5
Eaton Industries (Austria) GmbH, Eugenia 1, 3943 Schrems, Austria MA- XS24_Standard.docx/10.2018e/150501507/IL019188ZU
© 2018 by Eaton Industries (Austria) GmbH, www.eaton.eu/documentation All Rights Reserved / rinted in Austria
THE “ XS24E…
STANDARD“ SE-
RIES
This manual describes the following models:
XS24S-e2/F/ORT-IT 2A fix with input terminals XS24S02A001
XS24S-e4/F/ORT-IT 4A fix with input terminals XS24S04A001
XS24S-e6/F/ORT-IT 6A fix with input terminals XS24S06A001
XS24S-e8/F/ORT-IT 8A fix with input terminals XS24S08A001
XS24S-e10/F/ORT-IT 10A fix with input terminals XS24S10A001
XS24S-e13/F/ORT-IT 13A fix with input terminals XS24S13A001
XS24S-e16/F/ORT-IT 16A fix with input terminals XS24S16A001
XS24S-e2/F/ORT 2A fix without input terminals XS24S02A002
XS24S-e4/F/ORT 4A fix without input terminals XS24S04A002
XS24S-e6/F/ORT 6A fix without input terminals XS24S06A002
XS24S-e8/F/ORT 8A fix without input terminals XS24S08A002
XS24S-e10/F/ORT 10A fix without input terminals XS24S10A002
XS24S-e13/F/ORT 13A fix without input terminals XS24S13A002
XS24S-e16/F/ORT 16A fix without input terminals XS24S16A002
IN UT
TERMINALS
Articles marked “IT” (= “input terminal”) can be used individually (> see section on “stand-alone op-
eration”) or in combination with other articles. Should you wish to combine several components
(including for mixed operation), please consult the XS24 system manual.
STAND-ALONE
O ERATION
An individual XS24S-…/IT element can be used on its own to protect a channel. This requires the
selection of a model with input terminals (“IT”), as models without input terminals are supplied via
the busbar only.
TEM ERATURE
RISE
To ensure thermal protection, modules with high amperage should not be placed directly next to one
another, wherever possible. lease also refer to the technical data of the individual components.
De-rating: If three or more 16A modules are placed directly next to each other (in the specified tem-
perature range), these must be de-rated to 13A. For this type of application, we therefore recom-
mend using 13A modules instead. If 16A modules are to be used, please leave 1H (18 mm) between
each of the modules for cooling purposes.