Technical data sheet AVK230A-3
Globe valve actuator with emergency
control function for 2-way and 3-way
globe valves
• Actuating force 2000 N
• Nominal voltage AC 230 V
• Control 3-point
• Nominal stroke 32 mm
• Design life SuperCaps: 15 years
Technical data
Electrical data Nominal voltage AC 230 V
Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 85...265 V
Power consumption in operation 3.5 W
Power consumption in rest position 1.5 W
Power consumption for wire sizing 6.5 VA
Connection supply / control Cable 1 m, 4 x 0.75 mm²
Parallel operation Yes (note the performance data)
Functional data Actuating force motor 2000 N
Setting emergency setting position (POP) Actuator spindle retracted / extended,
adjustable (POP rotary button)
Manual override with push-button
Nominal stroke 32 mm
Actuating time motor 150 s / 32 mm
Actuating time emergency control
function
35 s / 32 mm
Sound power level motor 60 dB(A)
Sound power level emergency control
position
60 dB(A)
Position indication Mechanically, 5...32 mm stroke
Safety Protection class IEC/EN II reinforced insulation
Protection class UL UL Class 2 Supply
Degree of protection IEC/EN IP54
Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2
EMC CE according to 2014/30/EU
Low voltage directive CE according to 2014/35/EU
Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14
Certification UL cULus according to UL 60730-1A, UL 60730-2-
14 and CAN/CSA E60730-1:02
Mode of operation Type 1.AA
Rated impulse voltage supply / control 4 kV
Control pollution degree 3
Ambient temperature 0...50°C
Non-operating temperature -40...80°C
Ambient humidity 95% r.h., non-condensing
Maintenance Maintenance-free
Weight Weight 4.4 kg
Terms Abbreviations POP = Power off position / emergency setting
position
CPO = Controlled power off / controlled
emergency control function
PF = Power fail delay time / bridging time
Safety notes
• This device has been designed for use in stationary heating, ventilation and air
conditioning systems and must not be used outside the specified field of application,
especially in aircraft or in any other airborne means of transport.
www.belimo.eu AVK230A-3 • en-gb • 2017-03-09 • subject to changes 1