FASTRON. DTC1 Series Bedienungsanleitung

DTC1Series
IntelligentTemperature/HumidityPID
Controllerwith60StepProgramControl
UserManualV1.0
ThankyouforpurchasingFastronDTCseriesPID
Temperature/HumidityController.Thismanualexplains
howtoinstallandoperateyournewPIDController.
Beforeoperation,pleasereadthismanualfirsttofully
understandtheoperationofthisproduct.Thiscontroller
shouldbeinstalledbyaqualifiedElectricalEngineer,
TechnicianorElectrician.Forspecifictechnicalsupport
pleasecontactyouragentorrepresentative.
SafetyWarning
1a)AvoidtouchingtheACpowerterminalsafterthecontrollerispowered
on.
1b)Alwaysensurethesupplypowerisofffirstbeforeconnectingany
wires.
1c)Donotoperatethisinstrumentinplacesfullofexplosiveand
combustiblegases.
2.IncorrectConnectionofthePowerSupplycancausepermanent
damage.
3.Themaximumtorqueoftheterminalsshouldnotexceed8KN.
4.Pleasedonotuseinthefollowingcircumstances:
●wherethetemperaturechangesdramatically
●Placeswherehumidityistoohigh(~85%)andwaterisproduced
●Wherevibrationorimpactishigh
●Wherecorrosivegasesordustarepresent
●splashofwater,oilandchemicals
6.AllWiringshouldbekeptawayfromhighvoltage,highcurrentpower
ImprovedFeatures
(1)Slopevalueoffsetcompensation.
(2)2in(input)2out(output):1to2isolatedtransmission,2to1isolatedtransmission
(Optional)
(3)Multiplealarmmodes
(4)TransmissionofPV,SVandMV:forward,reverseanddifferencevaluein8ways.
(5)Outputsoftstartfunction.
(6)Dehumidificationfunction.
(7)ServoMotorControl(Optional)
(8)Optional60Segment,MultiSequence,ProgramControl
ProgrammingMenu
WiringConfiguration
Forapplicationnotesandexamplespleasevisit
https://fastron.com.au/blogs/pidtemperaturecontrollers


1.SensorTypeSetting
A.PressSET+◄keytoenterLEVEL3
B.OnceyoureachINPPress◄andtheSV
displaywillblink
C.Press▼or▲selecttheinputtype(refertothe
signalinputselectiontable).PressSETtoconfirm
E.Atthesametime,pressSET+◄toreturnto
LEVEL1
2.AL1/AL2Alarmmodesetting
A.PressSETfor5secondstoenterLEVEL2
B.PressSETseveraltimestoaccessAD1,thenpressthe
◄keyandthedisplaywillstarttoflash.
C.Press▼or▲selectthealarmtype(seealarmselection
table)
D.PressSETtoconfirm
E.PressSETtoreturntoLEVEL1
Step(3):SetalarmvalueAL1/AL2
SeeAL1andAL2inalarmmodeTable
A.PressSETkeyseveraltimestoaccessAL1
selection,andthenpress◄toenablethe
selection.
B.Press▲or▼toSETthevalue,andthenpress
the◄keytomovetothenextdigitanddoBoth
AL1andAL2canchoosealarmmodefrom0to10,
whichcanthesamesetting.
C.Aftersetting,pressSETkeytoconfirm.Pattern
EndoutputcanbeselectedasAlarmmode11.
Thereisalsoaconstanttemperatureandtiming
alarmmode19
D.PressSETtoreturntoLEVEL1settingandtest
thealarmfunctionorpatternendoutput.
Step(5):Autotuning(AT)Function
A.Onceinstalledinthefield,carryoutselftuningtoallow
thecontrollertodeterminetheoptimumATparameters.
B.ATcalculationwillchoosetheoptimumPIDParameters
basedonthecontrollersautotuningalgorithm.
C.Themaximumvalueoftheprocesscurveshouldbe
about80%oftherangeofinstrumentdetection.
D.Beforetheprogramisnotstarted(fixedvaluecontrol
STA=0),itisbettertocarryoutATaroundthemaximum
valueoftheprocesscurve(SV=0.3).E.InLEVEL1
process,pressSETkeyseveraltimestoreachAToption,
thenpressandkeytoput"1"tostartATcalculation.
F.ThismachineisusedasafixedvaluecontrolwhenSTA
="0",andasaprogramcontrollerwhenSTA=1,2,3.
G.Oncethecontrollerispoweredon,aslongasSTAdoes
notequal0(theprogramcontrolmachinedoesnotstartthe
programoperation,thecontrollerhasnooutput.
RateofChange/SlopeTemperatureLimit
Whenyoursystemneedsasoftstart(SVpresetslopeheating),pleaseoperateinthefollowingorder:
SETSVvalue→atLEVEL1,pressSETkeytofindRAPtoSETslopetemperaturevalue,and→thenpressSET
keytofindRTMtoSETslopetimeinminutes(forexample,SETslopeto10/min,RAPto10.0,RTMto001.0)
→aftersetting,SVvaluewillbeSETimmediatelyfromthecurrentPVvalueto10/min,untilreachingtheSET
SVvalue.
SlopeheatingprocessPROTheoutputpercentageofnormaltemperaturelightsflashingcontrolprocessis
automaticallycontrolledbyPID
SoftStartFunction
OutputSoftStart
ToenablesimplesoftstartfeaturesettheSVasfollows;
SetSVvalue>Inlevel3pressSETkeytoreachDLY,SETtheoutputsoftstartvalueinseconds(I.e.ifDLYis
setto10,thenthesoftstarttimewillbe10seconds).Exitthemenubypressingsetuntilyoureturntothemain
screen.Nowthesoftstartfunctionisactivatedwhenthecontrolissettobeginheating.

1.Scopeofselection:FastronElectronicsDTCSeriesfittedwithRS485
ModbusRTU“C5”Option
2.Workrealization:dataexchangebetweeninstrumentandhostcomputer
(instrumentcanonlybeusedasslavetoreceiveinterrogationandreply)
3.Serialtransmissionmode:RTU
4.Transmissioninterface:RS485
5.Communicationmedium:shieldedtwistedpair
6.Communicationstacknumber:1~255.Theupperlimitofthenumberof
connectingmetersisrelatedtotheloadcapacityofthehost,typicallyover15
or31metersrequiresignalIsolator/amplifier.
7.Functioncodeimplementation:readholdregister(03),writesingleregister
(06),writemultipleregisters(10)
8.Datalength:
8a)Whenwritingdatatothecontroller,amaximumof16consecutive
instructions(32bytes)canbewrittenatonetime.
8b)Whenreadingthemenudatainsidethemachine,thenonprogrammed
menucanread16consecutivemenusatatime(theunrealizedaddress
outsidetheparameteraddresstableis0),whiletheprogrammedmenucan
onlyread16consecutivemenusatatime
9.Numericalformat:signed16bitbinarycomplement;Thedatareadis10.0
timeslarger;Beforewritingthedata,enlargethedata10.0timesbefore
sendingit;Noticethetransition.
RS485MODBUSRTUcommunication
protocol
Baudrate:4800,9600,19200,38400,76800,
153600bps
Startposition:1
Databit:8
Checkbit:E(even),N(none)Stopbits:1,2
Framecheckmethod:(CRC16)
Messageformat:(N=2)
Troubleshooting
CommunicationApplicationNotes
1.ReadAMandAM1(coldcontrolmanual)menus,0represents
manualstate,1representsautomaticstate.
2.RAPistheprogramcontrolmenu,read,return0X0000
representstheprogramcontrolclose,return0X0001represents
theprogramcontrolstart:write0X0000toclosetheprogram
control,write0X0001tostarttheprogramcontrol,write0X0002
tostoptheprogramcontrol,write0X0002toendthe
suspension,continuetoruntheprogramcontrol.
3.Beforewritingtheprogramcontrolledmenu,pleasewrite
0x0000toRAPtoclosetheprogramcontrolledmenu.
4.BeforewritingMV/MV1threshold,pleasefirstwrite0x0000to
AM/AM1tomakethesystemswitchtomanualcontrol.
5.Whenthemultiplieris10,thereturneddataismagnified10
times.
6.PV1andPV2arereadonlyparameters.
7.Thereshouldbea150ms+timeintervalbetweenwrite
instructions,nomatterthesameaddressornotnot.instrument
failure,andthetimeintervalshouldbenolessthan150
milliseconds.
DTC1C5CommunicationsManual
Dieses Handbuch passt für folgende Modelle
1
Inhaltsverzeichnis
Andere FASTRON. Temperaturregler Handbücher
Beliebte Temperaturregler Handbücher anderer Marken

Swegon
Swegon LUNAd MB Bedienungsanleitung

Lucky Reptile
Lucky Reptile Thermo Control II Bedienungsanleitung

SENSORMETRIX
SENSORMETRIX Argon 100 Bedienungsanleitung

Fuji Electric
Fuji Electric PXE4 Bedienungsanleitung

Yuyao gongyi
Yuyao gongyi XMT-808 series Bedienungsanleitung

Selec
Selec TC544C Bedienungsanleitung













