4.
Links (for each relay)to connect + or –auxiliarypowerto the
relays’ common contacts, if required.
5.
LEDs (for each relay)to indicate when the relayis active.
6.
Data and powerconnection to a TS1041 card.
7.
Eight single-pole relayswith connection terminalsto the common
(C), normally open (NO),and normallyclosed (NC) contacts.
8.
M3 threaded earth terminal.
To install the card:
1. Disconnecttheplug pack and battery fromthe panel or
DGP.
2. Insertsix standoffs (supplied)into theDGPenclosureor a
separate enclosureata location suitablefor theten-way
cable to connectthecard to thecontrol panel,DGP,or
other card,as needed.
3. Use six M3 x 10 pan head screws to fix the card to the
standoffs.
4. Connecttheten-way cable to the controlpanel,DGP,or
other TS1041 card.
5. Connecttherelay cables to the card as required.
6. Reapply power to thepanel or DGP.
Configure theChallenger series panel,IntelligentAccess
Controller, or standard DGP accordingly:
•If connectingto a Challenger series panel, setthe value of
System Options >Relay Controllers to avalue greaterthan
0 where 1 represents every 8 relays available.
•If connectingto an IntelligentAccess Controller /Network
Access Controller,setthevalue of Controller Options >
Relay Controllersto avalue greater than 0 where 1
represents every 8 relays available.
•If connectingto astandard DGP,set the configuration DIP
switch segment6 to ON.
Wiring
Connectthecard viathe IN connector,usingthesupplied
ten-way cable, to oneof thefollowingdevices (the
connector number varies with the device):
•J14 on a Challenger series panel
•J21 on a 4-Door or 4-Lift Controller
•J8 on a standard (TS0820 orTS0824) DGP
•J200 on a Network Access Controller
•Out connector onaTS1041 card
8-Way Relay Cards may be daisy chained together.
The IN connectorofonecard is connected to theOUT
connector ofanother.See theSpecification tablefor
the number of daisy chainedcards supported by each
device.
Chains of1 or 2 cards may be powered fromthe parent
devicelisted above.The+12V link on theparentdevice
must be closed with ajumper.
Chains of3 ormore cards must be supplied with +12V
from an external supply to thepowerinputterminals
(Figure1, item 2). The+12V link on theparentdevice
must be open (jumper removed).
8-Way Relay Cards must be earthed (Fig 1, item 8).
Before you begin:
•Upon being powered up,relay cards may take up to 15 seconds to
activate
•If relays are powered externally and power to thepanel is lost,the
state ofall relays will reset(turn off)after 30 seconds
•Relays will indicatebut notreliably operatewhen voltageis less
than 9.5V
Specifications
NOTICE! This is a Class A product. In a domestic environment this
product may cause radio interference in which case the usermaybe
required to take adequate measures.
Disclaimer
The customer is responsiblefor testing and determiningthe
suitability ofthis productfor specific applications.In no eventis
Carrier Fire & Security Australia responsible or liable for any
damages incurred by the buyer or any third party arisingfrom
its use, or their inability to usethe product.