TECHNICAL DATA
June 1, 2011
6” MODEL G-6000P PREACTION
WITH ELECTRIC RELEASE
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Preaction 346a
1. DESCRIPTION
The 6” Model G-6000P Electric Release Preaction System Riser Assembly can be used as a
Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction
System with Electric/Pneu-Lectric Release. These �reaction systems are commonly usedThese �reaction systems are commonly used
where it is im�ortant to control accidental water discharge due to inadvertent damage to the
com�lete as shown in Figure 8. This pilot operated externally reset valve also in-
cludes an internal check diaphragm, which eliminates the need for a separate
check valve being installed in the system riser.
A. Viking Supervised Single-Interlocked Electric Release Preaction Systems
Utilizing the Viking G-6000P Valve
The system �i�ing is �ressurized with air or nitrogen as required by NFPA 13 for su-
interlock systems). This feature serves to �revent undetected leaks on the system �i�-
ing network. If the system �i�ing or a s�rinkler is damaged, the su�ervisory �ressure
is reduced and a “low air” su�ervisory alarm is activated.
-
lenoid valve controlled by an a��roved release control �anel with com�atible detection
When the solenoid o�ens, the �riming water is relieved from the internal �rime chamber assembly. The �rime chamber assembly
B. Viking Supervised Double-Interlocked Electric/Pneu-Lectric Release Preaction Systems Utilizing the Viking
G-6000P Valve.
The system �i�ing is �ressurized with air or nitrogen to serve both as a means of su�ervising the integrity of the �i�ing network
and as one �ortion of the system release o�eration. This feature serves to �revent undetected leaks on the system �i�ing net-
work. If the system �i�ing or a s�rinkler is damaged, the su�ervisory �ressure is reduced and a “low air” su�ervisory alarm is
activated.
electric solenoid and an additional “low air” alarm switch are connected to a com�atible release
control �anel and com�atible detection devices. The release control �anel is �rogrammed so that a signal from both a release
device and the low air alarm switch must be received before the solenoid is allowed to o�en. The air �ressure switch has two
inde�endently o�erating connections. The high side is wired as a low air su�ervisory switch, and the low side is wired as low air
and the low air alarm switch must o�erate in order to o�en the solenoid valve. When
assembly is forced o�en by the system water su��ly and water �asses through the G-6000P valve and internal check dia�hragm
2. LISTING AND APPROVALS
cULus Listed:
FM Approved: Preaction S�rinkler Systems
3. TECHNICAL DATA
Specifications:
vFactor: 811
Material Specifications:
Refer to Figure 11.
Flow
P
S
Form No. F_021311
htt�://www.vikinggrou�inc.com.
The Web site may include a more recent
edition of this Technical Data Page.
New �age 346a-m, issued June 1, 2011.