Page 6
© 2023 ABB. All rights reserved. CPS6000_Series II External Distribution_QSG Version 2.0
Ordering Codes Descriptions
CC109142980 QS873A Thermal Probe
CC848817024 B: 10’ controller to thermal probe wireset
CC109157434 B: 20’ controller to thermal probe wireset
CC848822560 C: 1’ thermal probe to thermal probe wireset
848719803 C: 5’ thermal probe to thermal probe wireset
CC848822321 C: 10’ thermal probe to thermal probe wireset
Ordering Codes Descriptions
108958422 ES771A Voltage Monitor Card
CC848791517 D: 2 ½’ ES771A to probe wireset
CC848797290 D: 6’ ES771A to probe wireset
848719829 D: 10’ ES771A to probe wireset
CC848791500 G: 4’ ES771A to ES771A or controller wireset
848652947 G: 10’ ES771A to ES771A or controller wireset
Temperature Measurement Temperature and Voltage Measurement
Information: Office Alarm Connections
All standard controller output alarm connections are available from the output connector. Connector J4 provides
access to the primary customer alarm output interface. Connector J4 is a 20-pin right angle header with latching
capability. Standard color coded cable assemblies are available.
Office Alarm Cables:
Discrete Wire 15ft: CC109157442
Discrete Wire 50ft: CC848817635
Discrete Wire 150ft: CC848817643
Contact technical field support for additional cable options.
48V Standard Pin Color
PCR Power Critical 1BL
PCR_C 11 BL-BK
PMJ Power Major 2O
PMJC 12 O-BK
PMN Power Minor 3G
PMN_C 13 G-BK
R1 Battery on Discharge (BD) 4BR
R1_C 14 W-BK
R2 AC/Multiple AC Fail (ACF) 5S
R2_C 15 BK-W
R3 Rectifier Fail (RFA) 6BL
R3_C 16 BL-R
R4 Very Low Voltage 7O
R4_C 17 R
R5 Fuse Alarm (External FAJ2) 8G
R5_C 18 R-G
R6 High Voltage (HV) 9BR
R6_C 19 R-W
R7 Unassigned
(User Configurable) 10 S
R7_C 20 R-BK
Information: 1 – Wire Battery Temp and Voltage Monitor
Battery Monitoring is accomplished with a “Daisy Chained” series of probes connected to J3. The Probes are used
to monitor battery temperature and voltage (ES771 required to monitor voltage). Bolt the Probe under the “–”
terminal connector hardware; NOT under the connecting Lug.