Ytc YT-700 Series Bedienungsanleitung

SOLENOID VALVES PRODUCT MANUAL
YT-700 SERIES
VERSION 1.02

2 YT-700 series
Contents
1. Introduction …………………………………………………………………………………………… 3
1.1 General information for the users ………………………………………………………………. 3
1.2 Manufacturer Warranty …………………………………………………………………………… 3
1.3 Explosion Proof Warning ……………………………………………………………………….. . 3
2. Product Description ………………………………………………………………………………….. 4
2.1 General …………………………………………………………………………………………….. 4
2.2 Main Features and Functions ……………………………………………………………………. 4
2.3 Label Description ………………………………………………………………………………….. 4
2.4 Product Number …………………………………………………………………………………… 5
2.5 Product Specification ……………………………………………………………………………… 5
2.6 Parts andAssembly – YT-700S (3 way)………………………………………………………….. 6
2.7 Parts andAssembly – YT-700D (4 way) ……………………………………………………..…. 6
2.8 Operation Logic – YT-700S (3 way)………………………………………………………………. 7
2.9 Operation Logic – YT-700D (4 way) ………………………………………………………………. 7
2.10 Dimension – YT-700S (3 way) ……………………………………………………………………. 8
2.11 Dimension – YT-700D (4 way) ……………………………………………………………………. 9
3. Installation ………………………………………………………………………………………………. 9
3.1 Safety ……………………………………………………………………………………………….. 9
3.2 Manual Switch……….. …………………………………………………………………………… 10
4. Connection ...……………………………………………………………………………………..…… 10
4.1 Safety ……….……….. …………………………………………………………………………… 10
4.2 Supply Pressure Condition ………………………………………………………………………. .10
4.3 Piping Condition …………………………………………………………………………………… 11
4.4 Connection – Actuator ……………………………………………………………………………...11
4.5 Connection – Power ………………………………………………………………………...…….. 12
5. Maintenance……………………………………………………………………………………………. 12
6. Trouble-Shooting ………………………………………………………………………………………. 13

3 YT-700 series
1. Introduction
1.1 General Information for the users
Thank you for purchasing Young Tech Co., Ltd products. Each product has been fully
inspected after its production to offer you the highest quality and reliable performance.
Please read the product manual carefully prior to installing and commission the product.
For the safety, it is important to follow the instructions in the manual. Young Tech Co.,
Ltd will not be responsible for any damages caused by user’s negligence.
The manual should be provided to the end-user.
Any modifications or repairs to the product may only be performed if expressed in this
manual.
The manual can be altered or revised without any prior notice. Any changes in
product’s specification, design, and/or any components may not be printed immediately
but until the following revision of the manual.
The manual should not be duplicated or reproduced for any purpose without prior
approval from Young Tech Co., Ltd, Gimpo-si, South Korea.
1.2 Manufacturer Warranty
For the safety, it is important to follow the instructions in the manual. Manufacturer will
not be responsible for any damages caused by user’s negligence.
Manufacturer will not be responsible for any damages or accidents as a result of any
alteration or modification of the product and its parts. If any alteration or modifications
are necessary, please contact Young Tech Co., Ltd directly.
Manufacturer warrants the product from the date of original purchase of the product for
one (1) year, except as otherwise stated.
Manufacturer warranty will not cover products that have been subjected to abuse,
accidents, alterations, modifications, tampering, negligence, misuse, faulty installation,
lack of reasonable care, repair or service in any way that is not contemplated in the
documentation for the product, or if the model or serial number has been altered,
tampered with, defaced or removed; damages that occurs in shipment, due to act of
God, failure due to power surge, or cosmetic damage. Improper or incorrectly
performed maintenance will void this limited warranty.
For detailed warranty information, please contact Young Tech Co., Ltd – South Korea.
1.3 Explosion Proof Warning
Please ensure the unit is being used and installed within the explosion proof certified
environment.
YT-700 series explosion proof grades are Ex d IIC T6 and can be used in zone 1.
Explosion proof type of cables and gaskets should be used, when explosion gases are

4 YT-700 series
present at the installation site.
Power should be turned off completely when opening product’s cover. When opening
the cover, ensure that there is no power remaining in any electrical parts nearby.
Blind plug is required when any port is not being used.
Flameproof certified sealing fitting and/or cable glands must be used. Power cable
must be at least 1mm2or 18AWG.
For external ground terminal, cable rug with surface area of more than 5.5mm2should
be used.
2. Product Description
2.1 General
Solenoid valve, YT-700 series, given AC or DC electric signal, outputs supply air pressure to
valve or changes the output port direction.
2.2 Main Features and Functions
Designed to be Ex d IIC T6 explosion proof grade.
Easy replacement of coil as both AC and DC type use same enclosure.
Can test the operation in manual switch without power source.
High durability as valve body is pneumatic pressure operating type.
Can be directly mounted on an actuator. (NAMUR design)
2.3 Label Description
Fig. 1: YT-700 Body Label
A. Model: Indicates the model number
B. Explosion Proof: Indicates certified explosion proof grade.
C. Air Supply (Max).: Indicates maximum supply pressure
D. Rating: Indicates allowable voltage.

5 YT-700 series
2.4 Product Number
2.5 Product Specification
Model YT-700
Valve Type 3 Way 4 Way
Max Sup. Pressure 0 ~ 0.4 Mpa
0 ~ 0.7 Mpa 0.1 ~ 1.0 Mpa
Flow Capacity
(Cv)
Output 0.2 (3 pie) at 0.4 Mpa 0.75
0.084 (1.6 pie) at 0.7 Mpa
Exhaust 0.093 N/A
Rating
AC 220V 9.5W (51mA) 13.5W (61mA)
AC 110V 4.8W (57.8mA) 14.5W (130mA)
DC 24V 3.8W (158mA) 13.5W (560mA)
Frequency 50 ~ 60 Hz
Explosion Proof Ex d IIC T6
Connection Type PT / NPT 1/4
Conduit Entry PF 1/4 (G1/2)
Coil Insulation Grade Class B
Ambient Temp. Operating -20 ~ 70’C
Explosion -20 ~ 50’C
Weight 0.8 kg (1.8 lb) 0.9 kg (2.0 lb)

6 YT-700 series
2.6 Parts andAssembly – YT-700S (3 way)
2.7 Parts andAssembly – YT-700D (4 way)

7 YT-700 series
2.8 Operation Logic – YT-700S (3 way)
As signal pressure is being supplied, the plunger (○
6) rises and creates secondary a gap
between the nozzle (○
9) and plunger (○
6) which results primary air pressure exhaustion.
When signal pressure has been turned off, the plunger (○
6) moves downward and blocks the
channel. At the same time, the air pressure will exhaust through the channel between the
plunger (○
6), vent (○
2), and body cap (○
1).
2.9 Operation Logic – YT-700D (4 way)
As signal pressure is being supplied, plunger (○
6) rises and creates a gap between the
nozzle (○
9) and plunger (○
6) which results primary air pressure to push down the spool (○
11 )
and exhausts air to OUT2 (C2). When signal pressure has been turned off, the plunger (○
6)
moves downward and blocks the channel. At the same time, air pressure pushes spool (○
11 )
upward and exhausts air to OUT1 (C1).

8 YT-700 series
2.10 Dimension – YT-700S (3 way)

9 YT-700 series
2.11 Dimension – YT-700D (4 way)
3. Installation
3.1 Safety
When installing a unit, please ensure to read and follow safety instructions.
Check unit’s specification and ensure to use as specified.
Follow other explosion proof procedures and safety precautions.
Use bypass valve or other supportive equipment to avoid entire system “shut down”.
YT-700 series is designed for explosion area.
Make sure all input and supply pressure to valve, actuator, and other related devices
must be turned off.

10 YT-700 series
3.2 Manual Switch
The manual switch can be adjusted by hand or by screw
driver (-). At the manual position (M), the valve can be
opened without power supply. At the automatic position (A),
the valve can be operated per input signal. DO NOT TURN
THE MANUAL SWITCH WITH FORCE, AS IT CAN BE
DAMAGED.
For YT-700D (4 way), the air channel will be switched as
below.
4. Connections
4.1 Safety
Supply pressure should be clean and dry air – avoiding moisture, oil or dust.
Always recommended to use air filter regulator (i.e. YT-200 series).
Young Tech Co., Ltd has not tested positioner’s operation with any other gases other
than clean air. Please contact Young Tech Co., Ltd for any questions.
4.2 Supply Pressure Condition
Dry air with at least 10℃lower than ambient temperature.
Avoid from dusty air. Positioner’s inner filter can only filter 5 micron or larger.
Avoid oil.
Comply with ANSI/ISA-57.3 1975(R1981) or ISA S7.3-1975(R1981).
Supply pressure range is 1.4 ~ 7 kgf/cm2(140-700 kPA)
Set air filter regulator’s pressure level 10% higher than actuator’s spring range pressure.
Dieses Handbuch passt für folgende Modelle
2
Inhaltsverzeichnis
Beliebte Steuereinheit Handbücher anderer Marken

Festo
Festo Compact Performance CP-FB6-E Stücklistenhandbuch

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Bedienungsanleitung

JS Automation
JS Automation MPC3034A Bedienungsanleitung

JAUDT
JAUDT SW GII 6406 Series Kurzanleitung

Spektrum
Spektrum Air Module System Bedienungsanleitung

BOC Edwards
BOC Edwards Q Series Bedienungsanleitung