TCS QD3041 Bedienungsanleitung

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com 202112
|Installation Manual
The QD3041 BACnet Building Manager connects
the local site BACnet controller network with
Ubiquity Cloud.
QD3041
BACnet Building Manager
BACnet® is a registered
trademark of ASHRAE.

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
23
23
Installation..........................................................................................................3
Introduction ...........................................................................................................................................3
Material List.............................................................................................................................................3
Mounting.................................................................................................................................................3
Input Connections.................................................................................................................................3
QD3041 Power and Communication Connections ........................................................................4
RS-485 Network Wiring .......................................................................................................................4
Three-Wire Network Wiring.......................................................................................................................................... 5
Startup .....................................................................................................................................................6
Troubleshooting ....................................................................................................................................6
Power LED Does Not Light Up ...................................................................................................................................... 6
No Communications with Controllers on the Network .......................................................................................... 6
No LAN Link to the Internet .......................................................................................................................................... 6
No Communication with RS-485 Ports (COM 1 and 2), Ubiquity Time-out, or No Data................................... 7
Conguration ......................................................................................................8
Introduction .....................................................................................................................................................................8
QD3041 Configuration via Laptop............................................................................................................................... 8
QD3041 Configuration via Command Line Interface (CLI) ................................................................................... 13
Appendices.......................................................................................................16
Appendix A: Local Management Port ..............................................................................................16
Connection Setup ......................................................................................................................................................... 16
Appendix B: Revert Back to DHCP Settings....................................................................................22
Appendix C: Monitor and Keyboard ................................................................................................25
Connection Setup .........................................................................................................................................................25
Contents

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
33
Introduction
Congratulations on choosing the TCS QD3041 BACnet Building Manager! The QD3041 is a compact, versatile network
controller that seamlessly connects with Ubiquity Cloud™ via BACnet.
This manual includes all the information you will need to properly install and set up your QD3041. As most units ship
precongured, you will most likely only need to read the Installation section of this manual and you can skip the Congura-
tion section. However, some customers do order their units without preconguration; for those customers, we include the
comprehensive “Conguration” section which contains essential information they will need to set up the unit.
If you have any questions regarding your QD3041 or your network, do not hesitate to contact TCS Technical Support at
800-288-9383, ext. 2.
Material List
• QD3041 BACnet Building Manager
• External Power Supply
• Wall Mounting Bracket
• Two 120 Ω terminating resistors for RS-485 network
Mounting
The QD3041 is designed to be hung on a wall via the mounting screw holes in each unit. It may also be set on a shelf or
table. If mounting on a wall, do not allow the mounting screws to contact the circuit board inside the enclosure.
When selecting a location to mount the QD3041, be sure to allow space for cable connections. Locate the QD3041 away
from excessive dust, heat sources, moisture or direct sunlight. The ideal environment is a server room. The temperature of
the room should not exceed 77ºF (25ºC); proper ventilation is mandatory.
Input Connections
Refer to the “QD3041 Power and Communication Connections” on page 4for the following input connections:
Power: Connect the included power supply to the back of the QD3041 and insert the power plug into a 120 VAC socket. A
blue light will show on the front of the unit, indicating it is powered up. If the unit does not automatically power up, press
the Power button on the front of the unit once.
Ethernet: Connect an Ethernet cable from your network port to the device’s Ethernet LAN port (C). Do NOT connect to port
L, which is reserved for Admin only. If you are using a cellular modem, connect an Ethernet cable from the QD3041 Ether-
net LAN port (C) to the Ethernet port on the Cellular Modem.
RS-485 Network: Connect an RS-485 network to one of the COM ports.
NOTE: The remaining ports on the QD3041 are unused or reserved for Admin only.
Installation

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
45
45
Installation
QD3041 Power and Communication Connections
Power and Communication Connections
RS-485 Network Wiring
All controllers connected to the network must be programmed with the same communication baud rate as well as a
unique MS/TP communication address from 0 to 127.
Use 22 AWG, twisted shielded three-conductor cable for network wiring. Network wiring should start at one controller and
go to the next and then go to the next, until the nal controller is reached. Wiring is such that all “A” wires are connected to
“A” wires, all “B” wires are connected to “B” wires, and all “REF” wires are connected to “REF” wires.
NOTE: “A" refers to the negative (–) RS-485 connection and “B” refers to the positive (+) RS-485 connection.
Place a 120 Ω terminating resistor at each of the two ends of the network directly across the “A” and “B” wires.
• If the QD3041 will be at one end of the network, hard-wire a 120 Ω terminating resistor across the “A” and “B” termi-
nals of the QD3041 (See “Three-Wire Network Wiring” on page 5).
• If the QD3041 will be in the middle of the network, do not wire in the terminating resistor on the QD3041 terminal
block.
Connect one end (ideally the furthest end from the QD3041) of the shield wire of the network wiring to earth ground.
NOTE: If you encounter issues with your network wiring or communications, contact TCS Technical Support (800-288-
9383, ext. 2).
Rx/Tx Activity LEDs
To Controllers
Not Used
USB PORT 2
USB PORT 1
USB PORT 4
USB PORT 3
L
C
ETHERNET 2
ETHERNET 1
POWER
(12VDC)
HDMIDP
REF REF
BA
B
COM 1 COM 2
A
Not UsedNot Used Local
Mgmt. Port
(Admin Only)
Monitor Ports
(Admin Only)
ETHERNET
CABLE
To Network Port or Cellular Modem
POWER
CORD
To Wall Outlet

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
55
Installation
Three-Wire Network Wiring
Follow this wiring diagram for all three-wire systems.
NOTES: In the middle of the network, all network wiring shields should be twisted together and taped off to prevent acci-
dental grounding. More than one ground on the network wiring can result in communication failure.
A maximum of two terminating resistors can be used.
Three-Wire Diagram
QD3041 at end of the network.
QD3041 in the middle of the
network.
1 3
2
Shielded, twisted three-conductor com-
munications wiring with one end earth
grounded. (120 Ω terminating resistors
provided.)
Shielded, twisted three-conductor com-
munications wiring with one end earth
grounded. (120 Ωterminating resistors
provided.)
4
NOTE: Each controller must use
the same baud rate and be as-
signed a unique BACnet MS/TP
address and device ID.
A
B
REF
Shield
A
B
REF
A
B
REF
Earth Ground
Only at one end
Drain
Wire
Last in Daisy Chain
120Ω
Terminating
Resistor
COM 1
REF AB
Drain
Wire
120Ω
Terminating
Resistor
A
B
REF
A
B
REF
A
B
REF
Last in Daisy Chain
Shield
Last in Daisy Chain
Earth Ground
Only at one end
120Ω
Terminating
Resistor
A
B
REF
A
B
REF
A
B
REF
Shield
Drain
Wire
COM 1
REF REF
AA
BB
120Ω
Terminating
Resistor
12
3
3
4
44
COM 1
REF A
B
COM 1
REF A
B

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
67
67
Installation
Startup
1. Verify all RS-485 connections from the controller network to the QD3041 are complete.
NOTE: Refer to “QD3041 Power and Communication Connections” on page 4 for steps 2 through 5 below.
2. Verify that all 24V power wiring to the controller network has been completed; all controllers are powered on and
each controller has been programmed with a unique BACnet MS/TP address and device ID.
3. Connect one end of the Ethernet cable to the Ethernet port (C) on the QD3041, and the other end to the network port
provided by the customer, or to a cell modem (if utilized).
4. Connect the power source to the QD3041 and apply power. If your QD3041 shipped precongured, it will automatical-
ly go online and contact Ubiquity Cloud.
5. You MUST call TCS Technical Support (800-288-9383 ext. 2) to verify connection and activate the unit.
6. If your QD3041 was not ordered precongured: You can congure it at this time. See the Conguration Section on
page 8.
Troubleshooting
Power LED Does Not Light Up
Be sure that the power supply module included with the QD3041 is plugged in to a 120VAC outlet that has power and
the 12V, 5A tip positive barrrel socket is plugged into the unit. Press the power button on the front of the unit; a blue light
should come on, indicating the unit ispowereed up.
No Communications with Controllers on the Network
Make sure the baud rate selection for the QD3041 is set to match the baud rate of all the controllers on the network. All
controllers on the network must have a unique MS/TP address and BACnet Device ID. Each port must be properly cong-
ured.
Check the network wiring, making sure to follow polarity; the wire that goes to A must go to A in all devices, as well as the
wire that goes to B and REF.
No LAN Link to the Internet
Verify the network cable is connected correctly and make sure the LEDs next to the Ethernet jack are properly illuminat-
ed. For example, a solid green LED at the RJ-45 LAN connector usually indicates that the QD3041 is either connected or
receiving a signal. If the green light is ashing, this is an indication of data being sent or received.
If there are no lights, the QD3041 may not be connected properly, or may not be receiving a signal from the network. If,
after checking the connections, the LED indicators are still off, the network adapter, port, or cable may be defective.
If there are lights but there is still no communication, this could be because the network communication is not set proper-
ly or there is a bad rewall proxy setting. Contact your IT department for support, or contact TCS Technical Support (800-
288-9383, ext. 2) for assistance.

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
77
Installation
No Communication with RS-485 Ports (COM 1 and 2), Ubiquity Time-out, or No Data
Verify each port on the QD3041 has the proper biasing resistors. Verify each port is also optically isolated, which cleans
up the signal and protects the unit from taking stray voltage off the RS-485 lines.
A set of LEDs on each of the RS-485 ports in the QD3041 allow the building occupant to view operational status of the
serial communication integrated board:
• GREEN – blinking indicates transmitting (Tx)
• YELLOW – blinking indicates receiving (Rx)
If neither of these lights are functioning, there could be a bad connection, a bad cable, a bad ground, or a bad component.
This could also be a conguration issue. Contact TCS Technical Support (800-288-9383, ext. 2) for assistance.

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
89
89
ConfigurationConfiguration
Introduction
The QD3041 utilizes an internal Gateway to communicate with Ubiquity Cloud and the attached device networks. This
Gateway can be congured locally by connecting a laptop directly to the unit, or by connecting a monitor and keyboard.
When using a laptop, you can congure the Gateway through the QD3041’s internal web page. When using a monitor and
keyboard, you can congure the Gateway via the text-based Command Line Interface (CLI).
NOTE: All Ubiquity Cloud services are accessed by logging into the Ubiquity Cloud Server (www.ubiquitysystems.net),
not by using the internal web page.
The QD3041 has a default Gateway login and password, which is supplied to customers upon request. It is the custom-
er’s responsibility to congure a custom login and password. Contact TCS Technical Support (800-288-9383, ext. 2) for
information on managing login credentials.
QD3041 Conguration via Laptop
Once you have made a connection and have logged in (see “Appendix A: Local Management Port” on page 16) you can
congure the operation of the unit.
If you are unable to access the configuration page, contact TCS Technical Support (800-288-9383, ext. 2) for assistance.
Installation Information
The BACnet Device Properties section contains unit-related information used to uniquely identify the unit when it is being
serviced in the eld. It also contains software/application-related information such as the software version and patch
level.
Installation Information
IMPORTANT: If you ordered your QD3041 preconfigured, which is typical, you can skip this section!
The Configuration section is for those who need to configure or reconfigure their unit.

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
99
Configuration
Device ID: The Device ID is a BACnet address that identies the unit on the BACnet network (similar to an IP address).
This number must a unique number. Once you have assigned a unique number to the unit, click the Update Device Info
button to save the number.
The Site Time section is used by the local network and the QD3041 until the Ubiquity Cloud Server performs a time syn-
chronization with the site.
Enter the timezone information in this section and click the Update Time Info button to save the setting.
Network Information
This section contains settings which control how the QD3041 connects to the Internet. All of these settings are deter-
mined by your local network administrator or IT department.
Network Information – Use DHCP
Network Options
The QD3041 supports both static IP and Dynamic Host Conguration Protocol (DHCP) IP address allocations. When utiliz-
ing DHCP addressing, the IP address settings are automatically assigned when communication is established. Enter host
name if needed (typically left blank).
IPV4 Network
If you are using a static IP address, deselect “Use DHCP” and ll in the static IP address information (IP Address, Gateway,
Subnet, DNS1 and DNS2 settings) established by the LAN/ WAN network administrator prior to installation.

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
10 11
10 11
Configuration
Network Information – Static IP Conguration
Proxy
If a proxy is required, select the “Use Proxy” check box and enter all the related details in the elds that appear. When you
are nished entering information in this section, click the Update Communication Info button.
Application Information
This section contains settings which dene how the QD3041 interacts with the controller network, and how it communi-
cates the data to Ubiquity Cloud.
Application Information
Inhaltsverzeichnis
Andere TCS Konferenzsystem Handbücher
Beliebte Konferenzsystem Handbücher anderer Marken

Kramer
Kramer VIA GO Bedienungsanleitung

AVT
AVT MAGIC AC1 Go Bedienungsanleitung

ProSoft Technology
ProSoft Technology AN-X4-AB-DHRIO Bedienungsanleitung

Sony
Sony PCS-I150 Bedienungsanleitung

Middle Atlantic Products
Middle Atlantic Products VTC Series Bedienungsanleitung

Prentke Romich Company
Prentke Romich Company Vanguard Plus Leitfaden