Veeder-Root ProtoNode FPC-N54 Benutzerhandbuch

Manual No: 577014-491 • Revision: A
ProtoNode FPC-N54 Gateway
Startup Guide

ii
Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in
connection with the furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication may be
photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
Contact TLS Systems Technical Support for additional troubleshooting information at 800-323-1799.
DAMAGE CLAIMS / LOST EQUIPMENT
Thoroughly examine all components and units as soon as they are received. If any cartons are damaged or missing, write a complete
and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the inspection and sign
the description. Refuse only the damaged product, not the entire shipment.
Veeder-Root must be notified of any damages and/or shortages within 30 days of receipt of the shipment, as stated in our Terms and
Conditions.
VEEDER-ROOT’S PREFERRED CARRIER
1. Contact Veeder-Root Customer Service at 800-873-3313 with the specific part numbers and quantities that were missing or
received damaged.
2. Fax signed Bill of Lading (BOL) to Veeder-Root Customer Service at 800-234-5350.
3. Veeder-Root will file the claim with the carrier and replace the damaged/missing product at no charge to the customer. Customer
Service will work with production facility to have the replacement product shipped as soon as possible.
CUSTOMER’S PREFERRED CARRIER
1. It is the customer’s responsibility to file a claim with their carrier.
2. Customer may submit a replacement purchase order. Customer is responsible for all charges and freight associated with
replacement order. Customer Service will work with production facility to have the replacement product shipped as soon as
possible.
3. If “lost” equipment is delivered at a later date and is not needed, Veeder-Root will allow a Return to Stock without a restocking fee.
4. Veeder-Root will NOT be responsible for any compensation when a customer chooses their own carrier.
RETURN SHIPPING
For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy” pages in the
"Policies and Literature" section of the Veeder-Root North American Environmental Products price list. Veeder-Root will not
accept any return product without a Return Goods Authorization (RGA) number clearly printed on the outside of the package.
©Veeder-Root 2023. All rights reserved.

Table of Contents
iii
Introduction
ProtoNode Gateway .........................................................................................................1
Contractor Certification Requirements ..............................................................................1
Safety Precautions ............................................................................................................1
Safety Warnings ...............................................................................................................2
Related Documents ..........................................................................................................2
Precautions Against Static Electricity ................................................................................2
ProtoNode Gateway .........................................................................................................3
Quick Start .........................................................................................................................4
Setup For ProtoNode
Record Identification Data ................................................................................................5
Point Count Capacity ........................................................................................................5
Configuring Device Configurations ...................................................................................5
Interfacing ProtoNode to Devices
Device Connections to ProtoNode ....................................................................................6
RS-232 Network .......................................................................................................6
RS-485 Network .......................................................................................................7
Bias Resistors...........................................................................................................7
Termination Resistor ................................................................................................8
Power-Up ProtoNode ...............................................................................................8
Connect the PC to the ProtoNode
Connecting to the Gateway via Ethernet ..........................................................................9
Changing the Subnet of the Connected PC .............................................................9
Setup Web Server Security
Login to the FieldServer ..................................................................................................10
Select the Security Mode ................................................................................................13
HTTPS with Own Trusted TLS Certificate..............................................................13
HTTPS with Default Untrusted Self-Signed TLS Certificate or HTTP
with Built-in Payload Encryption .............................................................................14
Configure the ProtoNode
Select Field Protocol and Set Configuration Parameters ................................................15
Setting ProtoNode Active Profiles ...................................................................................16
Verify Device Communications .......................................................................................17
Ethernet Network: Setting IP Address for the Field Network ..........................................17
How to Start the Installation Over: Clearing Profiles .......................................................19
Troubleshooting
Lost or Incorrect IP Address ...........................................................................................20
Viewing Diagnostic Information ......................................................................................20
Checking Wiring and Settings .........................................................................................21
LED Diagnostics for Communications Between ProtoNode and Devices ......................22
Taking a FieldServer Diagnostic Capture .......................................................................23
Factory Reset Instructions ..............................................................................................24
Internet Browsers Supported ..........................................................................................24

Table of Contents
iv
Additional Information
Update Firmware ............................................................................................................25
Mounting .........................................................................................................................25
Certification .....................................................................................................................26
Physical Dimension Drawing..................................................................................27
Change Web Server Security Settings After Initial Setup ...............................................28
Change Security Mode...........................................................................................28
Edit the Certificate Loaded onto the FieldServer....................................................29
Change User Management Settings ...............................................................................29
Create Users ..........................................................................................................30
Edit Users...............................................................................................................31
Delete Users...........................................................................................................32
Change FieldServer Password...............................................................................33
Routing Settings .............................................................................................................34
Specifications
Compliance with UL Regulations ....................................................................................35
Limited 2 Year Warranty ..........................................................................................36
Appendix A: Vendor Information – Veeder-Root
Interface To BACnet & Modbus Tables ........................................................................ A-1
Figures
Figure 1. FPC-N54 Connectivity Diagram (TLS450PLUS Shown) ..................................................3
Figure 2. RS-232 Connections from Devices to the ProtoNode R1 Port .........................................6
Figure 3. R1 Port RS-485/RS-232 Selection DIP Switch .................................................................6
Figure 4. RS-485 Connections from Devices to the ProtoNode R2 Port .........................................7
Figure 5. Bias Resistor DIP Switches ..............................................................................................7
Figure 6. Termination Resistor DIP Switches ..................................................................................8
Figure 7. Power Connections ..........................................................................................................8
Figure 8. Ethernet Port Location ......................................................................................................9
Figure 9. Web Server Security Window .........................................................................................10
Figure 10. Connection Not Private Warning ....................................................................................11
Figure 11. Connection Not Private Warning ....................................................................................11
Figure 12. FieldServer Login ...........................................................................................................12
Figure 13. Security Mode Selection Screen ....................................................................................13
Figure 14. Security Mode Selection Screen - Certificate & Private Key ..........................................14
Figure 15. Web Configurator Showing Configuration Parameters ...................................................15
Figure 16. Web Configurator Showing no Active Profiles ................................................................16
Figure 17. Web Configurator Showing no Active Profiles ................................................................17
Figure 18. Diagnostics & Debugging Button ....................................................................................17
Figure 19. Changing IP Address via FS GUI ...................................................................................18
Figure 20. Checking for IP Address of the Desired Gateway ..........................................................20
Figure 21. Error Messages Screen ..................................................................................................21
Figure 22. Diagnostic LEDs .............................................................................................................22
Figure 23. Diagnostic Capture Screen .............................................................................................23
Figure 24. Full Diagnostic Capture Entry .........................................................................................23
Figure 25. ProtoNode DIN Rail Mount .............................................................................................25
Figure 26. BTL Mark – BACnet® Testing Laboratory ......................................................................26
Figure 27. ProtoNode FPC N54 Dimensions ...................................................................................27
Figure 28. FS-GUI Page ..................................................................................................................28
Figure 29. FS-GUI Security Setup ...................................................................................................28

Table of Contents
v
Figure 30. FS-GUI User Management .............................................................................................29
Figure 31. Create User Window ......................................................................................................30
Figure 32. Setup Users ....................................................................................................................31
Figure 33. Edit User Window ...........................................................................................................31
Figure 34. Setup Users ....................................................................................................................32
Figure 35. Delete User Warning ......................................................................................................32
Figure 36. FieldServer Password Update via FS GUI .....................................................................33
Figure 37. Routing Settings .............................................................................................................34
Tables
Table 1. ProtoNode Part Number ......................................................................................................5
Table 2. ProtoNode Total Registers ..................................................................................................5
Table 3. COM Settings ......................................................................................................................5
Table 4. Required Current Draw for the ProtoNode ..........................................................................8
Table 5. Diagnostic LED Descriptions .............................................................................................22
Table 6. Specifications ....................................................................................................................35
Table A-1. System Veeder-Root Interface Mappings to BACnet, Modbus and SNMP ..................... A-1
Table A-2. Unknown_Type Veeder-Root Interface Mappings to BACnet, Modbus and SNMP ........ A-2
Table A-3. Tank Veeder-Root Interface Mappings to BACnet, Modbus and SNMP ......................... A-2
Table A-4. Liquid_Sensor Veeder-Root Interface Mappings to BACnet, Modbus and SNMP .......... A-3
Table A-5. Input Veeder-Root Interface to BACnet, Modbus and SNMP ......................................... A-3
Table A-6. Type_A_Sensor Veeder-Root Interface to BACnet, Modbus and SNMP ....................... A-3
Table A-7. Type_B_Sensor Veeder-Root Interface to BACnet, Modbus and SNMP ....................... A-3
Table A-8. Printer Veeder-Root Interface to BACnet, Modbus and SNMP ....................................... A-3
Table A-9. VVapor_Sensor Veeder-Root Interface to BACnet, Modbus and SNMP ........................ A-4
Table A-10. Groundwater_Sensor Veeder-Root Interface to BACnet, Modbus and SNMP ............... A-4
Table A-11. MAG_Sensor Veeder-Root Interface to BACnet, Modbus and SNMP ............................ A-4
Table A-12. Smart_Sensor Veeder-Root Interface to BACnet, Modbus and SNMP .......................... A-5
Table A-13. PLLD Veeder-Root Interface to BACnet, Modbus and SNMP ........................................ A-5

1
Introduction
ProtoNode Gateway
The ProtoNode is an external, high performance building automation multi-protocol gateway that is preconfigured
to automatically communicate between Veeder-Root’s devices (hereafter simply called “device”) connected to the
ProtoNode and automatically configures them for BACnet/IP, BACnet MS/TP, SNMP, Modbus RTU or Modbus
TCP/IP.
It is not necessary to download any configuration files to support the required applications. The ProtoNode is pre-
loaded with tested profiles/configurations for the supported devices.
The ProtoNode FPC-N54 is compatible with:
•TLS-3XX Console RS-232/RS-485 Dual Interface Module
•TLS-450PLUS Console RS-232/RS-485 Dual Interface Module
Contractor Certification Requirements
Veeder-Root requires the following minimum training certifications for contractors who will install and program the
equipment discussed in this manual:
Service Technician Certification (Previously known as Level 2/3): Contractors holding valid Technician
Certifications are approved to perform installation checkout, startup, programming and operations training, system
tests, troubleshooting and servicing for all Veeder-Root Series Tank Monitoring Systems, including Line Leak
Detection. This certification includes TLS-3xx and TLS4xx certification training.
In-Station Diagnostics (ISD-PMC) Technician Certification: ISD PMC Contractors holding a valid ISD/PMC
Certification are approved to perform (ISD/PMC) installation checkout, startup, programming, and operations
training. This training also includes troubleshooting and service techniques for the Veeder-Root In-Station
Diagnostics system. A current Veeder-Root Technician Certification is a prerequisite for the ISD/PMC course.
All service personal on site must comply with all recommended safety practices identified by OSHA and your
employer.
Review and comply with all the safety warnings in the manuals listed in this document above and any other
Federal, State or Local requirements.
Warranty Registrations may only be submitted by selected Distributors.
Safety Precautions
The following safety symbols may be used throughout this manual to alert you to important safety hazards and
precautions
EXPLOSIVE
Fuels and their vapors are extremely explosive if ignited.
FLAMMABLE
Fuels and their vapors are extremely flammable.
ELECTRICITY
High voltage exists in, and is supplied to, the device. A
potential shock hazard exists.
TURN POWER OFF
Live power to a device creates a potential shock hazard.
Turn Off power to the device and associated accessories
when servicing the unit.
OFF

Introduction Safety Warnings
2
Safety Warnings
Related Documents
576013-879 TLS-3XX Console Site Prep And Installation Manual
577014-073 TLS-450PLUS Console Site Prep And Installation Manual
577014-110 TLS-450PLUS/TLS4 Operator’s Manual
Precautions Against Static Electricity
If necessary to install electronic components in the ATG to implement this feature, read the following static
electricity precautions:
1. Before handling any components, discharge your body's static electric charge by touching a grounded surface.
2. Do not remove parts from their anti-static bags until you are ready to install them.
3. Do not lay parts on the anti-static bags! Only the insides are anti-static.
4. When handling parts, hold them by their edges and their metal mounting brackets.
5. Avoid touching comm board components or edge connectors that plug into slots when handling.
6. Never slide parts over any surface.
7. Avoid plastic, vinyl, and Styrofoam in your work area.
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
READ ALL RELATED MANUALS
Knowledge of all related procedures before you begin
work is important. Read and understand all manuals thor-
oughly. If you do not understand a procedure, ask some-
one who does.
WARNING
This console contains high voltages which can be lethal. It is also connected to low
power devices that must be kept intrinsically safe.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT,
RESULTING IN SERIOUS INJURY OR DEATH.
1. Turn off and tag power at the circuit breaker. Do not connect the console AC
power supply wires at the breaker until all devices are connected.
2. Attach conduit from the power panel to the console's Power Area knockouts
only.
3. Comply with all applicable codes including: the National Electrical Code;
federal, state, and local codes; and other applicable safety codes.
Connecting power wires to a live circuit can cause electrical shock that may result in
serious injury or death.
Routing conduit for power wires into the intrinsically safe compartment can result in
fire or explosion resulting in serious injury or death.
WARNING
OFF

3
Introduction ProtoNode Gateway
ProtoNode Gateway
Figure 1. FPC-N54 Connectivity Diagram (TLS450PLUS Shown)
T 2: DELIVERY NEEDED 12/20/201206:01 PM
TankOverview
TANK1: reg
FuelVolume 3655
FuelHeight 38.6
Ullage100% 6345
Temperature 61.9
WaterHeight 3.0
1Warning(s)
0Alarms(s)
Print (0)
Home
Favorites
Menu
Actions
Overview
TANK2: diesel
FuelVolume 1600
FuelHeight 20.6
Ullage100% 8345
Temperature 60.8
WaterHeight 0.0
!
One Serial Device
Ethernet Field Protocol
Local Network
Controller A
RS-485 Field Protocol
Local Network

4
Quick Start
1. Record the information about the unit. (“Record Identification Data” on page 5 )
2. Check that the ProtoNode and customer device COM settings match. (“Configuring Device Configurations” on
page 5)
3. Connect the ProtoNode 3 pin RS-232 R1 port to the RS-232 network connected to each of the devices. (“RS-
232 Network” on page 6)
4. If using a serial field protocol: Connect the ProtoNode 3 pin RS-485 R2 port to the field protocol cabling.
(“RS-485 Network” on page 7)
5. Connect power to ProtoNode 3 pin power port. (“Power-Up ProtoNode” on page 8)
6. Connect a PC to the ProtoNode via Ethernet cable. (“Connect the PC to the ProtoNode” on page 9
7. Setup Web Server Security and login via web browser. (“Setup Web Server Security” on page 10)
8. Use a web browser to access the ProtoNode Web Configurator page to select the profile of the device
attached to the ProtoNode and enter any necessary device information. Once the device is selected, the
ProtoNode automatically builds and loads the appropriate configuration. (“Setting ProtoNode Active Profiles”
on page 16)
9. Ethernet Network: If using an Ethernet field protocol, use a web browser to access the ProtoNode Web
Configurator page to change the IP Address. (“Ethernet Network: Setting IP Address for the Field Network” on
page 17)

5
Setup For ProtoNode
Record Identification Data
Each ProtoNode has a unique part number located on the side or the back of the unit. This number should be
recorded, as it may be required for technical support. The numbers are as follows:
FPC-N54 units have the following 3 ports: RS-485 + Ethernet + RS-485/RS-232.
Point Count Capacity
The total number of registers presented the device attached to the ProtoNode cannot exceed:
Configuring Device Configurations
•The connected serial device MUST have the same baud rate, data bits, stop bits, and parity settings as the
ProtoNode
•To set the ProtoNode’s COM settings, see “Select Field Protocol and Set Configuration Parameters” on
page 15.
•Table 3 specifies the device serial port settings required to communicate with the ProtoNode.
Table 1. ProtoNode Part Number
Model Part Number
ProtoNode FPC-N54-1759
Table 2. ProtoNode Total Registers
Part Number Total Registers
330020-840 5000
Table 3. COM Settings
Port Setting TLS-3XX/TLS4XX
Protocol V-R Interface
Baud Rate 9600
Parity Odd
Data Bits 7
Stop Bits 1
Dieses Handbuch passt für folgende Modelle
1
Inhaltsverzeichnis
Andere Veeder-Root Tor Handbücher
Beliebte Tor Handbücher anderer Marken

LST
LST M500RFE-AS Bedienungsanleitung

Kinnex
Kinnex Media Gateway Bedienungsanleitung

2N Telekomunikace
2N Telekomunikace 2N StarGate Bedienungsanleitung

Mitsubishi Heavy Industries
Mitsubishi Heavy Industries Superlink SC-WBGW256 Bedienungsanleitung

ZyXEL Communications
ZyXEL Communications ZYWALL2 ET 2WE Bedienungsanleitung

Telsey
Telsey CPVA 500 - SIP Bedienungsanleitung