Electrical Supply
Installation must be carried out by a qualified electrician in
accordance with BS 7671:2008 Wiring Regulations.
230/240V AC 50/60Hz mains supply to suitable lighting
track.
Site conditions: LED equipment is more susceptible to
static damage and over voltage than previous technology.
Before handling or connecting to the mains supply ensure
that all Stoane Lighting (SL) products are protected from
static discharge and that the mains supply is to regulation.
(230V +10 -6%)
This fitting is supplied with a Xicato LED module. Refer to
the fitting label for the module version and wattage. More
information on the module can be found at
www.xicato.com/support
Mains cables must be double insulated, strain relieved
and separated from E.L.V output cables.
Observe polarity:
Incorrect supply or reverse polarity can cause irreparable
damage.
All connections must be made before switching on mains.
If the supply is energised prior to making the connections
to the fitting then the resulting surge will damage the LED.
Maintenance:
All lighting equipment is delicate and easily damaged
through misuse or inappropriate installation (mechanical
or electrical). Repairs and replacements may cause
delays and will be chargeable. Contact SL for support if
required.
All Stoane Lighting products are covered by a five year
Warranty and a 25 year Duty of Care. Products are
designed to be upgraded, adapted and refreshed using
our comprehensive ReNew service. For more information
on our ReNew service and for full Warranty terms and
conditions visit stoanelighting.com or contact us at the
address shown.
The light source contained in this luminaire shall only be
replaced by the manufacturer or his service agent or a
similar qualified person.
Installation
Check that the track is mounted securely and is
capable of supporting the total weight of the
fittings on it.
Fitting Weight : 0.75kg.
Track must always be mounted to a horizontal ceiling,
mounting track vertically or on a wall or at an angle
will result in damage to the fittings.
Step 1 Insert the track adaptor into the track and
secure via the locking tab.
Whilst holding the fitting turn the locking tab
through 90° and the fitting will be locked in
place.
Step 2 Rotate the circuit selector to the required
circuit.
WARNING: Do not look at exposed LED lamps in
operation. Eye injury can result.
Additional items should not be hung or suspended
from this fitting. SL takes no responsibility for
additional items added by others or the consequences
of those items.
When supplying digital equipment with the potential to
be connected to networks, physically or wirelessly (i.e.
Bluetooth, WiFi, DMX radio etc.), SL does not take
responsibility for the digital security of the equipment
or associated networks. It is the customer’s
responsibility to select a protocol suitably robust for
their requirements and to ensure responsible
utilisation of passwords.
SL can provide assistance on dimming compatibility or
control systems by request. For advice on specific
dimming systems we recommend seeking assistance
from the commissioning engineer or the control
systems provider in the first instance.
Cleaning:
Fully isolate the fitting and allow to cool.
Clean the fitting with a slightly damp lint free cloth
from a mild solution of soap and water. The fitting
must be completely dry before reconnecting power.
Incompatible or abrasive chemicals can damage the
fitting, contact SL for advice if required.
ZTA.50 Mains Track.pdf 2 12/04/2021 11:00:05