FIXTURE TROUBLESHOOTING
Problem Checklist
No flow. Make sure the water supply for station is on.
Verify checks of Manifold Assembly correctly
installed. Remove eye pieces and clean out any
debris.
Water does
not drain
properly.
Check to see if station is installed level and
correct as needed. Make sure nothing is
blocking drain of the bowl. Remove any debris.
Double check the main waste line for the facility.
Make sure there is no blockage and that it can
handle the required drainage.
Water leaks
between
fittings or
connections.
Tighten all connections. If leak persists,
disassemble, apply additional sealant and
reassemble.
Insufficient
flow to eye/
face wash.
Turn water supply to station off. Remove the
eye pieces and clean out any debris. Make sure
diverter is fully opened. Verify pressure to station
is at 30 psi as required.
MAINTENANCE
Emergency Eye/Face Wash System shall be activated on a
weekly basis to verify operation and to flush the lines per the
American National Standards Institute (ANSI). Inspections
shall be recorded with inspector’s name and date tested.
Should the need to repair or replace any parts
on this station, please contact Stingray Systems.
Before any repairs are performed, please verify
that the water supply to the station is shut off.
GUARANTEE
We guarantee the Stingray Systems product to be free from
defects in workmanship and material, and for a period of
eighteen (18) months from date of shipment from the factory
or one (1) year from date of installation, whichever occurs
first, will replace any parts found by us to be defective. We
will not be held responsible, however, for any labor incidental
to, or for any damages caused by defective material.
With any questions, please do not hesitate in contacting us
at: 1-888-445-4142 or via email at info@tepid.com.
VALVE TROUBLESHOOTING
Problem Checklist
No hot water. Ensure hot water is on. Check pressure at both
inlets. Pressures must be near-equal, or seats will
check and only allow cold water. Need at least
30 psi at both hot and cold inlets. Need at least
a 20 degree difference between hot water and
set temperatures, as well as cold water and set
temperatures. Inspect checks for debris; clean/
replace if needed. Remove thermostat and check
for debris. Make sure liner can move. Clean
thermostat. If continues, replace thermostat.
No cold water. Ensure hot connects to hot side; cold to
cold side. Inspect checks for debris; clean/
replace if needed. Remove thermostat and
check for debris. Ensure liner can move. Clean
thermostat. Replace thermostat if needed.
No water. Ensure hot water is on. Check pressure at both
inlets. Pressures must be near-equal, or seats
will check and only allow cold water. Need at
least 30 psi at both hot and cold inlets. Need at
least a 20 degree difference between hot water
and set temperatures, as well as cold water and
set temperatures. Inspect checks for debris;
clean/replace if needed. Remove thermostat and
check for debris. Ensure liner can move. Clean
thermostat. Replace thermostat if needed.
Insufficient
flow.
Ensure hot water is on. Check pressure at both
inlets. Pressures must be near-equal, or seats
will check and only allow cold water. Need at
least 30 psi at both hot and cold inlets. Need at
least a 20 degree difference between hot water
and set temperatures, as well as cold water and
set temperatures.Inspect checks for debris;
clean/replace if needed. Remove thermostat
and check for debris. Ensure liner can move.
Clean thermostat. Replace thermostat if needed.
Temperature
fluctuation.
Ensure incoming building pressure is not
fluctuating. Inspect supply lines for other
equipment that may be reducing pressure to
the emergency fixtures. Check pressure at both
inlets. Pressures must be near-equal, or seats
will check and only allow cold water. Need at
least 30 psi at both hot and cold inlets. Need at
least a 20 degree difference between hot water
and set temperatures, as well as cold water and
set temperatures. Inspect checks for debris;
clean/replace if needed. Remove thermostat
and check for debris. Ensure liner can move.
Clean thermostat. Replace thermostat if needed.
Leaks around
thermostat.
Remove thermostat and check O-ring. If
damaged or worn, replace/tighten.
Water in
thermostat.
Check connection. Replace thermometer.