Bryant ASPCA1BBL040 Bedienungsanleitung

Liquid Cooled
Gas Engine
Generator Sets
UL 2200 Listed
2 Year Limited Parts
and Labor Warranty
3.9GN ENGINE
Power Matched
Naturally Aspirated
Ultra Quiet Mode
For Low Noise Exercise
- 60.0 dB(A) at 7 meters
Standby Power Rating
40 kW 60 Hz
• All input connections in one single area
• High coolant temperature shutdown
• Low oil pressure shutdown
• Low coolant level automatic shutdown
• Overspeed automatic shutdown
• Crank timer
• Exercise timer
• Oil drain extension
• Cool flow radiator
• Closed coolant recovery system
• UV/Ozone resistant hoses
• Watertight state of the art electrical connectors
• Mainline circuit breaker
• Radiator drain extension
• Battery charge alternator
• 2 Amp static battery charger
• Battery cables
• Battery rack
• Fan and belt guards
• Isochronous governor
STANDARD EQUIPMENT
• Innovative design and fully prototype tested
• UL2200 Listed
• Solid state frequency compensated
voltage regulator
• Dynamic and static battery charger
• Sound attenuated acoustically designed enclosure
• Ultra Quiet Mode for low noise level exercise
• Acoustically designed engine cooling system
• High flow low noise factory engineered exhaust system
• State of the art R100 digital control system
• Watertight electrical connectors
• Rodent proof construction
• High efficiency, low distortion designed alternator
• Vibration isolated from mounting base
• Matching transfer switches engineered and
tested to work as a system
• All components easily accessible for maintenance
• Electrostatically applied powder paint
FEATURES
Model Numbers:
Models are equipped with a
200 amp NEMA 3R Transfer Switch
with Service Disconnect
ASPCA1BBL040 - Aluminum Enclosure
ASPCS1BBL040 - Steel Enclosure

APPLICATION
& ENGINEERING DATA
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with
BS5514, ISO3046 and DIN6271). Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.
40 kW
GENERATOR SPECIFICATIONS
TYPE ..........................................................................................................Synchronous
ROTOR INSULATION ..........................................................................................Class H
STATOR INSULATION ........................................................................................Class H
TOTAL HARMONIC DISTORTION ........................................................................<3.5%
TELEPHONE INTERFERENCE FACTOR (TIF) ........................................................<50
ALTERNATOR OUTPUT LEADS 3 PHASE............................................................4 wire
BEARINGS ....................................................................................................Sealed Ball
COUPLING ..................................................................................................Flexible Disc
LOAD CAPACITY (STANDBY RATING) ................................................................40 kW
EXCITATION SYSTEM............................................................................................Direct
NOTE: Generator rating and performance in accordance with ISO8528-5,
BS5514, SAE J1349, ISO3046, and DIN6271 standards.
GENERATOR FEATURES
Revolving field heavy duty generator
Directly connected to the engine
Operating temperature rise 120 °C above a 40 °C ambient
Insulation is Class H rated at 150 °C rise
All models are fully prototyped tested
VOLTAGE REGULATOR
TYPE ................................................................................................................Electronic
SENSING ....................................................................................................Single Phase
REGULATION ..........................................................................................................± 1%
FEATURES................................................................................................V/F Adjustable
Adjustable Voltage and Gain
LED Indicators
ENGINE SPECIFICATIONS
MAKE ................................................................................................................ Generac
MODEL ..................................................................................................................V Type
CYLINDERS ..................................................................................................................6
DISPLACEMENT ................................................................................................3.9 Liter
BORE ........................................................................................................................3.91
STROKE ....................................................................................................................3.31
COMPRESSION RATIO ..........................................................................................9.1:1
INTAKE AIR SYSTEM........................................................................Naturally Aspirated
VALVE SEATS ......................................................................................Precision ground
LIFTER TYPE ............................................. Overhead Valve Push Rod Hydraulic Lifter
GOVERNOR SPECIFICATIONS
TYPE ................................................................................................................Electronic
FREQUENCY REGULATION ...................................................................... Isochronous
STEADY STATE REGULATION ............................................................................± .25%
ENGINE LUBRICATION SYSTEM
OIL PUMP ................................................................................................................Gear
OIL FILTER .............................................................................Full flow spin-on cartridge
CRANKCASE CAPACITY ..................................................................................4 Quarts
ENGINE COOLING SYSTEM
TYPE ............................................................................... Pressurized Closed Recovery
WATER PUMP ................................................................................................Belt driven
FAN SPEED..................................................................................................... 2060 rpm
FAN DIAMETER................................................................................................22 inches
FAN MODE............................................................................................................Pusher
FUEL SYSTEM
FUEL TYPE ..........................................................................Natural gas, propane vapor
CARBURETOR ..............................................................................................Down Draft
SECONDARY FUEL REGULATOR ..................................................................Standard
FUEL SHUT OFF SOLENOID ..........................................................................Standard
ELECTRICAL SYSTEM
BATTERY CHARGE ALTERNATOR ............................................................12V 30 Amp
STATIC BATTERY CHARGER ..............................................................................2 Amp
RECOMMENDED BATTERY .............................................................Group 24525CCA
SYSTEM VOLTAGE ............................................................................................12 Volts
OPERATING FUEL PRESSURE VAPOR SYSTEMS ..............Nat. Gas 5" to 14"H
2
O
............LP Vapor 5" to 14"H
2
O
CONTROL PANEL FEATURES
SEVEN LED INDICATOR LIGHTS ADDITIONAL FUNCTIONS
gnisnesytilitU•ydaermetsyS•
• Low fuel pressure • Delay on utility failure for engine start
refsnarterofebpu-mrawenignE•yrettabwoL•
ytilituotrefsnarterotyaleD•erusserpliowoL•
• High coolant temp/low coolant temp • Engine cooldown timer
testonresicrexE•deepsrevO•
• Overcrank
INTERNAL FUNCTIONS:
• 3 position switch (auto, off and manual)
• 2 wire start for any transfer switch
• Communicates with the Generac RTS transfer switch
• Built-in 7 day exerciser
• Selectable engine speed at exercise
• Governor controller is built into the master control board
• Temperature range -40 °C to 70 °C

STANDBY 40 kW
KW RATING - LP/NG 40/37
ENGINE SIZE 3.9 Liter V-6
eziSBCPMAWKzH06-WK/EGATLOVTUPTUOROTARENEG
5712.451GN/761PL73GN/04PLfp0.1,esahp-1,V042/021
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase 80
ENGINE COOLING
Air flow
(inlet air including alternator and combustion air)
ft35272.nim/
0.3.lagSUyticapactnalooC
000,151.rh/UTBtnaloocotnoitcejertaeH
Max. operating air temp. on radiator °C (°)051(06)F
Max. ambient temperature °C (°)041(05)F
COMBUSTION AIR REQUIREMENTS
105.4mfcz
H06rewopdetartawolF
SOUND EMISSIONS IN DBA
06sretem7tagnisicrexE
37sretem7tadaollluF
EXHAUST
274.3mfczH06tuptuodetartawolftsuahxE
Exhaust temp. at muffler outlet °83
9F
ENGINE PARAMETERS
0
081zH06MPRsuonorhcnysdetaR
LP 64.2 / NG 59zH06WKdetartaPH
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °52C
1.65% for every 10 °F above - °77F
Altitude Deration
381m-evobam001yreverof%1
006.tf-evoba.
tf000
1yreverof%3
OPERATING DATA
STANDBY 40 kW
FUEL – Natural Gas and LP Vapor Only
N.G.
Fuel consumption – 60 Hz
ft.3/hr. 550
221.5 (6.01)
LP ft. /hr.(gal./hr. - for reference only)
3
Exercise
Cycle 50%
Load 75%
Load
25%
Load 100%
Load
160 (4.34)
114.8 (3.12)
59.6 (1.62)
33.1 (.90)
82 148 285 397
TRANSFER SWITCH SPECIFICATIONS (If so equipped)
No. of Poles 2
002)spma(gnitaRtnerruC
052)CAV(gnitaRegatloV
Service Disconnect Breaker 200 Amp HACR Type
)dexif(rotinoMegatloVytilitU
%08pu-kciP
%06tuoporD
Return to Utility 1 minute
Exerciser 15 minutes weekly Standard
UL Listed Standard
dradnatS)detarroodtuO(R3AMEN-erusolcnE
4.7x50.31x5.32)”Dx”Wx”H(snoisnemiD
Weight 50 lbs.
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with
BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).

STANDBY 40 kW
INTERCONNECTIONS
INSTALLATION LAYOUT
40 240 1 O 175
/
0A9457
0C4449A-T
47822-T
47822-T
BB
E1
AA
N1
N1
N2
N2
23
23
194
194
194
194
23
23
N1
N1
N2
N2
22
22
33
33
11
11
44
44
UTILITY
METER
SOCKET
PANELBOARD
CONTROL
CONT ROL?
PA N E L
PANE L
AC?
GENERATOR
GE NERATOR
IF ATS IS USED AS SERVICE ENTRANCE
IF ATS IS USEDASSE RVICE ENT RANC E
DEVICE A BONDING JUMPER WILL NEED
DEVICE A BONDING JUMPER WILL NEED
TO BE INSTALLED SIZED TO MEET
TO BE INSTALLE D SIZED TO MEET
NATIONAL & LOCAL CODES.
NATIONAL&LOCAL CODES.
E2
E2
E1
E1
T1 T2
E2
E1
E2
T2T1
ALTERNATOR
FROM
STATOR
AT S
SERVICE
DISCONNECT
GROUND BAR
NEUTRAL BAR
NEW INSTALLATION
OR RETROFIT
NOTE: INSTALLATION TO BE DONE BY A
LICENSED ELECTRICIAN AND MUST
MEET ALL NATIONAL, STATE AND
LOCAL ELECTRICAL CODES.
BONDING
IN PANELBOARD
CONNECTION
DISCONNECT
STANDBY
(C2 & VR2)
(C1 & VR1)
UTILITY
GROUND BAR
9.05
All specifications are subject to change without notice.
UNIT WEIGHTS:
Steel 1658 lbs.
BRYANT, INC. • 7310 WEST MORRIS STREET • INDIANAPOLIS, IN 46231
WEBSITE: www.bryant.com
SS-ASPCL040-01
Aluminum 1541 lbs.
Dieses Handbuch passt für folgende Modelle
1
Inhaltsverzeichnis
Andere Bryant Tragbarer Generator Handbücher

Bryant
Bryant ASPAS1BBA007 Bedienungsanleitung

Bryant
Bryant ASPAX1BBA015 Montageanleitung

Bryant
Bryant ASPDA1BBL035 Bedienungsanleitung

Bryant
Bryant ASPAS1BBA007 Bedienungsanleitung

Bryant
Bryant ASPAS1BBA007 Bedienungsanleitung

Bryant
Bryant ASPAS1BBL015 Bedienungsanleitung

Bryant
Bryant ASPDA1BBL045 Bedienungsanleitung

Bryant
Bryant ASPAS1BBA007 Betriebsanleitung