Frequently asked questions during commissioning
1) AUTO is not shown → control is switched off
Possible reasons: Manual operation activated; control is switched off;
temperature is too high; current is less than 5 mA; voltage or THD of the
voltage are inadmissible
2) U ALARM is shown → voltage is out of tolerance
Possible reasons: Nominal voltage (SETUP/Un) or voltage transformer
factor is set incorrectly (SETUP/Pt)
3) I Lo ALARM is shown → measuring current is smaller than 5 mA
Possible reasons: Connection from the current transformer to the
controller is incorrect; the current transformer jumper was not removed;
current transformer ratio is too large; no current flow
4) EXPORT is shown → reverse current flow
Possible reasons: If there is no real reverse current flow, the voltage or
current measurement is incorrect (phase, polarity)
5) Wrong cos ϕis shown → incorrect connection
Possible reasons: Voltage or current measurement is incorrect (phase,
polarity)
6) Outputs are immediately switched off
Possible reasons: Stage sizes in the stage database are incorrect
7) Frequent switching operations
Possible reasons: Capacitor capacity have not been recognized yet