C & K Systems SECURIT ST800L+ Bedienungsanleitung

INSTALLATION
MANUAL
SECURIT 800L+ CONTROL PANEL ST800L+

2
CONTENTS
WARNINGS 3
STANDARDS 3
WARRANTY STATEMENT 3
PRODUCT DESCRIPTION 3
AVAILABLE PARTS 3
INTENDED USE 3
SPECIFICATIONS 4
INSTALLATION 5
Mounting 5
Wiring the Control Panel 5
Mounting a Remote Keypad 7
Wiring a Remote Keypad 7
POWERING UP 7
Initial Power Up 7
PROGRAMMING 8
Exit Time 8
Entry Time 8
Sounder Duration 9
Night Set/Home Set Exit Time 9
Circuit Programming 10
Extended Programming Options 10
Home Set Zone Selection 10
Engineer Access Code 11
Engineer Event Log Review 11
Engineer Test Options 11
Factory Programming Defaults 12
GLOSSARY OF TERMS 12
SOUNDER CONNECTIONS 14
FAULT FINDING 15
GENERAL QUESTIONS & ANSWERS 15

3
WARNINGS
Prolonged short circuit of any supply can cause damage to the unit.
Take the necessary precautions in not allowing liquids to spill on or into the unit.
STANDARDS
This unit conforms to ECD 89/336/EEC & LVD 73/23/EEC. It has been tested and proven to
meet all current emission and immunity regulations as set out by the EEC. This unit complies
with BS4737 part 1 1988 which relates to security control equipment.
WARRANTY STATEMENT
C & K Systems offers a two and a half year warranty from the date of manufacture for this
product.
If for some reason the unit fails in the first six months, C & K will replace the unit free of charge.
If it fails in the remaining two years, return the unit to C & K systems, and we will test the unit. If
it is found customer damaged, a charge will incur. Otherwise the unit will be repaired and
returned free of charge.
PRODUCT DESCRIPTION
The Securit 800L+ is an 8-zone programmable microprocessor control panel using state of the
art technology and manufacturing techniques. The control panel has many advanced features
that can only be found in more expensive control panels. These features include two user
codes, Chime, Fire, and Keypad PA. Many options in the programming functions allow the
control panel to be versatile and user friendly. This panel is the ideal choice for residential and
light commercial installations.
AVAILABLE PARTS
The following selection of spares and extras are available:
•Remote Keypad - giving full control over the control panel.
•Spare PCB - for replacement in the event of failure.
•Keyswitch - giving simple set/unset operation.
You can obtain these items from your original place of purchase.
INTENDED USE
This control panel is designed to be used in residential and light commercial applications such
as homes, small shops, and so on.

4
SPECIFICATIONS
The following information explains the specifications of the panel.
SPECIFICATION FOR SOFTWARE REVISION NUMBER V2.0
The software revision number is located on the top of the main processor.
SPECIFICATION
Power Supply
Mains Supply Voltage 230 V AC Nominal
PSU output voltage 13.7 V Nominal
Maximum output current 1 A (total)
Aux. current 500 mA Max.
Battery Fuse 1 A (20 mm)
Panel Quiescent 40 mA
Keypads
Supply Voltage 13.7 V
Quiescent Current 20 mA
Active 45 mA
Maximum number allowed 6
General For internal use only
Normal operating temperature 0°C to 40°C
Humidity 10 to 90% R.H. non condensing
Dimensions 263 mm (W) 223 mm (H) 82 mm (D)
Control Panel Weight 2.7 kg Excluding Battery
Stand by Battery 7.0Ahr max. valnve regulated lead acid
Standby Time (load dependent) 24 hrs with 2.8Ahr nom.
60 hrs with 7.0Ahr nom. based on
(
panel+keypad+2*PIR=40+20+25+25mA
)
Cable run per zone/circuit 100m max with 50mA load
Cable run (alarm sounder) 50m max with 7/0.2 cable
100 max with 16/0.2 or 7/0.2 paralleled
Factory Defaults
User/customer Code 1 1234
User/customer Code 2 Disabled (0000)
Engineer Code 7890
Circuit 1 Entry Circuit. (Fixed)
Circuit 2 Alarm Circuit isolated in Night set.
Circuit 3 Alarm Circuit.
Circuit 4 Alarm Circuit.
Circuit 5 Alarm Circuit.
Circuit 6 Alarm Circuit.
Circuit 7 Alarm Circuit.
Circuit 8 P.A (Personal Attack)
Full Set Exit Time 30 Seconds
Night set Exit Time 15 Seconds
Entry time 30 Seconds
Sounder Ring Time 15 Minutes
Chimes Disabled
PROCESSOR
VERSION
POWER
SUPPLY
KEYPADS
GENERAL
FACTORY
DEFAULTS

5
INSTALLATION
Locate the control panel out of sight, such as in a hall, or under stairs or a
cupboard, where connection is easy and the detector zone and mains cables
can be concealed. Avoid areas subject to high temperature or humidity, such
as next to a boiler/heater, in an airing-cupboard, or conservatory.
When fitting the keypad(s), site them where they are not visible from
outside, but where there is adequate light and accessibility for the user.
MOUNTING
1Remove the lid screws and the lid.
2Remove the printed circuit board (PCB) or keypad packaging.
3Place the panel in the selected position and mark three fixing holes.
4Mount the panel securely using all three mounting hole positions.
5Attach tamper spring and mount PCB onto the support pillars.
Note: for Mounting Remote Keypad see page 7.
WIRING THE CONTROL PANEL
WARNING MAINS CONNECTION
The panel must be permanently connected to the mains supply in
accordance with current IEE wiring regulation. A 5 amp fused spur,
installed by a qualified electrician, is strongly recommended. Any fault
which could be mains related must be diagnosed and corrected by a
qualified electrician to ensure continued safe operation.
CAUTION: Under certain circumstances the transformer metalwork
can reach 70° C. This is normal and well within prescribed limits.
Battery Connection
Maximum battery size is 12V 7.0Ah.
This panel requires a standby battery to be fitted to provide power in the
event of mains failure. A valve regulated lead acid battery must be used.
Detector Circuits
Connections are provided for up to eight detector circuits of which normally
closed detection devices must be used. A common tamper loop is provided
for all detection devices marked as 24 HR Tamper. One or more devices
may be connected to each alarm circuit. These should be connected in a
series configuration. These circuit connections are located to the bottom
right of the PCB (see Diagram B).
PIR Latch Line (L+)
In the event of two or more detectors (motion sensors or glassbreak
detectors) being fitted to any single zone, latching detectors should be
used. The L+ connection provides this function. It is low (0 V) when unset
and high (12 V) when set. It should be connected to the appropriate SET or
LATCH terminal in your detector. See glossary for explanation.
INSTALLATION
PROCEDURES
MOUNTING
PROCEDURE
MAINS
POWER
WARNING
BATTERY
SPECIFICATION
DETECTOR
CIRCUITS
LATCH LINE
DESCRIPTION

6
Detector reset (L+ when programmed for ID)
Some detectors require the removal of power to reset (such as Viper Plus®
or Smoke detectors). You can program the L+ terminal to be used as an ID
output using option 7-4. The L+ terminal should then be used as the
negative supply for these devices. The positive supply should be taken from
the AUX +.
Internal Sounders, Speakers, Strobe and Keyswitch Wiring
DETECTOR
RESET
External Sounder & Strobe
Diagram A shows the connection for external sounder and strobe. Please
note that the sounder trigger is applied negative (Negative ring).
ST- Strobe switched negative trigger.
S - Sounder switched negative trigger
+ Sounder hold off/strobe positive supply.
- Sounder hold off supply & sounder tamper feed (negative).
-R Sounder tamper return (negative).
AUX DC - Detector power
The auxiliary power is provided from connections marked AUX. This is to
provide the 12 V supply for detectors such as movement or glassbreak
detectors. The auxiliary power output is rated at 500 mA max (12 VCD
nominal). (See Diagram B.)
INTERNAL
DEVICES
EXTERNAL
DEVICES
AUXILIARY
POWER
BASIC BOARD
LAYOUT
Diagram B
Diagram A
Keyswitch Connections
Open = ON
Closed = OFF
OFF
ON
A maximum of two 16 ohm speakers
may be fitted in parallel.

7
MOUNTING A REMOTE KEYPAD
1Choose the keypad location, and then mark holes for mounting.
2Make sure the cable is run through the backbox.
3Screw the backbox in the selected position, making sure the cable is
not twisted.
WIRING A REMOTE KEYPAD
Use 6 core cable for connection of all remote keypads.
Connect the cable into the terminals shown in Diagram C, making sure each
wire goes to a like-named terminal in the panel. C goes to C, D to D, + to +
and - to -. Wire the tamper wires in series with your existing tamper loop.
You do not need to identify individual keypads to the system. If you use
more than one remote keypad, either wire it back to the control panel or
daisy-chain it from another keypad. Wire all connections in parallel with the
exception of the tamper circuit which you MUST wire in series. (See the
Glossary for series and parallel examples.)
POWERING UP
INITIAL POWER UP
Note: Keep the lid off the main control panel in order to enter engineer
mode. Alternatively, you can enter 7890 # to enter engineer mode.
1Switch the mains supply ON. The internal sounder then starts.
This denotes a tamper alarm.
2Enter 1 2 3 4 followed by the #(hash) button. This silences the
sounder, and the TAMPER LED flashes.
This has now acknowledged and cancelled the alarm; however,
because either the panel or keypad lid is removed, your main tamper
loop is open. This is normal at this time.
3Connect the battery and walk test the control panel.
This ensures all zones are clear.
4Power Down and complete the wiring of the control panel.
NEVER wire the control panel live.
5Power back up, cancel the alarm, and enter engineering mode by
entering 7, 8, 9, 0.
The panel is now ready for programming.
MOUNTING
REMOTE
KEYPADS
WIRING
REMOTE
KEYPADS
KEYPAD
DIAGRAM
INITIAL
POWER UP
Diagram C

8
If no programming is required, close any lids that are open and press the #
key. This exits engineering mode. Then refer to the Users Manual for
customer options.
If at any time you want to exit engineering mode, confirm any options you
have selected with the *(STAR) key. Then close ALL tamper circuits and
wait for approximately 60 seconds after which the panel automatically exits
engineering mode. Pressing the # key manually exits engineering.
If at any time you want to re-enter engineering mode, enter the engineering
code and then press the #key. This forces the panel into engineering mode.
Note: If left unattended for approximately 60 seconds, it reverts to day
mode.
If you need to stay in engineering mode for longer unattended periods, once
in engineering mode, open a tamper circuit. The easiest way to do this is to
remove the lid of the panel or keypad.
PROGRAMMING
Once the panel is in engineering mode, the following options are available.
EXIT TIME 3-0 (Range 10-90 seconds)
Enter 3-0. The factory default is 30 seconds. You can program a new time by
entering one key from the following list.
Enter 110 Seconds. LED 1 on.
Enter 215 Seconds. LED 2 on.
Enter 330 Seconds. LED 3 on. (Default)
Enter 445 Seconds. LED 4 on.
Enter 560 Seconds. LED 5 on.
Enter 690 Seconds. LED 6 on.
After choosing the desired option, press *to confirm. The accept tone then
sounds.
ENTRY TIME 3-1 (Range 10-90 seconds)
Enter 3-1. The factory default is 30 seconds. To reprogram the entry time,
enter one key from the following list.
Enter 110 Seconds. LED 1 on.
Enter 215 Seconds. LED 2 on.
Enter 330 Seconds. LED 3 on. (Default)
Enter 445 Seconds. LED 4 on.
Enter 560 Seconds. LED 5 on.
Enter 690 Seconds. LED 6 on.
Press *to confirm the option. The accept tone then sounds.
NO
PROGRAMMING
NEEDED?
EXIT
ENGINEERING
MODE
RE-ENTER
ENGINEERING
MODE
STAY IN
ENGINEERING
MODE
TIMERS
EXIT TIME
ENTRY TIME

9
SOUNDER DURATION 3-2 (Range 3-20 minutes)
Enter 3-2. The factory default is 15 minutes. You can program a new time by
entering one key from the following table.
Enter 1 3 minutes. LED 1 on.
Enter 2 4 minutes. LED 2 on.
Enter 3 5 minutes. LED 3 on.
Enter 4 10 minutes. LED 4 on.
Enter 5 15 minutes. LED 5 on. (default)
Enter 6 20 minutes. LED 6 on.
Press *to confirm the selection. The accept tone then sounds.
NIGHT SET/HOME SET EXIT TIME 3-3 (Range 0-90 seconds)
Enter 3-3. The factory default is 15 seconds. You can program a new time
by entering one key from the following table.
Enter 0 0 Seconds. All LEDs off (Instant).
Enter 1 10 Seconds. LED 1 on.
Enter 2 15 Seconds. LED 2 on. (default)
Enter 3 30 Seconds. LED 3 on.
Enter 4 45 Seconds. LED 4 on.
Enter 5 60 Seconds. LED 5 on.
Enter 6 90 Seconds. LED 6 on.
Press *to confirm the selection. The accept tone then sounds.
Note: If extension speakers are fitted in Night and Home set, you can alter
the exit sounder volume by the control on the PCB marked VOLUME.
Option Option Results from choosing option no.
Code Description 0 1 2 3 4 5 6
3-0 Exit Time (secs) 10 15 30 45 60 90
3-1 Entry Time (secs) 10 15 30 45 60 90
3-2 Sounder Duration (mins) 3 4 5 10 15 20
3-3 Night/HomeExit(secs) 0 101530456090
After you enter the user code, the sounder starts at the lower controlled
volume. The volume increases after 5 seconds if Night or Home set are not
selected.
Examples
Change the full set Exit Time to 60 seconds
ENTER THIS 3-0 5 *
Description Choose Full Set Select 60 seconds Confirm selection
Change the Sounder Duration to 3 minutes
ENTER THIS 3-2 1 *
Description Choose Sounder Select 3 minutes Confirm selection
Change the Entry Time to 45 seconds
ENTER THIS 3-1 4 *
Description Choose Entry Select 45 seconds Confirm selection
SUMMARY
NIGHT/HOME
SET EXIT
TIMER
SOUNDER
DURATION

10
CIRCUIT PROGRAMMING 4 (Range 2-7)
You can program circuits 2-7 to suit your requirements. Circuit 1 is fixed as
a Final exit circuit. Circuit 8 has limited options.
ENTER PROGRAM
ZONE ENTER PROGRAM
ZONE
4 - 2 2 4 - 6 6
4 - 3 3 4 - 7 7
4 - 4 4 4 - 8 8
4 - 5 5
Select the circuit you want to alter. You can then program that circuit by
entering one key from the following table.
N/S = Night Set
Option no. Zones 2-7 Zone 8
1 Alarm Alarm
2 Alarm with walk through Fire
3 Alarm & Isolate in Night Set PA
4 Alarm, Walk through & Isolate in N/S Momentary
Keyswitch
5 Alarm, Walk through & N/S Entry
6Fire
7 Entry Route
8P.A
See the glossary for descriptions of zone types.
After you select the option, press *to confirm. The accept tone then
sounds.
To program zone 3 as an Entry Route enter - 4 3 7 *
To program zone 8 as a Keyswitch enter - 4 8 4 *
Momentary Keyswitch Turn and hold for 0.5 seconds = FULL SET
Turn and hold for 2.0 seconds = PART SET
EXTENDED PROGRAMMING OPTIONS 7 (Range 1-8)
The control panel offers the following additional options.
Enter 7 - 1 Disables sounder and strobe in Night Set.
Enter 7 - 2 Chime Enable (See User Manual for zone allocation).
Enter 7 - 3 Full set door sense setting.
Enter 7 - 4 Convert L+ to ID- output.
Enter 7 - 5 Allow Manual Isolation of Zone 1 (Entry/Exit) In Night Set.
Enter 7 - 6 Remote Keypad PA Enable (Operated by * and #).
Enter 7 - 7 L+ signals first to alarm.
Enter 7 - 8 Inhibit strobe in Night and Home set and test (for speech
dialer connection).
Press *to confirm. The accept tone then sounds.
HOME SET ZONE SELECTION 8 (Range 1-8 N/A if Fire or PA)
The Home Set feature enables parts of the premises to be alarm protected
while other parts are occupied and in use. This feature is similar to Night
Set except that an Exit/Entry route is not required as part of the Setting or
Unsetting procedure.
In programming mode press 8to select Home Set zone selection mode.
HOME SET
ZONE
SELECTION
EXTENDED
PROGRAMMING
ZONE
SELECTIONS
CIRCUIT
PROGRAMMING
Andere Handbücher für SECURIT ST800L+
2
Inhaltsverzeichnis
Andere C & K Systems Bedienfeld Handbücher

C & K Systems
C & K Systems S802 Bedienungsanleitung

C & K Systems
C & K Systems Securit 700L Bedienungsanleitung

C & K Systems
C & K Systems Securit 802 Betriebsanleitung

C & K Systems
C & K Systems SYS3316RF Bedienungsanleitung

C & K Systems
C & K Systems System 2316E Bedienungsanleitung

C & K Systems
C & K Systems Securit 800L Handbuch

C & K Systems
C & K Systems active 5 Bedienungsanleitung

C & K Systems
C & K Systems LED Keypad Bedienungsanleitung

C & K Systems
C & K Systems SECURIT ST800L+ Bedienungsanleitung