Antrax MultiBox-LAN Bedienungsanleitung

antrax Datentechnik GmbH
[email protected] - www.antrax.de
MultiBox-LAN
•LAN interface
•watchdog funcionality
•relay ver ion
•en or input for temperature and humidity mea urement
•integrated control panel
Manual
18.02.2011
- 1 -
Ha enbrink 4, 32052 Herford, Germany Tel. +49 (0) 5221 929660 Fax +49 (0) 5221 9296628

antrax Datentechnik GmbH
[email protected] - www.antrax.de
Content
Safety In truction .................................................................................5
De cription............................................................................................5
Hardware..............................................................................................6
Connection and Initial Operation............................................................7
Statu LED.........................................................................................7
Configuration.........................................................................................8
DHCP................................................................................................8
Network etting with GBL_Conf............................................................8
View network etting ..........................................................................9
Change network etting ......................................................................9
Configuration via web interface.............................................................9
Configuration - Power Port ....................................................................10
Label...............................................................................................10
After power-up witch........................................................................10
If witching on after power-up, wait ....................................................10
After turning off, wait ........................................................................10
Watchdog Funktion...............................................................................11
Enable Watchdog...............................................................................11
Watchdog type..................................................................................11
ICMP Ping ......................................................................................11
TCP Ping ........................................................................................11
Ho t IP............................................................................................11
TCP Port...........................................................................................11
Ping interval.....................................................................................12
Ping retry.........................................................................................12
Configuration - IP Addre .....................................................................12
Ho tname........................................................................................12
IP Addre ........................................................................................12
Netma k..........................................................................................12
Gateway..........................................................................................12
U e DHCP.........................................................................................12
Configuration - IP ACL...........................................................................13
Reply ICMP-Ping reque t ...................................................................13
Enable IP Filter..................................................................................13
IP Acce Control Li t.........................................................................14
Configuration - HTTP.............................................................................14
HTTP Port.........................................................................................14
Enable HTML Auto Refre h..................................................................14
Require HTTP Pa word......................................................................15
- 2 -
Ha enbrink 4, 32052 Herford, Germany Tel. +49 (0) 5221 929660 Fax +49 (0) 5221 9296628

antrax Datentechnik GmbH
[email protected] - www.antrax.de
Check Pa word on tart page.............................................................15
Configuration - Alarm Beeper.................................................................16
Activate Beeper.................................................................................16
Ampere limit.....................................................................................16
Configuration - Me age .......................................................................17
Peak mea urement period..................................................................17
Generate Temperature Me age .........................................................17
Max Temperature..............................................................................17
Min. Temperature..............................................................................17
Configuration - SNMP............................................................................18
Enable SNMP-get...............................................................................18
Community public..............................................................................18
Enable SNMP- et...............................................................................18
Community private............................................................................18
Download SNMP MIB..........................................................................18
SNMP..............................................................................................18
SNMP-communitie ............................................................................19
MIB.................................................................................................19
SNMP-trap ......................................................................................19
Configuration - SNMP Trap Receiver Li t...................................................20
Enable Trap .....................................................................................20
Trap Ver ion.....................................................................................20
Configuration - Sy log...........................................................................21
Enable Sy log...................................................................................21
Sy log Server IP................................................................................21
Sy log Port.......................................................................................21
Sy log.............................................................................................21
Configuration - E-Mail............................................................................22
Enable E-Mail....................................................................................22
E-Mail erver....................................................................................22
Sender addre .................................................................................22
Recipient addre ..............................................................................22
Enable Authentifiaction.......................................................................22
U ername........................................................................................22
Set new pa word.............................................................................22
Repeat pa word...............................................................................22
Operation............................................................................................23
Switching at the device......................................................................23
Operation via web interface....................................................................24
Switching.........................................................................................24
Batchmode.......................................................................................25
Sen or.............................................................................................25
- 3 -
Ha enbrink 4, 32052 Herford, Germany Tel. +49 (0) 5221 929660 Fax +49 (0) 5221 9296628

antrax Datentechnik GmbH
[email protected] - www.antrax.de
Feature ..............................................................................................27
Bootloader-Mode...............................................................................27
Firmware-Update...............................................................................27
Technical information.........................................................................28
Factory etting .................................................................................28
Support...........................................................................................28
- 4 -
Ha enbrink 4, 32052 Herford, Germany Tel. +49 (0) 5221 929660 Fax +49 (0) 5221 9296628

antrax Datentechnik GmbH
[email protected] - www.antrax.de
Safety Instructions
The MultiBox-LAN mu t be in talled only by qualified per onnel according to the following
in tallation and operating in truction .
The manufacturer doe not accept re pon ibility in ca e of improper u e of the MultiBox-LAN
and particularly any u e of equipment that may cau e per onal injury or material damage.
The MultiBox-LAN contain no u er-maintenable part . All maintenance ha to be performed
by factorytrained ervice per onnel.
Check if the power cord, the plug and the ocket are in proper condition.
The MultiBox-LAN can be connected only to 230V AC (50 or 60 Hz) ocket .
Alway connect the MultiBox-LAN to properly grounded power ocket .
The MultiBox-LAN i intended for indoor u e only. Do NOT in tall the device in an area where
exce ive moi ture or heat i pre ent.
Becau e of afety and approval i ue it i not allowed to modify the MultiBox-LAN without
our permi ion.
Plea e re pect afety advi e and manual of connected device .
The MultiBox-LAN i NOT a toy. It ha to be u ed or tored out or range of children.
Packaging material i NOT a toy. Pla tic ha to be tored out of range of children. Plea e
recycle the packaging material .
In ca e of further que tion , about in tallation, operation or u age of the device, which are not
clear after reading the manual, plea e do not he itate to a k our upport team.
Description
The remote power witch MultiBox-LAN enable you to witch the power for electrical device
via TCP/IP network and a erial interface. For in tallation, MultiBox-LAN i imply connected
to a power upply and to the local network.
After allocating a free IP addre for the MultiBox-LAN, each of the four Power Port can be
witched by any computer in the ame LAN via web-interface. The MultiBox-LAN offer the
po ibility to u e SNMP and Sy log. Furthermore, acce to the device can be protected via IP
acce control li t (IP-ACL) or HTTP pa word .
A temperature en or or a hybrid en or (temperature and humidity) can be connected to the
MultiBox-LAN.
A watchdog function for each power port i implemented.
The LED di play on the front i able to how the the total load.
The MultiBox-LAN di po e of a leek and turdy pla tic ca ing and can be placed on a
de ktop or mounted to a 19“ rack.
- 5 -
Ha enbrink 4, 32052 Herford, Germany Tel. +49 (0) 5221 929660 Fax +49 (0) 5221 9296628

antrax Datentechnik GmbH
[email protected] - www.antrax.de
Hardware
Content of delivery
·MultiBox-LAN
· manual
Connections
1) Statu LED
2) Network connection
3) Power port LED
4) Power indication
5) Button ok
6) Button elect
7) Power connection
8) Power port
9) Sen or connection
- 6 -
Ha enbrink 4, 32052 Herford, Germany Tel. +49 (0) 5221 929660 Fax +49 (0) 5221 9296628

antrax Datentechnik GmbH
[email protected] - www.antrax.de
Connection and Initial Operation
1. In ert the plug of the AC power cord into an electrical outlet. The MultiBox-LAN will
boot and i ready in a few moment .
2. Connect your network with the network connection of the MultiBox-LAN.
3. Connect up to four con umer (device ) to the power port of the MultiBox-LAN.
Status LED
The tatu LED how different tate of the MultiBox-LAN:
•tatu LED red: Device i not connected to the ethernet
•tatu LED orange: Device i connected to the ethernet, TCP/IP etting are not
allocated
•tatu LED green: Device i connected to the ethernet, TCP/IP etting allocated, device
i ready to u e
•tatu LED blink alternately red and green: Device i in bootloader-mode.
- 7 -
Ha enbrink 4, 32052 Herford, Germany Tel. +49 (0) 5221 929660 Fax +49 (0) 5221 9296628

antrax Datentechnik GmbH
[email protected] - www.antrax.de
Configuration
DHCP
After witch-on the MultiBox-LAN look for a DHCP erver and reque t an available IP
addre .
Plea e check the IP addre allocated to MultiBox-LAN in the DHCP erver etting to make
ure that the ame addre i u ed at every reboot. To turn OFF DHCP plea e u e the oftware
GBL_Conf.exe or u e configuration via the web interface.
Network settings with BL_Conf
For changing the network propertie manually, the program GBL_Conf.exe i required. Thi
tool i available for free on our web ite www.antrax.de. Furthermore GBL_Conf.exe enable
you to in tall firmware update and to re et MultiBox-LAN to it factory etting . Activate
bootloader mode of MultiBox-LAN and run GBL_Conf.exe. The program will earch
automatically for connected device and will di play their network configuration.
If the di played IP addre accord with the factory etting (192.168.0.2), there i either no
DHCP erver available in the network or no free IP addre could be allocated.
Enter a free IP addre and the according netma k in the entry ma k, then ave the e change
by clicking on Program Device SaveConfig. Re tart the firmware of MultiBox-LAN, o that the
change will take effect. Now click on Search in order to have the new network configuration
di played.
- 8 -
Ha enbrink 4, 32052 Herford, Germany Tel. +49 (0) 5221 929660 Fax +49 (0) 5221 9296628

antrax Datentechnik GmbH
[email protected] - www.antrax.de
View network settings
Start the program and go to Search -> All Devices. Select the appropriate device from the li t.
The current etting of the device are di played in the lower part of the left half of the program
window. If the di played IP addre i the default etting (192.168.0.2), there i either no
DHCP erver available in the network or no free IP addr could be et.
Change network settings
Active the Bootloader-Mode of the MultiBox-LAN and choo e:
Search -> BootLoader-Mode Devices onl
Fill the required etting and tore the change : Program Device -> Save Config
Deactive the Bootloader-Mode of the MultiBox-LAN, for the change to take effect. Then go
to: Search -> All Devices
The new network configuration i now di played.
Configuration via web interface
Go to the web ite of MultiBox-LAN. Enter the IP addre of MultiBox-LAN into the addre
line of your internet brow er: http://"IP address of MultiBox-LAN"/ and pre LOGIN..
To enter the configuration menu, click on "Configuration" on the upper left ide of the creen.
- 9 -
Ha enbrink 4, 32052 Herford, Germany Tel. +49 (0) 5221 929660 Fax +49 (0) 5221 9296628

antrax Datentechnik GmbH
[email protected] - www.antrax.de
Configuration - Power Ports
Label
A name with a maximum of 15 character can be entered here for each Power Port.
After power-up switch
The Power Port’ witching tate after a power-on of the device can be defined here (on, off,
remember last state).
If switching on after power-up, wait ...
A witching delay of a Power Port can be defined here that i applied after witch on of
the device. The delay can la t up to 8191 econd . Thi corre pond to approx. two 2 hour
and 20 minute .
After turning off, wait ...
While thi function i enabled, the Power Port will reactivate after the tated time, when
it got witched off.
- 10 -