Bender MIP Series Bedienungsanleitung

Isolated Power Panels
For Healthcare Facilities
NAE209501-2 / 02.2019
T M
EN Manual

Bender Inc.
USA:
420 Eagleview Blvd.
Exton, PA 19341
Toll Free: 800-356-4266
Phone: 610-383-9200
Fax: 610-466-2071
E-mail: info@bender.org
Canada:
5810 Ambler Drive, Unit 1
Mississauga, ON L4W 4J5
Toll Free: 800-243-2438
Phone: 905-602-9990
Fax: 905-602-9960
E-mail: [email protected]
Web: www.benderinc.com
NAE209501-2, 02.2019
© Bender Inc.
All rights reserved.
Content subject to change.
T M

3IP Panels © 2018 Bender Inc. All Rights Reserved
Table of Contents
1. Introduction......................................................................................... 5
1.1 Isolated Power Panels...................................................................... 5
2. Safety Instructions.............................................................................. 6
2.1 General Safety Warning .................................................................. 6
2.2 Using This Manual............................................................................. 7
3. Model Types ........................................................................................ 8
3.1 MIP / MIE Series Isolated Power Panels ..................................... 8
3.2 MIC Series Isolated Power Panels with Circuit Control........ 8
3.3 MID Series Dual Output Voltage Isolated Power Panels..... 9
3.4 MIX Series Dual System Isolated Power Panels...................... 9
4. Components ...................................................................................... 10
4.1 Backbox Package............................................................................. 10
4.2 Front Trim Package......................................................................... 11
4.3 Isolation Transformer Kit .............................................................. 11
4.4 Interior Package............................................................................... 12
4.5 Circuit Breakers ................................................................................ 13
4.6 Line Isolation Monitor (LIM) ........................................................ 14
4.7 Fault Location (EDS) Kit................................................................. 14
4.8 Receptacle Kit ................................................................................... 15
4.9 Load Monitoring.............................................................................. 15
4.10 Accessories Package....................................................................... 15
5. Receiving, Handling, and Storage................................................. 16
5.1 Receiving............................................................................................ 16
5.2 Handling............................................................................................. 16
5.3 Storage................................................................................................ 16
6. Pre-Installation Requirements ....................................................... 17
6.1 General Requirements................................................................... 17
6.2 Support Requirements.................................................................. 18
6.3 Size Requirements .......................................................................... 18
7. Installation ......................................................................................... 19
7.1 Considerations ................................................................................. 19

4 IP Panels © 2018 Bender Inc. All Rights Reserved
7.1.1 Distance From Finished Floor..................................................... 19
7.1.2 Available Conduit Areas ............................................................... 19
7.2 Mount Backbox................................................................................ 20
7.3 Install Conduit.................................................................................. 22
7.4 Install Interior ................................................................................... 23
7.5 Remove Interior Deadfront ......................................................... 24
7.6 Install Breaker Kit............................................................................. 25
7.6.1 Components..................................................................................... 25
7.6.2 Install Breaker Bracket Assembly............................................... 26
7.6.3 Install Breaker Sub-Plate............................................................... 27
7.7 Install Transformer.......................................................................... 28
7.7.1 Vibration Pads and Mounting Hardware................................ 28
7.7.2 Mounting ........................................................................................... 29
7.7.3 General Instructions....................................................................... 30
7.7.4 Transformer and Incoming Power Wiring.............................. 30
7.7.5 Branch Circuit Wiring..................................................................... 31
7.7.6 Grounding ......................................................................................... 32
7.7.7 Accessories / Add-On Kit Wiring................................................ 32
7.8 Wiring Diagrams.............................................................................. 33
7.8.1 MIP, MIE, and MIX Series............................................................... 33
7.8.2 MIC Series........................................................................................... 34
7.8.3 MID Series .......................................................................................... 35
7.9 Reinstall Interior Deadfront......................................................... 36
7.10 Install Front Trim ............................................................................. 37
7.10.1 Install U-Type Retaining Nuts ..................................................... 37
7.10.2 Mount Front Trim............................................................................ 38
7.10.3 Install Line Isolation Monitor ...................................................... 39
7.10.4 Install Transformer Heat Shield (MIX Series Only)............... 40
7.10.5 Install Lower Front Trim (MIX Series Only)............................. 41
7.10.6 Install Restraining Lanyard (MIX series only)......................... 41
7.10.7 Connect Line Isolation Monitor Harness ................................ 42
7.10.8 Close Front Trim .............................................................................. 42

Introduction
5IP Panels © 2018 Bender Inc. All Rights Reserved
1. Introduction
1. 1 Isolated Power Panels
Bender isolated power panels provide isolated, ungrounded power to electri-
cal systems in operating rooms and other critical areas in healthcare facilities.
Isolated power systems allow for early detection of hazardous current while
keeping the system online. The system gives a visual indication of the level of
current in milliamperes (mA). When the threshold is reached, a visual and audi-
ble alarm is activated.
An isolation transformer serves a single operating room, except when supply-
ing power to equipment requiring 150 VAC or higher. A line isolation monitor
(LIM) indicates possible leakage current from all isolated conductors to
ground.
This manual provides instructions on installing and operating isolated power
panels. Refer to all relevant national and local codes and standards before pro-
ceeding with installation.

6 IP Panels © 2018 Bender Inc. All Rights Reserved
Safety Instructions
2. Safety Instructions
2. 1 General Safety Warning
Hazard of Electric Shock, Burn, or Explosion
Only qualified maintenance personnel should operate or service this equip-
ment. These instructions should not be viewed as sufficient for those who are
not otherwise qualified to operate or service this equipment. No responsibility
is assumed by BENDER for any consequences arising from use of this docu-
ment.
Turn OFF all sources of electric power before performing any inspections, tests,
or service on this equipment. Assume all circuits are live until they have been
properly de-energized, tested, grounded, and tagged. Failure to observe these
precautions will result in equipment damage, severe personal injury, or death.
Proper operation of this equipment depends on proper installation. Refer to
NFPA 70, NFPA 70E, CSA Z462, and other relevant standards and codes for
installation standards. Neglecting fundamental installation techniques will
result in equipment damage, severe personal injury, or death.
Do not make any modifications to the equipment. Failure to observe this pre-
caution will result in equipment damage or personal injury.
Use only manufacturer’s and manufacturer recommended accessories with
this equipment. Failure to do so may damage the equipment beyond repair.
!
DANGER

Safety Instructions
7IP Panels © 2018 Bender Inc. All Rights Reserved
2. 2 Using This Manual
Read these instructions carefully and become familiar with the equipment
before attempting to install, operate, or service it. Throughout this manual,
special messages may appear to warn of potential safety hazards or to call
attention to information which clarifies instructions or procedures. Observe all
safety messages that appear throughout this manual to avoid possible injury
or death. An explanation of these symbols is given below.
DANGER: Indicates a hazardous situation which, if
not avoided, will result in death or severe injury.
WARNING: Indicates a potentially hazardous situa-
tion which, if not avoided, may result in death or injury.
CAUTION: Indicates a potentially hazardous situation
which, if not avoided, may result in injury or equipment
damage.
NOTE: Provides additional information to clarify in-
structions for a product or procedure.
D
AN
G
ER
WARNIN
G
C
A
U
TI
O
N

8 IP Panels © 2018 Bender Inc. All Rights Reserved
Model Types
3. Model Types
3. 1 MIP / MIE Series Isolated Power Panels
Single-system, single-output-voltage isolated
power panel. MIP designation is used for pan-
els rated 10 kVA or below. MIE designation is
used for panels rated 15 kVA or above.
3. 2 MIC Series Isolated Power Panels with Circuit Control
Single-system, single-output-voltage (of
at least 150 V) isolated power panel. Pro-
vides programmable control of up to
twelve (12) individual circuits. Commonly
used with 208 VAC or 240 VAC portable
medical equipment, such as lasers. Circuit
control logic is configured at the factory.

Model Types
9IP Panels © 2018 Bender Inc. All Rights Reserved
3. 3 MID Series Dual Output Voltage Isolated Power Panels
Isolated power panel for a single-input-
voltage and dual-output-voltage system.
Commonly used to simultaneously supply
power to both normal line powered
equipment and equipment operating at a
voltage greater than 150 VAC (such as por-
table medical lasers).
3. 4 MIX Series Dual System Isolated Power Panels
Two MIP series interiors installed side-by-
side in a common enclosure. In figure
below, the transformer access front trim is
translucent for illustration purposes.
Wire is provided with the front trim
assembly for ground bus interconnection
and transformer terminal block connec-
tions to panel board lugs (or sub-feed
lugs, if applicable).

10 IP Panels © 2018 Bender Inc. All Rights Reserved
Components
4. Components
The following sections describe key components of isolated power panels.
These components are standard for the United States unless otherwise noted.
Ensure equipment conforms to all national and local codes and standards
prior to purchasing.
4. 1 Backbox Package
The backbox meet the requirements of NEMA
Type 1 according to UL 50. It is fabricated from a
minimum 14 GA galvanized steel and is
designed for flush (recessed) or surface mount-
ing. Flush mounting is standard. Surface
mounted backboxes must be requested during
the purchasing process.
Surface mounted backboxes are finished with a
coat of hospital grade ivory baked enamel or
equivalent.
All backboxes include an easy-lift-off hinge
assembly to ease front trim installation and sys-
tem maintenance.