GFA TS 971 Series Referenzhandbuch

Brief instructions
Door control
TS 971
Automatic control panel with radio
Version: 51171638
-aus-
Version: e / 01.2015
0000000 0000 51171638 XXXXX

2
GfA-ELEKTROMATEN
Australia Pty Ltd
P.O. Box 267
Roseville 2069 NSW
Telephone: 02 9882 2782
Facsimile: 02 9882 2783
Email: info@gfa-elektromaten.net
Web: www.gfa-elektromaten.net

3
Contents
1General safety information ............................................................................................ 5
2Technical data .............................................................................................................. 6
3Electrical installation ..................................................................................................... 7
Mains supply ..................................................................................................................... 7
Connection cable connection overview ............................................................................. 8
Limit switch configuration, screwable version up to year of construction in 1997 .............. 9
Limit switch configuration, single limit switches ................................................................. 9
Overview of control ......................................................................................................... 10
4Starting up the control ................................................................................................. 11
DES: Rapid adjustment of final limit positions ................................................................. 11
NES: Rapid adjustment of final limit positions ................................................................. 12
5Electrical installation – control accessories .................................................................. 13
External supply X1 .......................................................................................................... 13
Emergency stop X3 ......................................................................................................... 13
Automatic closing, On/Off X4 .......................................................................................... 13
External Control device X5 .............................................................................................. 13
Photo cell X6 ................................................................................................................... 13
Light curtain X6 ............................................................................................................... 14
Radio receiver X7............................................................................................................ 14
Pull switch X7 .................................................................................................................. 14
Intermediate stop X8 ....................................................................................................... 14
Red/green traffic lights X20 / X21 ................................................................................... 14
Magnetic brake X20 / X21 ............................................................................................... 14
Connection of spiral cable ............................................................................................... 15
WSD door-module (Wireless Safety Device) .................................................................. 16
Teach-in of WSD door-module ........................................................................................ 17
Completing the electrical installation ............................................................................... 17
6Control programming .................................................................................................. 18
7Table menu items ....................................................................................................... 19
Door operating modes ..................................................................................................... 19
Door positions ................................................................................................................. 20
Door functions, ................................................................................................................ 21
Safety functions .............................................................................................................. 25

4
DI / FI settings ................................................................................................................. 26
Extended door functions .................................................................................................. 27
Teach-in of handheld transmitter ..................................................................................... 28
Maintenance cycle counter .............................................................................................. 29
Readout of Data memory ................................................................................................ 30
Deleting of all settings ..................................................................................................... 3 0
Reading out WSD door-module data............................................................................... 31
8Safety devices ............................................................................................................ 31
X2: Input, safety edge ..................................................................................................... 31
EMERGENCY operation ................................................................................................. 32
9Status display ............................................................................................................. 33
Faults .............................................................................................................................. 33
10Explanation of symbols ............................................................................................... 38
11Declaration of Incorporation/Declaration of Conformity ................................................ 40
Symbols
Warning - Risk of injury or danger to life!
Warning - Danger to life from electric shock!
Note - Important information!
▶ Prompt - Required action!
Illustrations show example products. Differences from the delivered product are possible.

5
1General safety information
Specified normal use
The door control is intended for a power-operated door with a drive unit (NES/DES GfA limit
switch system).
The safe operation is only guaranteed with specified normal use. The drive unit is to be
protected from rain, moisture and aggressive ambient conditions. No liability for damage
caused by other applications or non-observance of the information in the manual.
Modifications are only permitted with the agreement of the manufacturer. Otherwise the
Manufacturer’s Declaration shall be rendered null and void.
Safety information
Installation and commissioning are to be performed by skilled personnel only.
Only trained electrical craftsmen are permitted to work on electrical equipment. They must
assess the tasks assigned to them, recognise potential danger zones and be able to take
appropriate safety measures.
Installation work is only to be carried out with the supply off.
Observe the applicable regulations and standards.
Coverings and protective devices
Only operate with corresponding coverings and protective devices.
Ensure that gaskets are fitted correctly and that cable glands are correctly tightened.
Spare parts
Only use original spare parts.

6
2Technical data
Series TS 971
Dimensions W x H x D 155 x 386 x 90 mm
Installation Vertical, free of vibration
Operating frequency 50 / 60 Hz
Supply voltage (+/- 10%)
1 N~220-230 V, PE
3 N~220-400 V, PE
3~220-400 V, PE
Output power for drive unit, maximum 3 kW
Protection per phase, on-site 10-16 A
External supply voltage:
(internal electronic protection)
24 V DC
0.35 A
External supply voltage: X1/L, X1/N
(protection via F1 micro-fuse)
1 N~230 V
1.6 A time-lag
Control inputs 24 V DC
Type 10 mA
Relay contacts 2 potential-free
changeover contacts
Loading of relay contacts,
ohmic/inductive
230 V AC, 1 A
24 V DC, 0,4 A
Control power consumption 18 W
Temperature range Operation: -10..+50
Storage: +0..+50 °C
Air humidity up to 93 %
non-condensing
Protection class of housing IP54
Compatible GfA limit switch NES (mechanical limit switch)
DES (digital limit switch)
Integrated radio receiver
WSD (Wireless Safety Device)
Handheld transmitter
2.4
434
GHz
MHz

7
3Electrical installation
Warning - Danger to life due to electrical current!
Disconnect the cables (mains OFF) and check that the supply is off
Observe the applicable regulations and standards
Ensure proper electrical connection
Use suitable tools
On-site backup fuse and disconnector unit!
Only use current sensitive earth leakage circuit breakers type B for FI-drive units
Connection to the indoor installation via an all-pole disconnector unit, with current
≥ 10 A as per EN 12453 (e.g. CEE plug connector, main switch)
Observe the installation instructions of the drive unit!
Mains supply
3~, N, PE
220 – 400 V
50 - 60 Hz
3~, PE
220 – 400 V
50 - 60 Hz
1~, N, PE, sym.
220 - 230 V
50 - 60 Hz
1~, N, PE, asym.
220 - 230 V
50 - 60 Hz
L1L2L3 NPE
L1 L2L3 PE
NPE
SI 25.15 WS, SI 45.7 WS
NPE
SI 25.15 WS, SI 45.7 WS

8
Connection cable connection overview
Ⓐ DES → Ⓑ X12 DES ⒸMOT → Ⓓ X13
Pin Core Pin Description: Pin Core Term. Description:
① 5/wh ① +24 V safety circuit ①3W Phase W
② 6/bn ② Channel B (RS485) ②2V Phase V
③ 7/gn ③ Ground ③1U Phase U
④ 8/ye ④ Channel A (RS485) ④4N Neutral conductor (N)
⑤ 9/gy ⑤ Safety circuit ⑤PE PE
⑥ 10/pk ⑥ 8 V DC supply voltage
Ⓐ NES → Ⓔ X12 NES
Pin Core Term. Description:
① 5/wh 11 Limit switch common +24 V, wire link to: 7, 9, 5, 14
② 6/bn 12 S5 Auxiliary limit switch
③ 7/gn 6 S3 Open limit switch
④ 8/ye 15 S6
A
uxiliary limit switch
⑤ 9/gy 8 S4 CLOSE limit switch
⑥ 10/pk 4 Safety circuit

9
Limit switch configuration, screwable version up to year of construction in 1997
56710 93214(N)
S6 S5 S3 S1 S2 S4
S10 F1
G1
Y1
1
3
2
4
5
X12
W1
M1
F1 Thermal contact X12 Limit switch board
G1 Rectifier S1 Emergency OPEN limit switch
M1 Motor S2 Emergency CLOSE limit switch
S10 Emergency manual operation S3 OPEN limit switch
W1 Connection cable S4 CLOSE limit switch
Y1 Spring-loaded brake S5
A
uxiliary limit switch
S6
A
uxiliary limit switch
Limit switch configuration, single limit switches
5 671093214PE
M1 S10 F1S4S3 S5 S6
W1
A1
A
1 Terminal box S3 OPEN limit switch
F1 Thermal contact S4 CLOSE limit switch
M1 Motor S5
A
uxiliary limit switch
S10 Emergency manual operation S6
A
uxiliary limit switch
W1 Connection cable

10
Overview of control
2.1
2.3
2.5
2.2
2.4
20.1
1.8
1.9
ANT
GN D
20.2
20.3
21.1
21.2
21.3
F1 = 1,6A t
V1
MOT
DES/
NES S11
S12
S13
X20X21T
X3
X2
X4 X5 XX6 X7 X8
F1
UBS S
X1
971
DES/
NES DES or NES limit switch socket X24 V mains supply, external devices
X1 Mains supply
F1 Micro-fuse 1.6 A time-lag X2 Safety edge and
door safety switch
MOT Motor socket
S Selector switch X3 Emergency STOP control device
S11 OPEN push-button X4
A
utomatic closing On/Off
S12 STOP push-button X5 Control device, external three push-button
S13 CLOSE push-button X6 Through / reflective photo cell
T Internal aerial, 434 MHz X7 Pull switch, external radio receiver
UBS Universal command sensor socket X8 Intermediate stop On/Off
V1 Display X20 Potential-free relay contact 1
X21 Potential-free relay contact 2