ZEDAR Regency Bedienungsanleitung

ZEDAR TECHNOLOGIES, INC.
Regency Spa Controller
Owner’s Manual
10/19/2009
Copyright Zedar Technologies, Inc. 2009. Specifications and information in
this manual are subject to
change

Regency Owner’s Manual Page 2
Table of Contents
.0 PREFACE ............................................................................................................................................ 4
.0. Electrical Requirements ............................................................................................................ 4
1.0.1.1 Ground fault Circuit Interrupter (GFCI) ................................................................................. 4
.0. . . GFCI In- line wiring ........................................................................................................... 4
.0. . .2 GFCI 240Vac 3 wire circuit ............................................................................................... 4
.0. . .3 GFCI 20/240 Vac 4 wire circuit .................................................................................... 5
.0. . .4 GFCI Concerns ................................................................................................................ 5
.0.2 Risk of Electrical Shock .............................................................................................................. 5
.0.3 Owner’s Responsibilities ........................................................................................................... 5
2.0 OVERVIEW ......................................................................................................................................... 7
2.0. Control Panel ............................................................................................................................. 7
2.0.2 Relay Board ............................................................................................................................... 7
2.0.3 Temperature sensors. ............................................................................................................... 7
2.0.4 System features ........................................................................................................................ 7
2.0.5 System Default Settings ............................................................................................................ 8
2.0.6 System Recommendations........................................................................................................ 8
3.0 CONTROL PANEL ............................................................................................................................... 9
3.0. Spa Control Keys ....................................................................................................................... 9
3.0.1.1 Water Pump 1 Key................................................................................................................. 9
3.0.1.2 Water Pump 2 Key .............................................................................................................. 0
3.0.1.3 Blo er 1 Key ........................................................................................................................ 0
3.0.1.4 Blo er 2 Key ....................................................................................................................... 0
3.0.1.5 Done Key ............................................................................................................................. 0
3.0.1.6 Light Key .............................................................................................................................. 0
3.0.1.7 Auxiliary Key ........................................................................................................................ 0
3.0.2 Status Control Keys ................................................................................................................. 0
4.0 CONTROLLER OPERATION ...............................................................................................................
4.0. Normal Operation ...................................................................................................................
4.0.2 Temperature Setting ...............................................................................................................
4.0.3 Spa Programming ....................................................................................................................

Regency Owner’s Manual Page 3
4.0.3.1 Clock Format ....................................................................................................................... 3
4.0.3.2 Clock Setting ........................................................................................................................ 3
4.0.3.3 Date Setting ........................................................................................................................ 3
4.0.3.4 Silence Timer ....................................................................................................................... 4
4.0.3.5 Vacation Timer .................................................................................................................... 5
4.0.3.6 Spa Mode ............................................................................................................................ 6
5.0 SPA OPERATION .............................................................................................................................. 8
5.0. Normal Operation ................................................................................................................... 8
5.0.2 Overheat Operation ................................................................................................................ 9
5.0.3 Freeze Protection Operation................................................................................................... 9
6.0 SYSTEM SPECIFICATIONS ................................................................................................................ 2
6.0. Relays ...................................................................................................................................... 2
6.0.2 Electrical Outputs .................................................................................................................... 2
6.0.3 Temperature ........................................................................................................................... 22
7.0 INSTALLATION INSTRUCTIONS ........................................................................................................ 23
7.0. Control Panel ........................................................................................................................... 23
7.0.2 System Controller .................................................................................................................... 23
7.0.2.1 Flo Sensor/ Pressure S itch .............................................................................................. 23
7.0.2.2 Thermo ell ......................................................................................................................... 23
7.0.2.3 Temperature Sensor ............................................................................................................ 23
7.0.2.4 Freeze Sensor ...................................................................................................................... 24
7.0.2.5 Heater ................................................................................................................................. 24
8.0 CONTACT INFORMATION ................................................................................................................ 25

Regency Owner’s Manual Page 4
1.0 PREFACE
1.0.1 Electrical Requirements
All Spa electrical wiring should be performed by a licensed electrician and must comply
with all NEC (National Electrical Code) and state and local code requirements.
The electrical loads for connections to this system MUST NOT exceed the rating
specified in this manual. Failure to comply with these specifications and/or improper
wiring may cause hazardous operating conditions and/or damage to the controller.
1.0.1.1 Ground fault Circuit Interrupter (GFCI)
Since January 994, a Ground Fault Circuit Interrupter is required by all electrical Spa
installations. The National Electrical Code (NEC) also states that a service disconnects
should be located near the Spa but no closer than 5 feet. A GFCI could be used for this
purpose.
All 20 Vac Spa require a dedicated 20 Amps GFCI service connection, all 240 Spa
require a dedicated 50 Amps GFCI service connection with a 6/3 AWG (four wire) all
copper conductors. In order to conserve electricity we recommend using 240 Vac
connections in all 240 Vac capable Spa.
It should also be verified that a dedicated service is used with no other circuits
connected to it.
1.0.1.1.1 GFCI In- line wiring
• Black and Red wires feeding the GFCI are connected to a properly sized circuit
breaker.
• White wire should be connected to the neutral bar and the Green is connected
to the ground bar.
1.0.1.1.2 GFCI 240Vac 3 wire circuit
A 240 Vac 3 wire service could be used if it does not operate any 20 Vac devices.
• Black and Red wires feeding the GFCI are connected to a properly sized circuit
breaker.
• White wire is not required and the Green is connected to the ground bar.

Regency Owner’s Manual Page 5
1.0.1.1.3 GFCI 120/240 Vac 4 wire circuit
A 240 Vac 4 wire service could be used if it does operate any 20 Vac devices.
• Black and Red wires feeding the GFCI are connected to a properly sized circuit
breaker.
• White wire should be connected to the neutral bar and the Green is connected
to the ground bar.
The White load wire must be connected to the neutral out terminal. Proper
installation of the neutral wire is essential for proper operation. If not wired
properly, the GFCI will trip when any of the 20 Vac devices is turned ON.
1.0.1.1.4 GFCI Concerns
If the GFCI does not stay engaged as soon as power is applied to the system, it could
indicate that it is not wired correctly. Please verify that all the connections are correct,
generally if the GFCI does not stay engaged, it is a wiring problem with the neutral wire.
The Neutral and the Ground wires cannot touch anywhere otherwise the GFCI will trip.
1.0.2 Risk of Electrical Shock
As a Spa owner some of the risks of electrical shock are but not limited to the following:
• All supply circuits must be disconnected before accessing the Relay Board
Terminals. The cover should only be removed by a qualified technician.
• Do not operate the Spa with the controller cover removed.
• Use copper wire only while installing the system.
• Do not allow any electrical appliance: lights, telephone, radios, televisions etc
within 5 feet of the Spa.
• Never try to operate any electrical device from inside the Spa.
1.0.3 Owner’s Res onsibilities
As a Spa owner some of your responsibility are but not limited to the following:
• Protect your Spa from freezing or any other damage.
• Do not permit children to use or access to the spa unless they are supervised at
all times.

Regency Owner’s Manual Page 6
• Before entering the Spa make sure that the water temperature never exceeds
04°C (40°C). Water temperature between 00°F (38°C) and 04°F (40°C) are
considered safe for adults use.
• Pregnant or possible pregnant women should limit Spa’s water temperature to
00°F (38°C) since excessive water temperature has a high potential for causing
fetal damage.
• The use of alcohol, drugs or medications before or while using the Spa made lead
to unconsciousness that could lead to drowning.
• Persons with infections or sores should never use the Spa. Temperature of the
spa may allow the growth of infectious bacteria if the system is not properly
sanitized.
• Persons using medication, suffering from obesity, history of heart disease, low or
high blood pressure, diabetes or problems with the circulatory system should
consult a physician before using the Spa.
• Adults should never use the Spa alone, always enter and exit the Spa slowly.

Regency Owner’s Manual Page 7
2.0 OVERVIEW
The Regency Spa Controller is a microprocessor based system designed to provide the
users with an efficient and effective way of managing their enjoyment time while using
a spa. It has been designed to provide you with maximum flexibility during the spa use
by allowing easy system programming that requires minimum effort. However it will
allow you to configure the inner workings of the spa if you choose to. The Spa could be
tailor to satisfy the user needs.
The Regency controller system package consists of:
2.0.1 Control Panel
This controller is installed on the spa consist of 0 push buttons (keys) that are used to
control pumps, air blowers, lights, any other auxiliary equipment as well as to program
the system. Some of its features are:
• One 2 lines 24 characters LCD display.
• 0 momentary buttons used to select operation and controller settings.
• Operating temperature 0°C to 85°C.
2.0.2 Relay Board
This board has been designed for installation below the Spa’s skirt. It provides the user
with the following features:
• Could control for 2 pumps, 2 blowers, 2 auxiliary, lights, ozone and heater.
• Inputs for sensing control switches.
• Inputs for temperature sensors.
• RJ45 connector for communication with the top controller.
• 20 or 240 Vac +/- 0% operation.
2.0.3 Tem erature sensors.
The Regency system uses 2 temperature sensors: one sensor is installed on the heater
surface to provide overheat freeze protection and the second is used to monitor the water
temperature.
2.0.4 System features
The Regency controller has been designed to meet all of the following conditions:

Regency Owner’s Manual Page 8
• When the water temperature is below the set point, the low speed will be turned
on, the pressure switch will be detected to determine that water is flowing through
the pipes and then the heater will be turned on.
• When the water temperature goes over the set point the heater will be turn on but
the low speed pump will continually run for one minute.
• The Ozone generator will be turned ON only when the pump is running in low
speed. It will be turned OFF if the pump is switch to high speed.
2.0.5 System Default Settings
All default settings of the controller including the date and the time of the day are
retained after power is removed from the system.
2.0.6 System Recommendations
In order to keep your Spa in optimum condition we recommend:
• Keep you Spa user’s manual which explain how to care for your spa.
• Maintain proper level of PH.
• Sanitize you Spa regularly; it will extend the life of your equipment.
• Keep proper chemical level in the Spa to prevent premature heater as well as
other components failure.
Please use this manual as a reference while m difying the perati n f
y ur Spa.

Regency Owner’s Manual Page 9
3.0 CONTROL PANEL
The control panel is installed on the lip of the spa for easy and convenient access. The
Regency model, consist of:
• 2 lines 20 character LCD display used to communicate the user Spa temperature,
Time of the day as well as date during normal operation. It is also use during
programming to convey all the information to the user.
• 0 membrane switches used to control all the different function of the Spa. They
are divided in 2 group:
Spa C ntr l keys: Pumps, Air Blower, Spa light, Done, Extra.
Status C ntr l keys: Up, Down, Programming
N te
If any of the keys in the control board is held depressed for more
than 30 seconds it ill be disable, a message ill be displayed
indicating this failure; after the depressed key is released it ill
be reactivated. This feature ill not allo the system to lock up
because of a collapsed or defective key.
3.0.1 Spa C ntr l Keys
There are 7 Spa control keys: Pump , Pump 2, Air , Air 2, Done, Spa Light and Auxiliary.
A Spa should have at least one water pump; optionally it could have a second or third pump, an
air blower, a mister or a fiber optic light setup and an extra device.
3.0.1.1 Water Pump 1 Key
Will control the primary pump which is usually a dual speed pump, the low speed is
used to filter the Spa and/or to circulate the water while the Spa is being heated. A
second depression of this switch will toggle between the high and the low speed of the
pump. If your primary pump is a single speed (HIGH speed) only, this switch will turn the
pump ON and OFF.

Regency Owner’s Manual Page 1
N te
If the Spa is equipped ith a circulating pump only, it ill be
used for filtration and heating instead of the lo speed pump.
3.0.1.2 Water Pump 2 Key
Will control a secondary pump On/OFF.
3.0.1.3 Blo er 1 Key
Will activate the primary air blower (bubbler). It is an ON/OFF key
3.0.1.4 Blo er 2 Key
Will activate the secondary air blower (bubbler). It is an ON/OFF key
3.0.1.5 Done Key
This key should be depressed after the Spa had been used. A depression of this key will
signal to the microcontroller in the system that Spa’s software management should take
over and execute the filtration cycles, heat maintenance, etc.
3.0.1.6 Light Key
Will activate the lights used in the Spa. It is an ON/OFF key
3.0.1.7 Auxiliary Key
Will activate any device attached to the Auxiliary relay in the system board. It is an
ON/OFF key
3.0.2 Status C ntr l Keys
There are 3 status control key: UP, Down and Programming. Their function will be
explained during the Spa Programming section of this manual.
Inhaltsverzeichnis

















