Adveco EB0025 Bedienungsanleitung

Installation,
Operation and
Maintenance Manual
PRODUCT MANUAL
TR500010
EB0025/EB0028/EB0030
Control Panels with Automatic Changeover, SMS and HR
PRACTICAL, EFFICIENT & SUSTAINABLE
BUILDING SERVICES SOLUTIONS

PRACTICAL, EFFICIENT & SUSTAINABLE BUILDING SERVICES SOLUTIONS
2
Warnings
This manual should be read and understood carefully prior to installation or operation of any part of the
EB0025, EB0028 or EB0030 control panel. Failure to read this manual or to follow its printed instructions may
lead to personal injury, damage to the panel and damage to the water heating installation. These instructions
should be kept in a safe and accessible place near the water heating unit.
The EB0025, EB0028 or EB0030 control panel should be stored in a safe place prior to installation to prevent
damage.
Copyright © 2016 Adveco Limited. All rights reserved.
No part of this publication may be copied, reproduced, altered and/or published by any means without the prior
written approval of Adveco Limited.
Any brand names mentioned within this publication are registered trademarks of their respective owners.
Adveco Limited reserve the right to modify specifications in this manual at any time and without notification.
Adveco Limited accept no liability for third party claims arising from unauthorised use and/or use other than
that as directed within this manual.
EB0025-EB0028-EB0030 Control Panel - Installation and maintenance manual

page
4
5
5
6
7
8
9
13
21
22
Contents
Product Description
Installation Instructions
1. Requirements of the Installer
2. Location
3. Installation Procedure
Contact and Warranty Information
3
58
27
57
EB0025-EB0028-EB0030 Control Panel - Installation and maintenance manual
EB0025
1. Technical Details
2. Wiring Diagram
3. Troubleshooting
Maintenance Instructions
Components & Terminology
41
42
47
EB0028
1. Technical Details
2. Wiring Diagram
3. Troubleshooting
EB0030
1. Technical Details
2. Wiring Diagram
3. Troubleshooting

Product Description
The Adveco range of EB0025, EB0028 and EB0030 control panels are complete wiring stations for a water
heating installation, providing power to primary and secondary heat sources to ensure a reliable supply of hot
water. Delivered prewired and ready to wall mount in an IP65-rated protective box, the panels include
automatic changeover functions from duty to a backup heat sources in response to a fault, a change in hot water
demand or differential tariff supplies.
All control panels include a system isolator, internal aerial, overload protection and volt-free contacts for BMS
error signal support. Optional heat recovery controls are included within the panels as standard, for use with the
Adveco HR001 Heat Recovery Box and Danfoss condenser units, or Scutts condenser units. Also included in
each panel is a GSM module designed to keep off-site facilities management informed of any appliance faults;
this will automatically send text and/or email alerts to the relevant service contacts immediately upon failure of a
primary heat source, as well as delivering a periodic healthy status report.
Adveco EB0025 Control Panel:
The EB0025 control panel includes a gas to electric auto-changeover function and is designed for use with an
SGE, SGS or BFC condensing gas-fired water heater with an electric backup heating element of up to 9kW
capacity. This produces a highly efficient and reliable water heating solution, with a gas-fired primary heat
source optionally supporting a fridge/freezer heat recovery process with additional electric immersion heater
backup.
Adveco EB0028 Control Panel:
The EB0028 control panel includes an electric to electric changeover function and is designed for use with
systems containing an ITE indirect electric water heater, or an IT indirect tank plus ST storage tank, with an
EB0027 dual-circuit 18kW/9kW electric immersion heater. The primary electric immersion heater can be used
to support an optional heat recovery process or provide the entire heating load, and contains an inbuilt 9kW
backup to ensure a reliable supply of hot water. The control panel also includes a seven-day timeclock and
controls for use with a destratification pump to be used for anti-Legionella purge cycling.
Adveco EB0030 Control Panel:
The EB0030 control panel includes a gas to electric auto-changeover function and is designed for use with a
BFC or SGS condensing gas-fired water heater in addition to an IT indirect tank with backup electric immersion
heater. The primary gas burner serves as a highly efficient source of hot water and can support preheating by
optional fridge/freezer heat recovery processes, with up to 9kW of backup electric heating capacity. The
control panel additionally includes a seven-day timeclock and controls for use with a destratification pump to be
used for anti-Legionella purge cycling.
This system is available as a fully packaged, prefabricated solution, enclosed within purpose-built GRP housing
for rooftop installation.
Available Ancillaries:
Adveco strive to offer a complete range of water heating solutions to meet the needs of an end user. The
following ancillaries are available and are compatible with the EB0028:
PRACTICAL, EFFICIENT & SUSTAINABLE BUILDING SERVICES SOLUTIONS
4
EB0025-EB0028-EB0030 Control Panel - Installation and maintenance manual

Installation Instructions
1. Requirements of the Installer
All installation work for this immersion heater kit must be carried out by an individual with the relevant
qualifications and experiences to work with electrical systems and who is registered with an electrical regulatory
body such as NICEIC, and should be compliant to:
• BS 7671:2008 IEE Wiring Regulations 17th Edition.
• BS EN 806 all parts.
• BS EN 60335-2-74, IEC 60335-2-74.
• Building Regulation Part G.
• Building Standards (Scotland) Regulations.
• Water Regulations.
• Health and Safety and Work Act 1974.
• Local Byelaws.
And any complementing or superseding documentation.
Adveco Limited accept no responsibility for failure to comply with the above or with safe working practices.
2. Location
For GSM module responsiveness, it is recommended that the control panel should be sited in an above ground
area with good signal reception . Basement installations may require a remote antenna (not included).
The control panel should be mounted at an accessible height on a wall adjacent to the water heater. The wall
should be strong enough to hold the panel and constructed of a suitable material to accommodate the panel
fixings. Should the control panel be installed away from the water heater, additional isolators must be included
near the heater and its components.
Cable connections for all panels enter through the floor of the enclosure and require 100mm of exterior
clearance. All panel dimensions are included in the technical details on pages 7-9 and should be consulted prior
to installation.
The EB0025 features a removable front panel and is suited for installation within cupboards or tight spaces. A
minimum frontal clearance of 300mm is recommended for access.
The EB0028 and EB0030 models feature a hinged front panel. A frontal clearance of no less than 500mm must
be present in order to open the panel door.
5
EB0025-EB0028-EB0030 Control Panel - Installation and maintenance manual

• Remove the back panel and its mounted components from the enclosure, resulting in an empty box in
order to prevent accidental damage to the components. Mark out and drill the necessary number of
holes for glands on the floor of the panel. One gland is required for each cable feeding into the panel.
Gland sizes must be correct for the cable they will accommodate.
• Mark out the mounting location on the wall using the supplied brackets. Drill and plug the wall, then
reaffix the back panel to the box and mount the complete assembly. Ensure the box is properly
assembled and securely fixed to the wall.
• A 400V rotary isolator should be installed feeding the control panel to provide means for safe isolation
of the system.
• Cable sizes should be dictated by the electrical load of each component. The terminals within the
control panel are of sufficient size to accommodate the largest cables that may be required.
• All cables must have correctly sized ferrules on the ends. A double ferrule must be used when two
cables are used in one connection.
• All cable glands must provide mechanical protection against pull-out. Within the box the cable insulation
should be cut back to near the gland.
• Unused heat recovery connections should be left empty.
• No additional link wires are required. All needed links are pre-installed.
• Following installation, the panel should be tested to and meet the requirements of NICEIC.
Installation Instructions
3. Installation Procedure
Warning: 400V circuits are present within the control panel. Suitable caution should be taken during the
installation process.
PRACTICAL, EFFICIENT & SUSTAINABLE BUILDING SERVICES SOLUTIONS
6
EB0025-EB0028-EB0030 Control Panel - Installation and maintenance manual

Maintenance Instructions
At minimum, the control panel should be checked annually by a qualified engineer. The unit must be fully
isolated from the mains electricity supply prior to any inspection or maintenance work being carried out. The
maintenance procedure should include at least the following checks:
• Visually inspect the interior of the panel for signs of overheating or distress. Any visible dust and dirt
should be removed with careful use of compressed air only.
• Press the test buttons of all contactors to ensure free travel.
• Check the tightness of every terminal connection within the control panel, including building cable
connections.
• With the panel still open, turn on the isolator and return power to the system. Warning: 400V/3ph
power will now be live within the panel. Exercise suitable caution.
• Confirm that the lead heat source is still operational.
• Simulate a fault within the lead heat source. For an electrical unit, trip the circuit breaker supplying the
primary heater. For a gas appliance, put the water heater in to fault.
• Confirm that a fault notification has been received from the GSM module. This can be done by checking
with the manager of the store. Fault messages may take several minutes to arrive by email.
• Check the settings and operation of all thermostats within the system.
• Isolate the system and close the panel door.
• Check the time and programme of the programmable clock (if installed). The clock controls the
destratification pump which should run no less frequently than twice per week, for two hours per cycle.
7
EB0025-EB0028-EB0030 Control Panel - Installation and maintenance manual

EB0025
1. Technical Details
EB0025
415V/3ph/50Hz
10kA
16A/phase
Internal
400mm
300mm
160mm
5kg
Adveco Order Code:
Supply:
Fault level:
Max load current:
Aerial:
Height:
Width:
Depth:
Weight:
• E0047: Control panel with gas to electric auto-changeover function. Includes main isolator feeding a
gas-fired water heater and an immersion heater, plus circuit breakers, volt-free contacts for BMS
support and heat recovery options.
• E0012: GSM modem for automatic SMS or email notification of faults.
Included Parts:
•EB0029: 9kW electric immersion heater assembly for use with BFC and SGS 30-60 water heaters
• 0304296S: 7.5kW electric immersion heater for use with SGE water heaters
Compatible Ancillaries:
•SGE, SGS and BFC condensing gas-fired water heaters
• HR001 Heat Recovery Box
Suitable for use with:
8
PRACTICAL, EFFICIENT & SUSTAINABLE BUILDING SERVICES SOLUTIONS
EB0025-EB0028-EB0030 Control Panel - Installation and maintenance manual

© Copyright
9
EB0025-EB0028-EB0030 Control Panel - Installation and maintenance manual
EB0025
2. Wiring Diagrams

EB0025-EB0028-EB0030 Control Panel - Installation and maintenance manual
© Copyright
PRACTICAL, EFFICIENT & SUSTAINABLE BUILDING SERVICES SOLUTIONS
10