10 en | Product Description Modular fire panel
07.2020 | 12.0 | F.01U.028.089 System Information Bosch Sicherheitssysteme GmbH
Module Description Function
BCM-0000-B Battery controller
module
Controlling the power supply to the panel and the
battery charge level
CZM 0004 A Conventional zone
module
Connecting conventional peripheral devices using
four monitored conventional lines
ENO 0000 B External notification
module
Connecting fire service equipment complying with
DIN 14675
FPE-5000-UGM Module interface to
UGM
Connection to UGM systems
IOP 0008 A Input-output module Individual displays or flexible connection of various
electrical devices, with 8 independent digital inputs
and 8 open collector outputs
IOS 0020 A Communication
module, 20mA
With S20 and RS232 interfaces
IOS 0232 A Communication
module, RS232
Connection of two devices using two independent
serial interfaces, e.g. Plena or a printer.
LSN 0300 A LSN bus module
300mA
Connection of an LSN loop with up to 254LSN
improved elements or 127LSN classic elements at a
maximum line current of 300mA
LSN 1500 A LSN bus module
1500mA
Connection of an LSN loop with up to 254LSN
improved elements at a maximum line current of
1500mA or 127LSN classic elements at a maximum
line current of 300mA
NZM 0002 A Notification
appliance zone
module
Allows connection of two conventional, monitored
notification appliance circuit lines
RMH 0002 A Relay module high-
voltage
Monitored connection of external elements with
feedback, with two changeover contact relays
suitable for switching mains voltage
RML 0008 A Relay module low-
voltage
For low voltage switching, with eight changeover
contact relays
– Fire brigade peripheral module
A fire brigade peripheral module is connected via FPE-5000-UGM or via IOS 0020 A
functional module. The fire brigade peripheral module FMF-ADP-TTY connects fire service
devices e.g. a Fire service operating panel or a Fire brigade information center to the fire
panel.
Notice!
Safety Systems Designer can be used to plan fire alarm systems that conform to the relevant
limits (e.g. in terms of cable length and power supply).