Datcon DT1600 U Series Bedienungsanleitung

DT1600 Ux xx xx
AC Voltage Transmitters
Operating Instructions

DT1600 Ux xx xx
2 20180621-V0
Contents
1. About this document.....................................................4
1.1. Function ................................................................................... 4
1.2. Target group............................................................................. 4
1.3. Symbolism used....................................................................... 4
2. For your safety...............................................................5
2.1. Authorized personnel ............................................................... 5
2.2. Appropriate use........................................................................ 5
2.3. Warning about misuse ............................................................. 5
2.4. General safety instructions....................................................... 5
2.5. CE conformity........................................................................... 5
2.6. Environmental instructions ....................................................... 5
3. Product description.......................................................6
3.1. Delivery configuration............................................................... 6
3.2. Type designation...................................................................... 6
3.3. Principle of operation ............................................................... 6
3.4. Adjustment ............................................................................... 7
3.5. Indicator ................................................................................... 7
3.6. Storage and transport .............................................................. 8
4. Mounting.........................................................................9
4.1. General instructions ................................................................. 9
4.2. Main dimensions of the instrument .......................................... 9
4.3. Mounting procedure ............................................................... 10
5. Connecting ...................................................................11
5.1. Preparing the connection ....................................................... 11
5.2. Connecting to the power network........................................... 12
5.3. Connecting the signal processing unit and the power supply 13
5.4. Put the instrument under supply voltage................................ 13

DT1600 Ux xx xx
20180621-V0 3
6. Fault rectification.........................................................14
6.1. Fault finding............................................................................ 14
6.2. Repairing................................................................................ 14
7. Dismounting.................................................................15
7.1. Dismounting procedure .......................................................... 15
7.2. Disposal ................................................................................. 15
8. Calculation for application..........................................16
8.1. Calculations............................................................................ 16
9. Appendix.......................................................................17
9.1. Technical specification ........................................................... 17
9.2. Application example ............................................................... 19

DT1600 Ux xx xx
4 20180621-V0
1. About this document
1.1. Function
This operating instructions manual has all the information
you need for quick set-up and safe operation of
DT1600 Ux xx xx.
Please read this manual before you start setup.
1.2. Target group
This operating instructions manual is directed to trained
personnel. The contents of this manual should be made
available to these personnel and put into practice by them
1.3. Symbolism used
Information, tip, note
This symbol indicates helpful additional information.
Caution, warning, danger
This symbol informs you of a dangerous situation that could
occur. Ignoring this cautionary note can impair the person
and/or the instrument.
•
List
The dot set in front indicates a list with no implied
sequence.
→Action
This arrow indicates a single action.
1
Sequence
Numbers set in front indicate successive steps in a
procedure.

DT1600 Ux xx xx
20180621-V0 5
2. For your safety
2.1. Authorized personnel
All operations described in this operating instructions
manual must be carried out only by trained and authorized
specialist personnel. For safety and warranty reasons, any
internal work on the instruments must be carried out only by
DATCON personnel.
2.2. Appropriate use
The DT1600 Ux xx xx an AC voltage transmitter.
Detailed information on the application range is available in
Chapter 3. Product description.
2.3. Warning about misuse
Inappropriate or incorrect use of the instrument can give rise
to application-specific hazards, or damage to system
components through incorrect mounting or adjustment.
2.4. General safety instructions
The DT1600 Ux xx xx is a high-tech instrument requiring the
strict observance of standard regulations and guidelines.
The user must take note of the safety instructions in this
operating instructions manual, the country-specific
installation standards as well as all prevailing safety
regulations and accident prevention rules.
2.5. CE conformity
The DT1600 Ux xx xx is in conformity with the provisions of
the following standard:
EN 61326:2004 (EMC)
EN 61010-1:2001 (safety)
2.6. Environmental instructions
Protection of the environment is one of our most important
duties.
Please take note of the instructions written in the following
chapters:
•Chapter 3.6. Storage and transport
•Chapter 7.2. Disposal

DT1600 Ux xx xx
6 20180621-V0
3. Product description
3.1. Delivery configuration
Delivered items The scope of delivery encompasses:
•DT1600 Ux xx xx
•documentation:
this operating instructions manual
certification
warranty
3.2. Type designation
3.3. Principle of operation
Area of application The DT1600 Ux xx xx AC Voltage Transmitters provide an
output signal proportionally with the average value (F) or
with the TRMS value (R) of the input AC voltage.
The version marked with R is recommended to use for
measure of non-sinusoidal signals.
The output can be current (0-20 mA, 4-20 mA), active (A) or
passive (P) or voltage (0-10 V).
In all types the input, the output and power supply are
galvanic isolated from each other.
Operating principle
The AC voltage connected to the input is transformed and
isolated by the input transformer. The secondary voltage of
the transformer is lead to the AC/DC converter. The DC
voltage controls the output current or voltage according to
the input AC current.

DT1600 Ux xx xx
20180621-V0 7
Power supply There are two power supply versions:
18-40 VDC / 14-29 VAC (DT1600 Ux xx xx) or
140-250 VAC / 180-250 VDC (DT1600 Ux xx xx PS).
The overcurrent protection in installation is 4 A (B).
3.4. Adjustment
The DT1600 Ux xx xx doesn’t need any adjustment.
After connected to the power supply it is ready to work.
3.5. Indicator
The following figure shows the indicator on the
DT1600 Ux xx xx front panel.
1. The power green indicator shows that the instrument is
in “power on” state.

DT1600 Ux xx xx
8 20180621-V0
3.6. Storage and transport
This instrument should be stored and transport in places
whose climatic conditions are in accordance with chapter
9.1 Technical specifications, as described under the title:
Environmental conditions.
The packaging of DT1600 Ux xx xx consist of environment-
friendly, recyclable cardboard is used to protect the
instrument against the impacts of normal stresses occurring
during transportation. The corrugated cardboard box is
made from environment-friendly, recyclable paper. The
inner protective material is nylon, which should be disposed
of via specialized recycling companies.

DT1600 Ux xx xx
20180621-V0 9
4. Mounting
4.1. General instructions
The instrument should be installed in a cabinet with
sufficient IP protection, where the operating conditions are
in accordance with chapter 9.1 Technical specifications,
as described under the title: Operating conditions.
Mounting position
The DT1600 Ux xx xx is built in a plastic housing, for
mounting on TS-35 rail.
The instrument should be mounted in vertical position
(horizontal rail position).
Horizontal mounting may cause overheating and damage of
the instrument.
4.2. Main dimensions of the instrument

DT1600 Ux xx xx
10 20180621-V0
4.3. Mounting procedure
The following figure shows the mounting procedures (fixing
on the rail):
Mounting on the rail
The mounting doesn’t need any tools.
1. Tilt the instrument according to the figure; put the
instrument’s mounting hole onto the upper edge of the rail
(figure step 1.).
2. Push the instrument’s bottom onto the bottom edge of the
rail (figure step 2.), you will hear the fixing assembly
closing.
3. Check the hold of the fixing by moving the instrument
firmly.
Inhaltsverzeichnis
Andere Datcon Sender Handbücher

Datcon
Datcon DT1012 Bedienungsanleitung

Datcon
Datcon DT1310 Series Bedienungsanleitung

Datcon
Datcon DT1010 Series Bedienungsanleitung

Datcon
Datcon DT7200 Series Bedienungsanleitung

Datcon
Datcon DT7001 Bedienungsanleitung

Datcon
Datcon DT1012 IP Bedienungsanleitung

Datcon
Datcon PQRM5100 11 U I Series Bedienungsanleitung
Beliebte Sender Handbücher anderer Marken

Dejero
Dejero EnGo 3x Bedienungsanleitung

Rosemount
Rosemount 4600 Bedienungsanleitung

Speaka Professional
Speaka Professional 2342740 Bedienungsanleitung

trubomat
trubomat GAB 1000 Bedienungsanleitung

Teledyne Analytical Instruments
Teledyne Analytical Instruments LXT-380 Bedienungsanleitung

Rondish
Rondish UT-11 Bedienungsanleitung