Greyline DLT 2.0 Bedienungsanleitung

www.greyline.com
USER'S GUIDE
Installation & Operation
Instructions
Differential Level Transmitter
Model DLT 2.0
Manual Series A.1.3

Note: This page has been left blank intentionally.

Page 3
DLT 2.0 Differential Level Transmitter
INDEX
CONNECTIONS: ...............................................................................................4
KEYPAD SYSTEM............................................................................................6
CALIBRATION MENU.....................................................................................7
ICONS.................................................................................................................8
MAIN DISPLAY................................................................................................9
MESSAGE ICON...............................................................................................9
STATUS .............................................................................................................9
PASSWORD.....................................................................................................10
UNITS/MODE..................................................................................................11
CALIBRATION................................................................................................12
CHANNEL SETUP ..........................................................................................16
RELAY PARAMETERS..................................................................................17
SPECIAL FUNCTIONS...................................................................................18
SENSOR MOUNTING/LOCATION...............................................................20
APPLICATIONS HOTLINE............................................................................26
PRODUCT RETURN PROCEDURE..............................................................27
APPENDIX A - OPTIONS...............................................................................29
DATA LOGGING (Optional)...........................................................................35
CONVERSION GUIDE ...................................................................................37
SPECIFICATIONS...........................................................................................38
IMPORTANT NOTE: This instrument is manufactured and calibrated to meet product specifications.
Please read this manual carefully before installation and operation. Any unauthorized repairs or
modifications may result in a suspension of the warranty.
Available in Adobe Acrobat pdf format

Page 4
DLT 2.0 Differential Level Transmitter
CONNECTIONS:
POWER INPUT: 100 to 240 VAC 50/60Hz . No adjustments are necessary for voltages within this
range.
Optional DC: 9-32 VDC, 9 Watts. Connect to + and - terminals.
Optional Thermostat and Heater modules are available rated for 115 VAC or 230 VAC.
IMPORTANT NOTE: To comply with CSA/UL electrical safety standards, AC power input and relay
connection wires must have conduit entry to the instrument enclosure. Installation requires a switch,
overcurrent fuse or circuit breaker in the building (in close proximity to the equipment) that is marked
as the disconnect switch.
Risk of electric shock. Loosen cover screw to access connections. Only qualified personnel
should access connections.
Note: Use of instrumentation over 40°C ambient requires special field wiring.
Note: User replaceable fuse 2 Amp 250V (T2AL250V).
!

Page 5
DLT 2.0 Differential Level Transmitter
CONNECTIONS
HEATER OPTION
POWER
INPUT
AC
LN
Sens
B
Sens
A
4-20
B
Sens
4-20
A
Sens
NO
C
NC
NO
C
NC
–
+
4-20
Diff
RLY2
RLY1
AC
GND
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
RLY3 RLY4 RLY5 RLY6
EXTRA RELAYS OPTION
+ - + -
GND
USB HARNESS
CONNECTOR
DATA LOGGER OPTION
CORE
WHT
SHLD
GRN
CORE
WHT
SHLD
GRN

Page 6
DLT 2.0 Differential Level Transmitter
KEYPAD SYSTEM
The DLT 2.0 uses a menu system. Arrows show the four directions to leave a menu box. Press a key to
move to the next item in the direction shown. Move the cursor (underline) under numerals and increase
or decrease numerals with the and keys.
To store calibration values permanently (even through power interruptions), press .

Page 7
DLT 2.0 Differential Level Transmitter
CALIBRATION MENU
--Password----------
Password 0000
--Units/Mode--------
Mode}Flow
Linear ft
Volume USG
Time min
Temperature C
Display Alt
--Calibration-------
}Sensor B
Min Range 1.000ft
Max Range 12.000ft
Slope Offst 0.000ft
Damping 10%
LOE Time 30sec
USG/min
Tot 20130.8 USG
Relays 1 2 3 4 5 6
0.000
--Message-----------
Data log Logging
Log Used 0%
Sensor A Good
Sensor B Good
Temperature A 22C
Temperature B 22C
--Status------------
.00ft}Level A 12
Level B 11.30ft
Difference 0.70ft
20130.8USGTot
EC 100%A
EC B 100%
Relays 1 2 3 4 5 6
--Special Functions-
Language English
}
Analog Out 4-20mA
Backlight High
Reset Totalizer NO
Restore Defaults NO
New Password 0000
--Simulation--------
}Test Actual
ALevel 12.000ft
Flow B 0.00USG/m
Difference 0.00ft
Level A4-20mA 19.99
4-20mA Flow B 4.00
4-20mA Diff 20.00
Relays 1 2 3 4 5 6
--Relay Parameters--
Relay 1}
Sensor B
FlowFunction
Mode Pump
10000 USG/mOn
8000 USG/mOff
LOE mode Off
OAlternate N
--Data Logging-------
Log Site ID 0}
Mode Flow
Set Date Sep 22/2009
Set Time 14:24:40
Interval 30sec
Log Logging
--Configuration-----
}
Utility 1.25.05
Sonar 1.14
24Logger 1. T
6Relays
Analog 3Out
-- ----Channel Setup--
Type V-notch}
Size 22.5°
--Menu Selections----
Units / Mode}
Calibration
SetupChannel
Relay Parameters
Data Logging
Special Functions
Simulation
Configuration
OPTIONAL FEATURES
--24 hr log-------- -B
Date Feb. 12/20}10
50138 USGTotal
34.82 USG/mAverage
52.20 USG/mMaximum
11:08:00Max Time
0.000 USG/mMinimum
9:15:00Min Time
--24 hr log-------- -A
Date Feb. 12/20}10
4.82 ftAverage
8.20 ftMaximum
11:08:00Max Time
0.000 ftMinimum
9:15:00Min Time

Page 8
DLT 2.0 Differential Level Transmitter
ICONS
1. 2. Message waiting. Press .Ç
Data logging .off
1. 2. Data logging .on
1. 2. 3. 4. USB file download.
File download completed.
Download Error.
A sensor reading displayed. Echo OK.
B sensor reading displayed. Echo OK.
Difference reading displayed. Echo OK.
No Echo .
1.
A
1.
B
1.
D
2.
A
2.
B
2.
D
3.
A
3.
B
3.
D

Page 9
DLT 2.0 Differential Level Transmitter
MAIN DISPLAY
NOTE
Sensor A reads Range, Level or Volume
Sensor B reads Range, Level, Volume HRT and Flow
The display is configured from “Units/Mode” menu to display the Sensor
A measurement, Sensor B measurement or Level Difference. The DLT 2.0 will
start-up with this display.
The display also shows Units Selected, Totalizer and Relay States.
MESSAGE ICON
Press from the MAIN display to view status of the data logger and
error/warning messages provided by the instrument. The Message Icon will
appear on the MAIN display if error messages are being generated by the
instrument. Press to return to the main display.
STATUS
Press from the MAIN display to view instrument status. Level for both
sensors is displayed.
Tot Displays the current totalizer reading.
EC Displays echo confidence.
Relays Energized relays will display as a white character on a black
background.
24 HR LOG (Data Logging option only)
Press from the MAIN display to view a formatted flow report from instruments
with a built-in data logger. Press to scroll down one day or repeatedly to scroll
to a specific date. Press to toggle between Sensor A and Sensor B formatted
reports. Up to 365 days can be stored. Newest date will overwrite the oldest. Press
to return to the main display.
USG/min
Tot 20130.8 USG
Relays 1 2 3 4 5 6
0.000
--Message-----------
Data log Stopped
Log Used 0%
Sensor A Good
Sensor B Good
Temperature A 21C
Temperature B 21C
--Status------------
.00ft}Level A 12
Level B 11.30ft
Difference 0.70ft
20130.8USGTot
EC 100%A
EC B 100%
Relays 1 2 3 4 5 6
--24 hr log-------- -B
Date Feb. 12/20}10
50138 USGTotal
34.82 USG/mAverage
52.20 USG/mMaximum
11:08:00Max Time
0.000 USG/mMinimum
9:15:00Min Time

Page 10
DLT 2.0 Differential Level Transmitter
PASSWORD
The password (a number from 0000 to 9999) prevents unauthorized access to
the Calibration menu.
From the MAIN display press to get to Password. Factory default
password is 0000 and if it has not been changed press to proceed to the
Menu Selections screen.
If a password is required, press to place the cursor under the first digit and or
to set the number, then to the second digit, etc. Press or to proceed to
the Menu Selections screen.
A new password can be stored by going to Special Functions/New
Password.
--Password----------
Password 0000
Inhaltsverzeichnis
Beliebte Sender Handbücher anderer Marken

Dejero
Dejero EnGo 3x Bedienungsanleitung

Rosemount
Rosemount 4600 Bedienungsanleitung

Speaka Professional
Speaka Professional 2342740 Bedienungsanleitung

trubomat
trubomat GAB 1000 Bedienungsanleitung

Teledyne Analytical Instruments
Teledyne Analytical Instruments LXT-380 Bedienungsanleitung

Rondish
Rondish UT-11 Bedienungsanleitung