Digital PIDController
TS80B-E1
Carefully readall theinstructions inthis manual.Please place
this manualin aconvenient locationfor easyreference.
WARNING
CAUTION
(4) Control output[OUT]:
M:Relay contact V: Voltagepulse
8: Current(DC4 ~20 mA) 5:DC0-5VDC
6: DC0-10VDC T:Trigger (fortriac driving)
(5) Remark:
N: No
(6) Alarm1[AL1 for highalarm] See"5.5 "
N: No alarm
A: Deviationhigh alarm H:Process high alarm
(7) Alarm2[AL2 for lowalarm] See"5.5 "
N: No alarm
B: Deviation lowalarm J: Processlow alarm
(8) Power
A: 220VAC B 85-265VAC D 24VDC E 24VAC
Initial Setting
Initial Setting
!
TS80B-E1
INSTRUCTION MANUAL
1
An externalprotection device must be installed iffailure of this
instrument could resultin damage to the instrument, equipment
or injury topersonnel .
All wiringmust be completedbefore power inturned on toprevent
electric shock, fireor damage toinstrument and equipment .
This instrument must be used in accordance with the
specifications to prevent fire or damage to instrument and
equipment.
This instrument is not intended for use in locations subject to
flammable or explosivegases.
Do not touch high-voltage connections such as power supply
terminals , etc.to avoid electricshock.
This instrument is protected from electric shockby reinforced
insulation. Provide reinforced insulation between the wirefor
the input signal and the wires forinstrument power supply, source
of power and loads.
This instrument is design for installation in an enclosed
instrumentation panel. All high-voltage connections such as
power supply terminals must be enclosed in the instrumentati on
panel to avoid electric shock byoperating personnel.
All precautions describedin this manual should be taken to avoid
damage to the instrument or equipment.
All wiring mustbe in accordance with local codes andregulations.
Always observe precautions described in this manual.
Otherwise serious injury or accidentmay result.
Do not allow metalfragments or lead wire scraps to fallinside this
instrument. This may cause electricshock, fire or malfunction.
Firmly tighten each terminal screw at the specified torque.
Otherwise electric shock or fire mayresult.
Do not place any obstacle around this instrument in order
not to impede radiation of heat.And do not close ventilationholes.
Do not connect wires tounused terminals.
Before cleaning the instrument,always turn off the power supply.
Remove stains from thisinstrument using a soft,dry cloth. Do not
use a volatile solvent such asthinner in order toavoid deformation
or discoloration.
Do not rub norstrike the display unit of this instrumentwith a hard
object.
-
1. PRODUCTCHECK
-
(1) Control action
F: PID reverseaction with autotuning
(1)(2) (3) (4) (5) (6)(7) (8)
(2) Input type,(3) Range code: See"8.INPUTRANGE TABLE"
Check MODELand CODE
is very importantwhen ordering.
2.1 MountingCautions
2. MOUNTING
(1) Use this Instrument within the following ambient
temperature and ambienthumidity.
Allowable ambienttemperature: 0 to50
Allowable ambienthumidity: 45 to85% RH
(2) Avoidthe following whenselecting the mountinglocation.
Rapid changes inambient temperature whichmay cause condensation.
Corrosive or inflammablegases.
Direct vibration orshock to themainframe.
Water,oil,chemicals,vaporor steam splashes.
Excessive induction noise,static electricity,magnetic fields ornoise.
Direct air flowfrom an airconditioner.
Exposure to directsunlight.
Excessive heat accumulation.
C
TS81B/TS84B/TS85B/TS87B/TS89B
TS85B
TS84B
TS89B
TS87B
TS81B
Example
Model: TS89B Specification:
Model of thecontroller:TS89B
Size: 96mm x96mm
Control action: PIDreverse action
Input: K typethermocouple
Out put: Relayoutput
Alarm: 1 deviationhigh alarm (AL1)
Power: AC220V
Code: FKA4-MN*AN-A
2.2 Dimensions
TS81B
50 14.6
50
44.0
44.0
58.0
80
13.6
11
TS84B
TS85B
50 14.6
96
44.0
90.0
104.0
80
13.6
11
74 14.6
74
67.5
67.5
80.0
80
13.6
11
UP
TS87B TS89B
90
96 14.6
96
90.0
104.0
80
13.6
11
UP
Unit:mm Unit:mm
Unit:mm Unit:mm