SETTING PULSE METER K FACTOR (LITRES PER PULSE)
Example only (default setting 10)
To reach this screen scroll through the setup screens by pressing ◄key from the MAIN
screen. The default (factory) setting for the K factor of the pulse meters is 10 litres per
pulse. To change the K factor press Enter to get the flashing cursor prompt. Enter the
new K factor of 1,5,10 or 100 litres per pulse and then press Enter again to confirm.
Press ▲key to return to MAIN screen.
SET HIGH FLOW (HF) TIMES FOR DAYS OF WEEK
Example only
To reach this screen scroll through the setup screens by pressing ►key from the
MAIN screen.
This screen and the six following screens enable a daily time period to be entered
during which high usage is anticipated. During these time periods High Flow
parameters apply. See - SETTING MAXIMUM HIGH FLOW RATE
Times outside this period are by default low usage during which time Low Flow
parameters apply. See - SETTING MAXIMUM LOW FLOW RATE
Press Enter to show the flashing cursor. Enter the time period FROM and then TO
using the numeric keys (in 24Hr format). Confirm by pressing the Enter key. Press ►
key to continue to the next day of the week or press ◄key for the previous day.
IT IS IMPORTANT THAT THE FOLLOWING IS READ AND UNDERSTOOD
Example: The default High Flow (HF) time settings are from 08:00 to 18:00 Mon to Fri with no High
Flow (HF) time period set on Sat or Sun. This would apply to a typical office installation where the
High Flow parameters would apply during the working (occupied) day and the Low Flow (LF)
parameters would apply at night and over the weekend (unoccupied).
For a restaurant or club where High Flow (HF) times span midnight eg from 8pm to 3am, simply
swap the HF & LF times and settings. Enter the times of low usage as HF during the day eg from
03:00 to 20:00 with the corresponding flow settings.
HF settings do not have to be greater than LF settings, they are just labels.