- 4 -
CR# Attrib. Register name Explanation
#8 O R/W CH1 sampling range
Set sampling range in CH1 ~ CH4:
Range = K1 ~ K100
Default = K10
#9 O R/W CH2 sampling range
#10 O R/W CH3 sampling range
#11 O R/W CH4 sampling range
#12 X R CH1 average input value
Average value of input signals at CH1 ~ CH4
#13 X R CH2 average input value
#14 X R CH3 average input value
#15 X R CH4 average input value
#20 X R CH1 present input value
Present value of input signals at CH1 ~ CH4
#21 X R CH2 present input value
#22 X R CH3 present input value
#23 X R CH4 present input value
#28 O R/W Adjusted Offset value of CH1 Set the adjusted Offset value of CH1 ~ CH4.
Default = K0
Definition of Offset in DVP04AD-E2:
The corresponding voltage (current) input
value when the digital output value = 0.
#29 O R/W Adjusted Offset value of CH2
#30 O R/W Adjusted Offset value of CH3
#31 O R/W Adjusted Offset value of CH4
#34 O R/W Adjusted Gain value of CH1 Set the adjusted Gain value in CH1 ~ CH4.
Default = K16,000
Definition of Gain in DVP04AD-E2:
The corresponding voltage (current) input
value when the digital output value = 16,000.
#35 O R/W Adjusted Gain value of CH2
#36 O R/W Adjusted Gain value of CH3
#37 O R/W Adjusted Gain value of CH4
Adjusted Offset Value, Adjusted Gain Value:
Note1: When using Mode 6 for input, the channel do NOT provide setups for adjusted Offset or Gain
value.
Note2: When input mode changes, the adjusted Offset or Gain value automatically returns to defaults.
#40 O R/W
Function: Set value changing
prohibited
Prohibit set value changing in CH1 ~ CH4.
Default= H’0000.
#41 X R/W
Function: Save all the set
values Save all the set values, Default =H’0000
#43 X R Error status Register for storing all error status. Refer to
table of error status for more information.
#100 O R/W Function: Enable/Disable limit
detection
Upper and lower bound detection, b0~b3
corresponds to Ch1~Ch4 (0: Enable/1:
Disable). Default= H’0000.
#101 X R/W Upper and lower bound status
Display the upper and lower bound status
(0: Not exceed /1: Exceeds upper or lower
bound value), b0~b3 corresponds to
Ch1~Ch4 for lower bound detection result;
b8~b11 corresponds to CH1~CH4 for upper
bound detection result.
#102 O R/W Set value of CH1 upper bound
Set value of CH1~CH4 upper bound. Default
= K32000.
#103 O R/W Set value of CH2 upper bound
#104 O R/W Set value of CH3 upper bound
#105 O R/W Set value of CH4 upper bound
#108 O R/W Set value of CH1 lower bound
Set value of CH1~CH4 lower bound. Default
= K-32000.
#109 O R/W Set value of CH2 lower bound
#110 O R/W Set value of CH3 lower bound