Upon receiving unit, check for any damage
and report it immediately to the shipper. Also
check to see that all accessory items are
accounted for.
Move fan to desired location and fasten
securely through mounting holes in base.
Shims may be necessary depending upon
roofing material thickness. The diagram
below shows dimensions for Model CUBE.
Access to the motor compartment is
accomplished by removing the screws
designated “R” in Fig. 1. The cover can then
be removed and placed on a flat surface in
an area protected from strong winds.
The motor’s amperage and voltage rating
must be checked for compatibility to the
supply voltage prior to final electrical
connection. For NFPA - restaurant CUBE
applications, the electrical supply must enter
the motor compartment through the breather
tube. For other non-flammable applications
the electrical supply can be routed through
the conduit chase between the curb cap and
the bottom of the motor compartment.
Consult local code authorities for your
specific requirements.
A drain trough is provided on all CUBE fans
for single-point drainage of water and
residue. Some means for collection of this
residue must be provided, either a container
directly under the trough or use of an
adapter and pipe to carry the residue to a
remote collection point. An optional grease
trap with water separator baffles is available
from your Greenheck representative.
Installation, Operating and Maintenance Manual
READ AND SAVE THESE INSTRUCTIONS
Model CUBE Belt Drive
Upblast Centrifugal
Roof Exhaust Fan
PN 457693
MODEL A B *C D Shaft
Bearings
Damper
Size
Roof
Opening
Approx.
Unit
Weight
CUBE-098, 101, 101HP, 121, 131 19 247/8281/4173/83/412x12 141/2x 141/266
CUBE-141, 141HP
CUBE-161, 161HP, 161XP 22 287/8293/4193/83/416x16 181/2x 181/287
CUBE-180 3/4
CUBE-180HP 1 126
CUBE-200 30 353/8285/821 3/4
18x18 201/2x 201/2
CUBE-200HP 1 142
CUBE-220, 220HP
CUBE-240, 240HP, 240XP 34 423/4337/8251/21 24x24 261/2x 261/2175
CUBE-300, 300HP, 300XP 40 50 36 29 1 30x30 321/2x 321/2313
CUBE-360, 360HP, 360XP 46 585/8391/8293/836x36 381/2x 381/2440
CUBE-420 52 653/16 443/4351/4
11/442x42 441/2x 441/2578
CUBE-480 58 743/16 481/836 11/248x48 501/2x 501/2675
Dimension “A” is the inside dimension of the curb cap. The roof curb should be 11/2in. less than
the curb cap to allow for roofing and flashing.
All dimensions are in inches. *May vary depending on motor size.
Dimensional Data
min. of 18 in.