Gossen MetraWatt SMARTCONTROL ECS Bedienungsanleitung

Operating Instructions
SMARTCONTROL | ECS
Energy Management System
Input/Output Module for 24 Channels
3-349-552-03
2/5.19

2 GMC-I Messtechnik
GmbH
Table of Contents
1. Input/Output Module for 24 Channels ............................................................ 3
1.1 Jumper Designations and Functions................................................................ 4
2. Input/Output Module for 24 Channels and SmartControl Manager ................. 7
2.1 Command Type IO24Analog............................................................................ 8
2.2 Command Type IO24Meter............................................................................ 10
2.3 Command Type IO24Relay ............................................................................ 10
2.4 Command Type IO24Status........................................................................... 11
2.5 Backup Battery ............................................................................................. 13
3. Characteristic Values .................................................................................... 14
4. Repair and Replacement Parts Service, Calibration Center and Rental
Instrument Service ....................................................................................... 16
5Product Support Industry.............................................................................. 16

GMC-I Messtechnik GmbH 3
1. Input/Output Module for 24 Channels
The I/O module for 24 channels expands the SmartControl with 24 additional digital inputs
(DI0 through DI23).
Furthermore, ports DI18 through DI21 can be configured as switching outputs K1 through
K4 by means of jumpers. Ports DI22 and DI23 can be configured as analog outputs with
jumpers as well.
The module is mounted with the help of the included accessories, and is connected to the
expansion port at the SmartControl PCB (at the bottom in the picture) with the included
cable.
Please observe all safety precautions for assembly and the connection of ports
included in the SmartControl user’s manual.

4 GMC-I Messtechnik
GmbH
1.1 Jumper Designations and Functions
The terminals for ports DI0 through DI23 are designated a and b. The terminals for
the digital inputs, for example DI0, are designated a0 and b0.
Jumpers for the active or passive digital input mode: If the ports are used as digital
inputs, either sensors with their own power supply or, e.g., floating contacts/reed
contacts can be connected. For a more detailed description of this function please
refer to the “Digital Inputs” section in the SmartControl user’s manual. However, the
digital input tariff and synchronization functions described in the user’s manual are
not available in this case.
Digital in / option:
Jumpers for selecting options for the last six digital inputs (DI18 through DI23).
Ports DI18 through DI21 can be configured as switching outputs K1 through K4. For example,
SV27/SV29 plugged onto 2-3,respectively, configures DI18 as floating NO contact K1.
For a more detailed description of the relays please refer to the “Analog Inputs, Relays”
section in the SmartControl user’s manual.
The jumpers required for selecting switching outputs K1 through K4 are:
SV29/SV27, SV33/SV31, SV38/SV36, SV42/SV40.

GMC-I Messtechnik GmbH 5
The following are then available at the terminals, for example for DI18 as switching output K1:
DI18a and DI18b, the switching function is configured as a normally open contact (NO).
Ports DI22 through DI23 can be configured as analog outputs.
The jumpers required for selecting analog outputs ANA0 through ANA1 (command address:
0-1) are:
SV37/SV39, SV41/SV43.
Function selection for the analog outputs:
Required jumpers for ANA0 -> SV30 SV28 SV26
Required jumpers for ANA1 -> SV35 SV34 SV32
Example ANA0 as 0-10V output -> Jumper plugged onto SV28, SV26.
The following are then available at the terminals for DI22:
DI22a analog plus (+)
DI22b analog ground (-)
Example ANA0 as 0-20mA output -> no jumper plugged onto SV30, SV28, SV26
The following are then available at the terminals for DI22:
DI22a analog plus (+)
DI22b analog ground (-)
The following combinations are possible for both analog outputs:
ANA0
ANA1
Use
0-10V
0-10V
Common ground
0-20mA
-
Common ground
-
0-20mA
Common ground
0-20mA
0-20mA
Electrical isolation required
0-10V
0-20mA
Electrical isolation required
0-20mA
0-10V
Electrical isolation required
Within this context, electrical isolation means, for example, that the ground terminals at
ANA0 and ANA1 are neither connected with each other nor with any external ground
terminals.

6 GMC-I Messtechnik
GmbH
Further components:
Jumper SV44 (always plugged in) disconnects the reset cable from the main PCB.
Briefly unplugging the jumper results in a reset.
Jumper SV45 (always open) is used to reinitialize the BBSRAM.
LEDs 1 through 24 (red): indicates pulses at inputs DI0 through DI23.
LED 30 (green) DIAG, blinks approx. once per second for normal operation.
LEDs 25 through 28 (green): status display for the switching outputs
LED on = contact closed
LED off = contact open
SV1 is the interface to the main PCB at the SmartControl (expansion port).
The jumpers for active and passive inputs correspond to those of the SmartControl (refer to
the “Digital Inputs” section in the SmartControl user’s manual).
The connection terminals for DI0 through DI23 are numbered 49 through 96.

GMC-I Messtechnik GmbH 7
2. Input/Output Module for 24 Channels
and SmartControl Manager
The input/output module for 24 channels is configured with SmartControl Manager software.
The “IO24Meter” spreadsheet can be accessed under calibration in the SmartControl Manager:
Factor, unit of measure and meter reading can be entered. These entries are written to the
SmartControl after clicking the “Accept” button, and all entries can be returned to their
default values by clicking the “Reset” button.
Click the current reading for setting the meter readings. Change the reading and
acknowledge with enter. Save the changes to the SmartControl with the button „...“ which
then appears.
The units of measure entered here are used automatically when the meters are read.
Units of measure and meter factors can only be changed here.
One of the following IO24 commands can now be entered to a new program in the
SmartControl Manager under menu item “programming”:
The symbols are located in the middle at the top of the main window.
Just click the symbols and drag them to an empty command field. “D/A” means analog,
“123” means meter, the third symbol represents a relay, “I/O” means status.

8 GMC-I Messtechnik
GmbH
2.1 Command Type IO24Analog
The address determines the output channel (ANA0=0 or ANA1=1).
The command variable determines the analog output value. Any desired reference can be
used.
Only analog values within the output range are displayed. Larger and smaller values are
shortened accordingly.
Example: the command variable has the value 15, whereas the value 10 is shown as analog
value.
The value range of the input value can be further adjusted to the output range by adjusting
the slope, etc. of the command variable.

GMC-I Messtechnik GmbH 9
By clicking „Test“ a window opens. Upon entering a test value and clicking the “Start”
button, the analog output is set to the corresponding value. If no test value is entered, the
command variable is used.

10 GMC-I Messtechnik
GmbH
2.2 Command Type IO24Meter
The name can be changed in the bottom field in the meter command, and selection can be
made as to whether or not writing to flash memory will take place.
Furthermore, it can be specified for each input whether or not this value will be stored to
flash memory.
Attention: If changes are made here (clear or add meter, or use another input), another
ID is assigned to the data as of this point in time which must be given special consideration
during read-out because the configuration of the data has been changed!
Further settings, for example unit of measure, can be entered under “Calibration” ->
“IO24Meter”.
2.3 Command Type IO24Relay
Please refer to the “SmartControl Manager, Command Type Relay” section in the user’s
manual for the SmartControl with regard to this command type.
The functions are the same, only the addresses for DI18 through DI21 in the address field
of this command type are 0-3.
Andere Handbücher für SMARTCONTROL ECS
3
Inhaltsverzeichnis
Beliebte E/A-System Handbücher anderer Marken

WAGO
WAGO 750-344 Bedienungsanleitung

Teknim
Teknim TWM-1887 Bedienungsanleitung

Intelligent Appliance
Intelligent Appliance IA-2662-E Bedienungsanleitung

BERGHOF
BERGHOF ECC DIO 16/16 Bedienungsanleitung

Advantech
Advantech PCM-27J3AU Installations- und Betriebshandbuch

Festo
Festo CP-E08-M12-CL Bedienungsanleitung