INSTALLATION GUIDE
Version 2.12
English
EN 101.00.SIO2 V2.12A

CONTENTS
Safety information 2
Instructional icons 2
Introduction 4
Components 4
Name of each part 5
Installation Example 5
Connections 6
Power 6
RS-485 6
Fail Safe Lock 7
Fail Secure Lock 7
Door button 8
Door sensor 8
Product Specifications 9
FCC compliance information 11
Appendices 12
Disclaimers 12
Copyright Notice 12

2
Safety information
Safety information
Please read this safety instructions before you use the product to prevent injury to yourself and others and to prevent
property damage. The term 'product' in this manual refers to the product and any items provided with the product.
Instructional icons
Warning: This symbol indicates situations that could result in death or severe injury.
Caution: This symbol indicates situations that may result in moderate injury or property damage.
Note: This symbol indicates notes or additional information.
Warning
Installation
Do not install or repair the product arbitrarily.
• This may result in electric shock, fire, or product damage.
• Damages caused by any modifications or failure to follow installation instructions can void the manufacturer’s warranty.
Do not install the product in a place with direct sunlight, moisture, dust, soot, or a gas leak.
• This may result in electric shock or fire.
Do not install the product in a location with heat from an electric heater.
• This may result in fire due to overheating.
Install the product in a dry location.
• Humidity and liquids may result in electric shock or product damage.
Do not install the product in a location where it will be affected by radio frequencies.
• This may result in fire or product damage.
Operation
Keep the product dry.
• Humidity and liquids may result in electric shock, fire, or product damage.
Do not use damaged power supply adaptors, plugs, or loose electrical sockets.
• Unsecured connections may cause electric shock or fire.
Do not bend or damage the power cord.
• This may result in electric shock or fire.

3
Safety information
Caution
Installation
Do not install the power supply cable in a location where people pass by.
• This may result in injury or product damage.
Do not install the product near magnetic objects, such as a magnet, TV, monitor (especially CRT), or speaker.
• The product may malfunction.
Secure I/O 2, the electrical locking device and access controller must use independent power source.
Operation
Do not drop the product or cause impacts to the product.
• The product may malfunction.
Do not press buttons on the product by force or do not press them with a sharp tool.
• The product may malfunction.
When cleaning the product, mind the following.
• Wipe the product with a clean and dry towel.
• If you need to sanitize the product, moisten the cloth or the wipe with a proper amount of rubbing alcohol and gently
clean all exposed surfaces including the fingerprint sensor. Use rubbing alcohol (containing 70% Isopropyl alcohol) and a
clean, non-abrasive cloth like lens wipe.
• Do not apply liquid directly to the surface of the product.
Do not use the product for anything other than its intended use.
• The product may malfunction.

4
Introduction
Introduction
Components
Secure I/O 2
Fixing screw x2 Bracket x2 120Ω resistor Diode
• Components may vary according to the installation environment.

5
Introduction
Name of each part
5
• Press INIT button to reset Secure I/O 2 interworking with a device and then connect to another device.
Installation Example
Secure I/O 2 is connected with RS-485 and can be installed anywhere due to its small size. It can be installed with a
junction box or onto a wall control box already installed. It can be installed at the rear side of an Exit button.
LED status indicator for Power
LED status indicator for RS-485 D- (TRX-)
LED status indicator for RS-485 D+ (TRX+)
RS-485 D+ (TRX+)
RS-485 D- (TRX-)
RS-485 GND
Relay Output Normally Closed
Relay Output Common
Relay Output Normally Open
INIT button
Relay status indication LED
Power
GND
LED status indicator for External IN 1
External IN 1+
External IN GND
External IN 2+
LED status indicator for External IN 2
RESET button
Exit button
External Input
RS-485
Access Controller
Relay Output
Door lock
device

6
Connections
Connections
• Cable should be AWG22~AWG16.
• To connect the cable to Secure I/O 2, strip off approximately 5~6 mm of the end of the cable and connect
them.
Power
• Do not share the power with the access controller.
• If the power is shared by other devices, it should provide 9–18V and a minimum of 500 mA.
• When using a power adapter, it should have IEC/EN 62368-1 certification.
RS-485
• RS-485 should be twisted pair, and maximum length is 1.2 km.
• Connect a termination resistor (120Ω) to both ends of a RS-485 daisy chain connection. It should be installed at both
ends of the daisy chain. If it is installed in the middle of the chain, the performance in communicating will deteriorate
because it reduces the signal level.
Termination
resistor
(120Ω)
DC
Power
RS-485 TRX+ RS-485 TRX-
Termination
resistor
(120Ω)
GND
Access controller
Access controller

7
Connections
Relay
Fail Safe Lock
In order to use the Fail Safe Lock, connect the N/C relay as shown in the figure below. There is normally a current flowing
through the relay for the Fail Safe Lock. When the relay is activated, blocking the current flow, the door will open. If the
power supply to the product is cut off due to a power failure or an external factor, the door will open.
• Connect a diode to both ends of the power input as shown in the figure below when installing a deadbolt or a
door strike. Make sure to connect the Cathode (direction to the stripe) to the + part of the power while paying
attention to the direction of the diode.
Dead bolt
/ Door strike DC power
Fail Secure Lock
In order to use the Fail Secure Lock, connect N/O relay as shown in the figure below. There is normally no current
flowing through the relay for the Fail Secure Lock. When the current flow is activated by the relay, the door will open. If
the power supply to the product is cut off due to a power failure or an external factor, the door will lock.
• Connect a diode to both ends of the power input as shown in the figure below when installing a deadbolt or a
door strike. Make sure to connect the Cathode (direction to the stripe) to the + part of the power while paying
attention to the direction of diode.
Dead bolt /
Door strike DC power

8
Connections
Door button
Door sensor
Door
RTE button
or
Door button
+
GND
Door
Door Sensor

9
Product Specifications
Product Specifications
Category Feature Specification
General
Model SIO2
CPU Cortex M3 72 MHz
Memory 128 KB Flash + 20 KB RAM
LED
Multi-color
• PWR
• RS-485 TX/RX
• IN1/IN2
• RELAY
Operating temperature -20°C ~ 50°C
Storage temperature -40°C ~ 70°C
Operating humidity 0% ~ 80%, non-condensing
Storage humidity 0% ~ 90%, non-condensing
Dimension (W x H x D) 36 mm x 65 mm x 18 mm
Weight 37 g
Certificates CE, FCC, KC, RoHS
Interface
RS-485 1 ch
TTL Input 2 ch
Relay 1 relay
Electrical
Power
• Recommended: 9 VDC (130 mA), 12 VDC (100 mA), 18 VDC (70 mA)
• Maximum: 18 VDC (200 mA)
• Current: Maximum 200 mA
Relay 2 A@ 30 VDC Resistive load
1 A@ 30 VDC Inductive load