ULM-53-dat-5.6
LEVEL METER SETTING
The measuring range is setup by means of two buttons "DOWN"
and "UP".The "DOWN" button is used to enter to the setting mode
(setting the 4mA or 0V limit) and to decrease the output current
or voltage. The "UP" button as an opposite function (setting the
20mA or 10V limit and increasing the output current or voltage).
Values are confirmed by simultaneous pressing of both buttons for
about 1sec. The setting process is indicated by yellow "MENU"
LED indicator.
For detailed information please read at the instructions manual.
RANGE OF APPLICATION
For continuous non-contact level measurement of liquids (water solutions, sewerage water, etc.), mash and paste materials (sedi-
ments, sticks, resins etc.) in closed or open vessels, sumps, reservoirs and open channels.
In case the level of bulk-solid materials is measured, the measurement range is reduced. We recommend to consult the use with
the manufacturer.
button "DOWN"
button "UP"
LEDindicator"MENU"
LEDindicator"STATE"
connector
ultrasonic transmitter
Full viewofultrasonic level meter
LED indicators colour function
"STATE" green
Slow flashing (1–2 sec. depends on the measuring interval) – reception of reflected signal (echo) from the measured
level. Correct function.
Fastblinks– the measured value is in "dead zone" of the level meter, or the ultrasonic transm. is polluted.
Dark– the measured value is in "dead zone" of the level meter, or the ultrasonic transm. is polluted. Incorrect
installation or malfunction.
"MENU" yellow Slow blinks– signalization setting limit 4 mA
Fastblinks– signalization setting limit 20 mA
STATUS AND FAILURE SIGNALIZATION
ELECTRICAL CONNECTION
The ultrasonic level meter is designed to be con-
nected to supply unit or to controller through two or
three-wire cable with outer diameter 6 ÷ 8 mm (rec-
ommended cross section of cores 0,5 to 0,75 mm2)
by means of connector which is included in delivery.
Connection diagram and inner view of the connector
as shown in picture. Always disconnect the power
supply before connecting the level meter electrically!
Note: In case of strong electromagnetic interferences
(EMI), parallel cable ducting with power lines, or when
cable length exceeds 30m we recommended to use
shielded cable.
WARNING:
With regard to possible occurrence of electrostatic
charge on non-conductive parts of the level meter, me-
tallic flanges of the ULM-53Xi-10-I and ULM-53Xi-20-I
(for explosive areas) level meters must be grounded
with ground terminal!
The inside of the
connectorsocket
Connection scheme
bk – black bn – brown
bu – blue NC – not connected
coments:
0V
(bu)
+U
(bn)
0V
(bu)
+U
(bn)
Uout
(bk)