All
other product or service names are the property of their registered owners.
©2010 EGS Electrical Group, LLC. All rights reserved. Specications are subject to change
without notice.
Aunque se han tomado todas las precauciones para asegurar la exactitud y acuciosidad
de este manual, EGS Electrical Group, LLC. no asume responsabilidad alguna, y rechaza
toda responsabilidad por daños que pudieran resultar debido al uso de esta información o
por cualquier error u omisión.
El SolaHD y los logos de Emerson son registrados en la Ocina de patentes de EEUU.
Todos los otros nombres del producto o el servicio son la propiedad de sus propietarios
registrados.
©2010 EGS Electrical Group, LLC. Todos los derechos reservados en el mundo entero.
Las especicaciones pueden cambiar sin previo aviso.
Bien que toutes les précautions aient été prises an d’assurer que les renseignements du
présent manuel sont complets et exacts, EGS Electrical Group, LLC. n’assume aucune
responsabilité, et décline toute responsabilité pour des dommages découlant de l’utilisation
de cette information ou de toute erreur ou omission.
Les logo de SolaHD et Emerson sont enregistrés dans l’U.S. Patent and Trademark Ofce.
Tous l’autres produit ou les noms de service sont la propriété de leurs propriétaires inscrits.
©2010 EGS Electrical Group, LLC. Tous droits réservés mondialement. Les caractéris-
tiques techniques sont sujettes à modication sans préavis.

Contents/Contenido/Contenus
STFE Elite Instruction Manual • iii
Introduction ............................................................................................................................................... 4
Warnings Dened ..................................................................................................................................... 4
Pre-Installation ...................................................................................................................................... 5–6
Installation ................................................................................................................................................ 7
Technical Specications ........................................................................................................................... 8
Dimensional Drawings .............................................................................................................................. 9
System Design ....................................................................................................................................... 10
Troubleshooting/Service/Maintenance ................................................................................................... 11
Product Registration & Warranty Information ......................................................................................... 11
Introducción ............................................................................................................................................ 12
Denición de advertencias ..................................................................................................................... 12
Antes de la instalación ...................................................................................................................... 13–14
Instalación .............................................................................................................................................. 15
Especicaciones técnicas ....................................................................................................................... 16
Planos dimensionales ............................................................................................................................. 17
Diseño del sistema .................................................................................................................................. 18
Diagnóstico de problemas/servicio/mantenimiento ................................................................................ 19
Inscripción del producto y información sobre la garantía ....................................................................... 19
Introduction ............................................................................................................................................. 20
Dénition des avertissements ................................................................................................................. 20
Préinstallation ................................................................................................................................... 21–22
Installation .............................................................................................................................................. 23
Caractéristiques techniques ................................................................................................................... 24
Dessins dimensionnels ........................................................................................................................... 25
Conception du système .......................................................................................................................... 26
Dépannage/Entretien/Maintenance ........................................................................................................ 27
Enregistrement du produit et information sur la garantie ........................................................................ 27

English Version STFE Elite Instruction Manual • 4
Introduction
The STFE Elite Series combines rugged, high-energy transient protection with
the original Active Tracking® Filter technology to provide protection against the full
spectrum of voltage transients and surges.
Proper installation is required for maximum system performance. To ensure
a quality installation, the installer should read the entire manual and follow all
instructions before and during the installation.
These instructions do not replace national or local electrical codes. Check appli-
cable electrical codes to ensure compliance. Installation of the STFE Elite Series
should only be performed by qualied personnel.
Warnings Dened
Indicates an imminently hazardous situation
that, if not avoided, will result in death or serious injury.
This signal word is limited to the most extreme situations.
Indicates a potentially hazardous situation that,
if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation that,
if not avoided, may result in minor or moderate injury. It
may also be used to alert against unsafe practices.

English Version STFE Elite Instruction Manual • 5
Preinstallation
The unit is designed for indoor operation in ambient temperatures
of -40ºC (-40ºF) to +60ºC (+140ºF) with a relative humidity of 0% to 95% (non-
condensing).
All units provided with terminal blocks must be
installed inside an enclosure and located so as to prevent accidental contact with
terminals during maintenance and service.
All electrical connections must be installed by a licensed electrician. All wiring
must comply with the National Electrical Code (NEC) and applicable local codes.
The total current draw that a unit may continu-
ously handle is provided in the Voltage, Current and Power Congurations table
on page 6.
Overloading the unit can permanently damage the device.
The nominal operating voltage for each model is provided in
the Voltage, Current and Power Congurations table on page 6.
Failure to use the unit at its rated voltage can permanently damage the
unit or provide inadequate protection.
Input and output ground terminals must be connected for proper operation.
Grounding is not only required for safety, but also for equipment performance.
Incorrect grounding can reduce or impede the operation of the unit.

English Version STFE Elite Instruction Manual • 6
Catalog Number Load Current Minimum Wire Size*
(AWG Suggested)
Fuse/Circuit Breaker Ampacity
Suggest Max
Single-Phase Models (120 V ac)
STFE030-10N 3.0 A 24 3.0 A 3.75 A
STFE050-10N 5.0 A 22 5.0 A 6.25 A
STFE100-10N 10.0 A 20 10.0 A 12.5 A
STFE200-10N 20.0 A 12 20.0 A 25.0 A
Single-Phase Models (240 V ac)
STFE030-24L 3.0 A 24 3.0 A 3.75 A
STFE050-24L 5.0 A 22 5.0 A 6.25 A
STFE100-24L 10.0 A 20 10.0 A 12.5 A
STFE200-24L 20.0 A 12 20.0 A 25.0 A
Single-Phase Models (120 V ac)
STFE030-10N
STFE050-10N
STFE100-10N
STFE200-10N
Single-Phase Models (240 V ac)
STFE030-24L
STFE050-24L
STFE100-24L
STFE200-24L
*16 AWG wire or larger may be required by code, dependent upon application

English Version STFE Elite Instruction Manual • 7
Installation
• For units provided with a ground connection, a green (with or without one or
more yellow stripes) insulated grounding conductor identical in size, insulation
material, and thickness to the grounded and ungrounded conductors must be
installed (ref. NEC Table 250-95) and referenced back to an acceptable building
earth ground.
• Attachment plugs, receptacles, etc. in the vicinity of the STFE Elite Series must
be of grounding type, with the grounding conductors connected to an acceptable
building earth ground.
• Terminals, lugs, and connectors used in installation must be suitable for the
material of the conductors. Conductors of dissimilar metals shall not be inter-
mixed in a terminal or splicing.
LINE LOAD
L/L1
N/L2
GND
L/L1
N/L2
GND
L/L1
TO
REMOTE INDICATION
IF NEEDED
TO LOAD OR
EQUIPMENT
PROTECT
RELAY
CONTACTS
NO COM NC
L/L1
N/L2
N/L2
GND GND
LINE INPUT
FROM SOURCE

English Version STFE Elite Instruction Manual • 8
Technical Specications
Description Catalog Number
STFEXXX-10N STFEXXX-24L
Input Voltage 120 V (0–150 VRMS) 240 V (0–275 VRMS)
Line Frequency 47–63 Hz
Response Time < 0.5 ns normal mode; < 5 ns common mode
Enclosure Fully enclosed metal housing
Connection/Mounting Type DIN rail mount
Status Indication Green LED “OK”, Form C contact, 10 A @ 250 V ac or 5 A @ 100 V dc
Weight 1.7 lb. (0.7 kg)
Dimensions H x W x D 4.88 in. (124 mm) x 2.56 in. (65 mm) x 4.56 in. (116 mm)
Operating Temperature -40°C to +50°C at full load; derate linearly to 60% at +70°C
Operating Humidity 0% to 95% Non-condensing
Peak Surge Current Capability
Per Phase 30,000 A
Line to Neutral 20,000 A
Line to Ground 10,000 A
Neutral to Ground 10,000 A
Load Surge Current Rating
10 ms 5 x Nominal
1 s 3 x Nominal
10 s 2 x Nominal
Nominal Discharge Current Rating 3 kA
Frequent Response
Normal Mode (forward-reverse) 100 kHz to 50 MHz 90 dB Max
Common Mode (forward-reverse) 5 kHz to 50 MHz 60 dB Max
Transient Reduction (IEEE C62.41)*
*All Voltage congurations are single
phase, 2 wire + ground
Typical Category A Ringwave (6 kV, 200 A, 100 kHz) < 60 V peak
Typical Category B Ringwave (6 kV, 500 A, 100 kHz) < 100 V peak
Safety Agency Approvals UL 1449, UL 1283 (recognized component), CE
Warranty 5 year limited warranty
UL 1449 (3rd Edition) Voltage Protection Ratings
Protection Mode 120 V, 3–5 A Models 120 V, 10–20 A Models 240 V, 3–5 A Models 240 V, 10–20 A Models
Line to Neutral 400 400 N/A N/A
Line to Line N/A N/A 800 800
Line to Ground 600 500 1200 1000
Neutral to Ground 600 500 N/A N/A

English Version STFE Elite Instruction Manual • 9
Dimensional Drawings
Active Tracking Filter
STFE Elite Series
NO COM NC L/L1 N/12
L/L1 N/L2
4.88 in. (124 mm)
2.56 in. (65 mm)
4.56 in. (116 mm)

English Version STFE Elite Instruction Manual • 10
System Design
Rear View
DIN Connector
Strong all metal for
horizontal or vertical
mounting
Internal View
of Components
MOV Array
provides high-energy
all mode protection
Series Blocking Inductor
blocks voltage, smooths current
Silicone Avalanche Diodes
fast-responding surge suppressor
Finger Safe Terminals
Green LED Unit Status Indicator
Pulse Capacitor
high-frequency noise absorption
Form C Relay Contacts
DC OK signal
Dieses Handbuch passt für folgende Modelle
10
Inhaltsverzeichnis
Sprachen:
Beliebte Wasserfiltersystem Handbücher anderer Marken

Gaggenau
Gaggenau BRITA INTENZA 467873 Bedienungsanleitung

Brita
Brita SAFF-100 Bedienungsanleitung

HEISSNER
HEISSNER FPU24000-00 Bedienungsanleitung

BGS technic
BGS technic 1518 Bedienungsanleitung

Reverse Osmosis
Reverse Osmosis RF Series Bedienungsanleitung

ubbink
ubbink Filtramax Series Bedienungsanleitung