FASTRON. DTC1 Series Bedienungsanleitung

DTC1Series
IntelligentTemperature/HumidityPID
Controllerwith60StepProgramControl
UserManualV1.0
ThankyouforpurchasingFastronDTCseriesPID
Temperature/HumidityController.Thismanualexplains
howtoinstallandoperateyournewPIDController.
Beforeoperation,pleasereadthismanualfirsttofully
understandtheoperationofthisproduct.Thiscontroller
shouldbeinstalledbyaqualifiedElectricalEngineer,
TechnicianorElectrician.Forspecifictechnicalsupport
pleasecontactyouragentorrepresentative.
SafetyWarning
1a)AvoidtouchingtheACpowerterminalsafterthecontrollerispowered
on.
1b)Alwaysensurethesupplypowerisofffirstbeforeconnectingany
wires.
1c)Donotoperatethisinstrumentinplacesfullofexplosiveand
combustiblegases.
2.IncorrectConnectionofthePowerSupplycancausepermanent
damage.
3.Themaximumtorqueoftheterminalsshouldnotexceed8KN.
4.Pleasedonotuseinthefollowingcircumstances:
●wherethetemperaturechangesdramatically
●Placeswherehumidityistoohigh(~85%)andwaterisproduced
●Wherevibrationorimpactishigh
●Wherecorrosivegasesordustarepresent
●splashofwater,oilandchemicals
6.AllWiringshouldbekeptawayfromhighvoltage,highcurrentpower
ImprovedFeatures
(1)Slopevalueoffsetcompensation.
(2)2in(input)2out(output):1to2isolatedtransmission,2to1isolatedtransmission
(Optional)
(3)Multiplealarmmodes
(4)TransmissionofPV,SVandMV:forward,reverseanddifferencevaluein8ways.
(5)Outputsoftstartfunction.
(6)Dehumidificationfunction.
(7)ServoMotorControl(Optional)
(8)Optional60Segment,MultiSequence,ProgramControl
ProgrammingMenu
WiringConfiguration


1.SensorTypeSetting
A.PressSET+◄keytoenterLEVEL3
B.OnceyoureachINPPress◄andtheSV
displaywillblink
C.Press▼or▲selecttheinputtype(refertothe
signalinputselectiontable).PressSETtoconfirm
E.Atthesametime,pressSET+◄toreturnto
LEVEL1
2.AL1/AL2Alarmmodesetting
A.PressSETfor5secondstoenterLEVEL2
B.PressSETseveraltimestoaccessAD1,thenpressthe
◄keyandthedisplaywillstarttoflash.
C.Press▼or▲selectthealarmtype(seealarmselection
table)
D.PressSETtoconfirm
E.PressSETtoreturntoLEVEL1
Step(3):SetalarmvalueAL1/AL2
SeeAL1andAL2inalarmmodeTable
A.PressSETkeyseveraltimestoaccessAL1
selection,andthenpress◄toenablethe
selection.
B.Press▲or▼toSETthevalue,andthenpress
the◄keytomovetothenextdigitanddoBoth
AL1andAL2canchoosealarmmodefrom0to10,
whichcanthesamesetting.
C.Aftersetting,pressSETkeytoconfirm.Pattern
EndoutputcanbeselectedasAlarmmode11.
Thereisalsoaconstanttemperatureandtiming
alarmmode19
D.PressSETtoreturntoLEVEL1settingandtest
thealarmfunctionorpatternendoutput.
Step(4):ProgramControlSettingand
Operation(Optional)
A.AtLEVEL1masterPV/SVdisplaypressSETkeyseveral
timestoreach“C01”inordertostarttosettheprogram.
Press◄and▲or▼andSETtosetthetemperatureforthe
fristsegment.
B.PressSETtoselectT01.Press◄and▲or▼andSET
tosetthetimeforthefristsegment.
C.PressSETseveraltimesuntilyoureachOU01.Press◄
and▲or▼andSETtosettheMVhighlimitforthefirst
segment.Repeatforeachsteptocreatethepattern.
D.EnsureallremainingCX,TXandOUXvaluesaresetto
0
Youmaywanttosetupmultiplepatterns.
E.NotethatwhenpresettingofsegmentsIscomplete,CX,TXandOUXofthenextsegmentmustallbeput"0"
astheisolationsegmentandmarkbetweengroups.
E.60isthemaximumofsegments.
G.CALsettingisthefirststepnumberofthestartupoperationgroup.Forexample,ifthesecondgroupsbegins
atC08,thenCALshouldbesetto08.
F.IftheprogramControlneedstostartfrom0DegC,setSTAparameterto1;ifPVisneeded,puttheSTAitem
into2or3.ProgramcontrolENDmodehastwooptionsseeoperationflowchart(endofLEVEL3)
G.Duringoperationtheprogramsegmentorstepnumberyoucanchangethecurrentsegment/stepnumberto
runforwardorbackwardwithintherangeofthecurrentgroup;SelectStitemtoseethecurrentsteptimeofthe
currentrunningsegmentinordertoknowwhereexactlyintheprogramyouarecurretlyoperating.
H.Tostart/endtheprogram,pleasepressSETkeyand▲keyatthesametime.
I.Pressthe▲buttontopause/continuetheprogram.
J.Toensurethecontrollerreachesthedesiredtemperatureregardlessofthetimeperiod,youcanselectWait
Value(WB)intherangeof(0.110DegC),WB=0meansthecontrollerwilladvanceeveniftheset
temperatureisnotreached.SeeendlfLEVEL3menu
K.Thecontrollerwillstarteitherbyshortingterminals6and7,orbypressingthe
·Pressthe▲andSETkeyonce(34seconds)tostarttheprogramcontrol;ifpressthe▲andSETkeyonce
again(34seconds)programcontrolwillend;·duringtheprogramcontroloperation,press▲keyonce(12
seconds)topausetheprogramcontrol.Ifpressthe▲keyagainprogramcontrolwillcontinuetorun.

Step(5):Autotuning(AT)Function
A.Onceinstalledinthefield,carryoutselftuningtoallowthecontrollertodeterminetheoptimumAT
parameters.
B.ATcalculationwillchoosetheoptimumPIDParametersbasedonthecontrollersautotuningalgorithm.
C.Themaximumvalueoftheprocesscurveshouldbeabout80%oftherangeofinstrumentdetection.
D.Beforetheprogramisnotstarted(fixedvaluecontrolSTA=0),itisbettertocarryoutATaroundthemaximum
valueoftheprocesscurve(SV=0.3).E.InLEVEL1process,pressSETkeyseveraltimestoreachAToption,
Step(6)ManuallymodifyingPIDparameters.(OptionalFineTuning)
UsethebelowduietochangetheP,I,Dvaluesforfinetuningofmanualtuning(LEVEL2)
Example:ToSetfourgroupsasshownintheabovefigure
Inthefirstgroup,therearefivestages:thefirststage,thesteptemperatureisC1,andthesteptimeisT1.Inthe
secondsegment,theendtemperatureisC2andtheendtimeisT2.Inthethirdstage,thesteptemperatureisC3
andthesteptimeisT3.Inthefourthsection,thesteptemperatureisC4andthesteptimeisT4.Inparagraph5,
thesteptemperatureisC5andthesteptimeisT5.
Thesecondsetofsevensections:thefirstsection,theendtemperatureisC7,theendtimeisT7.Inthesecond
segment,theendtemperatureisC8andtheendtimeisT8.Inthethirdsection,theendtemperatureisC9and
theendtimeisT9.Inthefourthsegment,theendtemperatureisC10andtheendtimeisT10.Inparagraph5,
thesteptemperatureisC11andthesteptimeisT11.Inthesixthparagraph,thesteptemperatureisC12and
thesteptimeisT12.Intheseventhsection,theendtemperatureisC13andtheendtimeisT13.Thethirdsetof
threesections:thefirstsection,theendtemperatureisC15,theendtimeisT15.Inthesecondsegment,theend
temperatureisC16andtheendtimeisT16.Inthethirdsection,theendtemperatureisC17andtheendtimeis
T17.
Thefourthsetoffivesegments:thefirstsegment,theendtemperatureisC19,theendtimeisT19.Inthesecond
segment,theendtemperatureisC20andtheendtimeisT20.Inthethirdsection,thesteptemperatureisC21

RateofChange/SlopeTemperatureLimit
Whenyoursystemneedsasoftstart(SVpresetslopeheating),pleaseoperateinthefollowingorder:
SETSVvalue→atLEVEL1,pressSETkeytofindRAPtoSETslopetemperaturevalue,and→thenpressSET
keytofindRTMtoSETslopetimeinminutes(forexample,SETslopeto10 /min,RAPto10.0,RTMto001.0)
→aftersetting,SVvaluewillbeSETimmediatelyfromthecurrentPVvalueto10 /min,untilreachingtheSET
SVvalue.
SlopeheatingprocessPROTheoutputpercentageofnormaltemperaturelightsflashingcontrolprocessis
automaticallycontrolledbyPID
DehumidificationFunction
Forsystemswhichrequiredehumidificationfunction.
InLevel1Menu,pressSETbuttonseveraltimestoreach
SRTtopresetdehumidificationPVvalue,(Mostcommon
rangeis1040DegC)pressSETkeyagainandreach
LMOtopresetdehumidificationworkoutputpercentage,
generally2.0to5.0%.ForexampleforSRT=40,andLMO
=2%,theControllerwilloutputat2%whenthesystem
temperaturedropsbelow40DegC.Thisfeaturecanhelp
avoidheaterburnout.
Theabovecurveshowstwopoints,theDipintheheating
curveiscausedbythedehumidificationsetting.The
secondpointisthenormaloutputofthePIDController.
SoftStartFunction
OutputSoftStart
ToenablesimplesoftstartfeaturesettheSVasfollows;
SetSVvalue>Inlevel3pressSETkeytoreachDLY,SETtheoutputsoftstartvalueinseconds(I.e.ifDLYis
setto10,thenthesoftstarttimewillbe10seconds).Exitthemenubypressingsetuntilyoureturntothemain
screen.Nowthesoftstartfunctionisactivatedwhenthecontrolissettobeginheating.

JumperSettingsforTC JumperSettingsforRTD
Note:futureversionV1.2willhavefullmultirangeinputtypewithoutJumperselection
Dieses Handbuch passt für folgende Modelle
1
Inhaltsverzeichnis
Andere FASTRON. Temperaturregler Handbücher
Beliebte Temperaturregler Handbücher anderer Marken

Swegon
Swegon LUNAd MB Bedienungsanleitung

Lucky Reptile
Lucky Reptile Thermo Control II Bedienungsanleitung

SENSORMETRIX
SENSORMETRIX Argon 100 Bedienungsanleitung

Fuji Electric
Fuji Electric PXE4 Bedienungsanleitung

Yuyao gongyi
Yuyao gongyi XMT-808 series Bedienungsanleitung

Selec
Selec TC544C Bedienungsanleitung