Atronix 9885107 Bedienungsanleitung

Model Capacity (VA) Article number
a-TroniX UPS Edition One 6kVA 6000 9885107
a-TroniX UPS Edition One 10kVA 10000 9885108
06/2021 Seite 1
ONLINE UPS
Installation and
Operating Instructions
a-TroniX
UPS Edition One
6kVA, 10kVA

Page 2 06/2021
Installation and Operating Instructions
UPS Edition One 6kVA, 10kVA
INTRODUCTION
The publication and copyright of this documentation remain with the company:
AKKU SYS Akkumulator- und Batterietechnik Nord GmbH
Verbindungsweg 23 · 25469 Halstenbek / Hamburg · GERMANY
Telefon +49 4101 | 3 76 76-0 / Fax +49 4101 | 3 76 76-66
Thank you very much
for purchasing our a-TroniX series online UPS.
It is an intelligent, single-phase, high-frequency online UPS and meets the required safety
standards.
Due to its excellent electrical performance with a power factor of cos phi 1.0, as well as
perfect intelligent monitoring and network functions, it meets the world‘s most advanced
level.
With the a-Tronix Series Edition One, your installations are safely protected from power
supply problems and the functionality of your equipment is maintained.
Read carefully before use
Read this manual carefully before installation.
It contains important regulations and instructions for the use of this product and provides
technical support for the operator of the unit.
All rights reserved
AKKU SYS Akkumulator- und Batterietechnik Nord GmbH cannot be held responsible for
any inaccuracies or inappropriate information in this instruction manual.
The information in this document is subject to change without notice, but there is no
obligation to update it on an ongoing basis.
We reserve the right to make design and equipment changes to improve the production
process or the product. AKKU SYS GmbH accepts no liability for errors in this operating
manual and any consequences resulting therefrom.

06/2021 Page 3
Installation and Operating Instructions
UPS Edition One 6kVA, 10kVA
Table of Contents
Page
1. Important safety instructions 4
1.1 Symbols used in this guide 6
2. Product Introduction 7
2.1 Product view (UPS 6-10 kVA) 7
2.2 The principle of the product 9
2.3 Product Category 9
3. Installation 10
3.1 Unpacking and inspection 10
3.2 Installation Note 10
3.3 UPS input and output connection 11
3.4 Communication cable connection 12
4. Panel display, operation and running 13
4.1 Start up and turn off UPS 13
4.1.1 Start up operation 13
4.1.2 Turn off operation 13
4.2 Faceplate display 14
4.2.1 Faceplate display illumination 14
4.2.2 LCD display 15
4.3 Parameter settings 17
4.3.1 Mode-setting 17
4.3.2 Output voltage class setting 18
4.3.3 Output frequency setting 18
4.3.4 Battery capacity setting 19
4.3.5 Battery quantity setting 19
4.3.6 Bypass Volt-Hi setting 20
4.3.7 Bypass Volt-Lo setting 20
4.3.8 Buzzer Mute Setting 21
4.3.9 Battery Test Setting 21
4.3.10 Parallel ID setting 23
4.3.11 Parallel quantity setting 23
4.3.12 Parallel redundancy quantity setting 24
4.4 Alarm Information 24
5. Maintenance 26
5.1 Battery maintenance 26
6. Troubleshooting 27
7. Specification 28

Page 4 06/2021
Installation and Operating Instructions
UPS Edition One 6kVA, 10kVA
1. Important safety instructions
Be sure to observe all warnings and operating instructions in this manual. Keep this
manual in a safe place and read the following instructions carefully before installing and
operating the unit.
The system may only be installed and connected by trained electricians in compliance
with the relevant safety regulations.
The operating instructions must be read and understood by all personnel and specialists
who are responsible for the operation, cleaning as well as disposal of the unit.
Dangerous voltages and high temperatures are present inside the UPS. Observe the
local safety instructions and the corresponding laws during installation, operation and
maintenance, otherwise personal injury or damage to the unit may occur. The safety
instructions in this manual serve as a supplement to the local safety instructions.
Our company accepts no liability for damage caused by failure to observe the safety
instructions.
The UPS as well as the associated components may only be used for the purpose
corresponding to their design - to supply electrical devices (230 V AC) which in total do
not exceed the rated power. Any other use or use beyond this is considered improper and
may result in personal injury, property damage and/or damage to equipment
Please note the following:
■ Don’t use the UPS when the actual load exceeds the rated load.
■ Internal short circuit of the UPS will cause electric shock or re. So don’t place
the containers equipped with liquid on the top of the UPS so as not to cause
danger of electric shock.
■ Do not place the UPS in a location with high temperature or humidity,
corrosive gases or much dust.
■ Ensure good air circulation between the inlet opening at the front and the
outlet opening at the back to prevent excessive heating.
■ Avoid direct sunlight or the proximity of heat-emitting objects.
■ If smoke appears on the UPS, please switch off the power as soon as possible
and contact your supplier.
■ Work on accumulators is to be carried out and supervised only by personnel
with appropriate expertise in the required safety rules. Unauthorised persons
must be kept away from accumulators.
■ There are high capacity batteries in the UPS. Do not open or destroy them.
The released electrolyte is dangerous for people and the environment. There is
a risk of explosion. If internal maintenance or battery replacement is required,
contact your supplier.

06/2021 Page 5
Installation and Operating Instructions
UPS Edition One 6kVA, 10kVA
■ When changing batteries, always insert the same number and type of
batteries.
■ Batteries or their connections can cause electric shocks.
■ If short circuits occur on batteries, touching the live parts can cause severe
burns.
■ Batteries must never be brought into contact with heat sources or ames.
■ Do not attempt to dispose of the batteries by burning them.
Defective accumulators must be disposed of in an environmentally friendly
manner. Do not throw them in the household waste under any circumstances
and observe the local disposal regulations.
Use the certied and professional recycling service of our AkkuSys team.
For more information, contact us on the order hotline +49 4101/376760,

Page 6 06/2021
Installation and Operating Instructions
UPS Edition One 6kVA, 10kVA
1.1 Symbols used in this guide
In these operating instructions, the abbreviation UPS stands for:
Uninterruptible Power Supply.
Accumulators are usually used as energy storage for a UPS system. These are also
colloquially referred to as accumulators or batteries.
Warnings and notes are indicated by the corresponding symbols (pictograms) and must
be observed:
WARNING!
Warning of dangerous electrical voltage.
General warning of danger points.
Warning when handling accumulators.
NOTE:
This symbol indicates texts, notes or tips. Failure to take precautionary
measures may result in damage to the product and/or its functions or to an
object in its vicinity.
ENVIRONMENT:
Indicates recycling information.
Indicates assemblies or parts that must be disposed of properly.
Do not dispose of them in the household waste.

06/2021 Page 7
Installation and Operating Instructions
UPS Edition One 6kVA, 10kVA
2. Product Introduction
2.1 Product view (UPS 6–10 kVA)
6/10kVA Front Panel view 6/10kVA Rear Panel view
(without maintenance)
1) USB (to connect the UPS to a PC)
2) EPO (for emergency shutdown)
3) Parallel port 1
4) Parallel port 2
5) Intelligent slot
6) RS232
7) Input switch
8) Terminals (covered)

Page 8 06/2021
Installation and Operating Instructions
UPS Edition One 6kVA, 10kVA
6/10kVA Rear Panel view
(with maintenance)
1) USB (to connect the UPS to a PC)
2) EPO (for emergency shutdown)
3) Parallel port 1
4) Parallel port 2
5) Intelligent slot
6) RS232
7) Input switch
8) Terminals (covered)
9) Output switch
10) Maintenance bypass switch (covered)

06/2021 Page 9
Installation and Operating Instructions
UPS Edition One 6kVA, 10kVA
2.2 The principle of the product
UPS Principle Diagram
1. Mains input
2. Rectier
3. Inverter
4. Bypass switch
5. Bypass
6. Charger
7. Battery bank
8. Extended Battery Pack (optional)
9. UPS output
2.3 Product Category
USV Type Remark
Standard Unit 6 kVA Internal batteries 16-20 PCS (12V/PCS)
10 kVA Internal batteries 16-20 PCS (12V/PCS)
1 2
78
3
5
6
4 9

Page 10 06/2021
Installation and Operating Instructions
UPS Edition One 6kVA, 10kVA
3. Installation
3.1 Unpacking and inspection
■ Do not tip the UPS when removing it from the packaging. A general risk of tipping
always exists with units that have a high centre of gravity.
■ Check whether the UPS has been damaged during transport and do not switch on the
UPS if damage is detected. Please contact your supplier immediately.
■ Remove the packaging with the utmost care to avoid any damage to the unit. Check all
packaging materials to ensure that no parts are missing. Check the model number on
the back of the UPS to ensure that your delivery is correct.
The packaging is recyclable. After unpacking, please keep it for reuse or dispose
of it properly.
3.2 Installation Note
Observe the following when setting up / installing the UPS:
The system may only be installed and connected by trained electricians in
compliance with the relevant safety regulations!
■ All environmental and operating conditions requirements specied in the technical data
must be complied with in order to ensure the correct functioning of the UPS.
■ The unit may only be set up on its castors and on a rm, stable and horizontal surface.
■ Make sure that the vents on the front and rear of the UPS are not blocked. Ensure that
there is an appropriate ow channel. There should be a clearance of at least half a
metre on each side to maintain ventilation and prevent the temperature inside the unit
from becoming too high.
■ Keep the UPS away from high temperatures, water, ammable gases, corrosive gases,
dust, direct sunlight, and excessive humidity.
■ Observe a vertical installation position.
■ Load such as computers, linear loads and small inductive loads (in each case devices
with residual current circuit breakers) can be connected to the UPS.
■ If the UPS is unpacked in an environment with very low temperatures,
condensation may occur and water droplets may form. In this case, wait until
the UPS is completely dry inside and out before continuing installation and
commissioning, otherwise there is a risk of electric shock.
Dieses Handbuch passt für folgende Modelle
1
Inhaltsverzeichnis
Andere Atronix UPS Handbücher
Beliebte UPS Handbücher anderer Marken

Pylontech
Pylontech Victron & Pylontech US5000 Bedienungsanleitung

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Bedienungsanleitung

Mecer
Mecer ME-1000-WTU Bedienungsanleitung

Mustek
Mustek PowerMust 530(B) Plus Installations- und Betriebshandbuch

Emerson
Emerson Liebert NXL series Bedienungsanleitung

MAKELSAN
MAKELSAN BOXER SERIES Bedienungsanleitung