Haes ESENTO ESEN-8MAR Leitfaden

Installation, Commissioning &
Operating Manual
MARINE APPROVED 8 - 12 ZONE CONVENTIONAL
CONTROL PANEL
Approved Document UI-ESEN12MAR-01 Issue 8.0
MED Ref: 0832/15

IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualied and authorised
to do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance
and remedial work. This work must only be carried out by competent service personnel who are fully
conversant with the contents of the panel’s installation manual and have the necessary skills for maintaining
this equipment.
This re alarm system requires periodic checks as specied in BS 5839 Part 1 It is the responsibility of the
system user to ensure it is regularly serviced and maintained in good working order.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this re alarm panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to
product specications at our discretion and without prior notice. E & O E.
IMPORTANT SAFETY NOTES
Haes Technologies Ltd, Unit 3 Horton Industrial Park, West Drayton, UB7 8JD
ATTENTION
Model Number MED Ref No.
Esento Marine 8 zone conventional panel ESEN-8MAR 0832-MED-1086
Esento Marine 12 zone conventional panel ESEN-12MAR 0832-MED-1086
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for re detection and re alarm systems for buildings.
Provided Options (with requirements):
Output to re alarm devices, dependency type ‘A’, test condition
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for re detection and re alarm systems for buildings.
European Standard BS IEC60092-504 : 2001
Electrical installations in ships, special features, control and instrumentation.
European Standard BS IEC60533 : 1999
Electrical and electronic installations in ships, electromagnetic compatibility.

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
1
CONTENTS
Page
ABOUT THIS PANEL 2
PRODUCT OVERVIEW 2
CABINET DETAILS 3
CIRCUIT BOARDS 4
MAIN PCB TERMINALS 6
ZONE CARD TERMINALS 7
TECHNICAL SPECIFICATION 8
POWER SUPPLY MODULE 9
DESIGN CONSIDERATIONS 10
GENERAL DETECTION CIRCUIT SCHEMATIC 10
GENERAL SOUNDER CIRCUIT SCHEMATIC 11
INSTALLATION 12
SAFETY 12
ESD PRECAUTIONS 13
GENERAL 13
MOUNTING THE CABINET 13
MAINS CONNECTIONS 14
CONNECTING THE BATTERIES 15
SETUP & PROGRAMMING 16
NETWORK PANELS SETUP 16
LEVEL 3 ENGINEERING MODE 18
LEVEL 3 ENGINEERING OPTIONS INDEX 19
OPERATING 48
PANEL CONTROLS & INDICATIONS 48
DISABLE MODE 50
TEST MODE 51
FAULT DIAGNOSIS 52
FUNCTIONALITY DURING A SYSTEM FAULT 53
SERVICE & MAINTENANCE 54
DUTIES OF THE RESPONSIBLE PERSON 54
ROUTINE MAINTENANCE & TESTING 54
SCHEDULE OF TESTING LOG BOOK 56
FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK 60
USER INSTRUCTIONS 63

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
The Esento Marine 8 to 12 zone is a conventional control panel with integral power supply & space for
standby batteries.
Esento Marine panels are fully approved to European standards EN54-2 & 4, Fire Detection and Alarm
Systems – Control & Indicating Equipment.
The control panel comprises of a sheet steel enclosure suitable for wall mounting with a hinged, lockable
front access door. It can be semi recessed, using a suitable recessing bezel. Cable entry is via 20mm
‘knockouts’ located at the top and rear of the cabinet.
An eight button keypad is used to control the system and allow access to the function options. The three
main buttons, ‘RESOUND’ (red), ‘SILENCE’ (blue) and ‘RESET’ (green) being much larger and colour
coded to assist the end users.
Eight or twelve re zone circuits are provided plus four monitored sounder circuits. Fire & fault VFCO
relays, re & fault switched negative outputs, class change and an alert input are also included.
The panels are supplied with a 3.0 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
Quiesecent and alarm current details for standby battery calculations
Models Standby Current Alarm Current
ESEN-8MAR 139mA 220mA
ESEN-12MAR 182mA 267mA
TPCA04-S 4 zone ext card, standard 43mA 47mA
TPCA04-H 4 zone ext card, high spec 49mA 87mA
TPCA05 comms card 5.2mA N/A

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
3
ABOUT THIS PANEL
CABINET
60mm 85mm
310mm
455mm
300mm
450mm
Fire Detection System

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
4
ABOUT THIS PANEL
CIRCUIT BOARDS
Esento Marine 8-12 panels comprise of two main circuit boards plus optional ancillary boards
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3 4 5 6
ON
1 2 3 4 ENTER
RESOUND SILENCE RESET
TPCA01-X2MAR/X4MAR - Master PCB
TPCA03 - LED Display & Controls PCB

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
5
ABOUT THIS PANEL
ANCILLARY CIRCUIT BOARDS
+ - + - + - + -
ZONE A ZONE B ZONE C ZONE D
1 2 3 4
ON
D
C
B
A
TWIN
COMS A COMS B 28
V+
SW -ve OUTPUTS
+ - + -
1 2 3 4 5 6
1 2 3 4
ON
ADDRESS
+ - + - + - + -
ZONE A ZONE B ZONE C ZONE D
1 2 3 4
ON
D
C
B
A
TWIN
+ -- - + -
OPA OPB AUX SNDR A SNDR B
CNO
TPCA04-S - Std spec 4 zone extension card
TPCA05 - Comms PCB
TPCA04-H - High spec 4 zone extension card
• 4 x conventional zone circuits.
• Piggy backs on Main PCB for
connection to network & repeater
panels
• 6 programmable switch -ve outputs
• 4 x conventional zone circuits.
• 2 x switched -ve outputs
• 1 x Aux relay output
• 2 x monitored sounder circuits

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
6
ABOUT THIS PANEL
MAIN PCB TERMINALS
28v output fused @ 500mA
28v input for power supply
Temperature compensation voltage control link
Commmon re VFCO relay
unfused. Max 3A @ 30vdc
Commmon fault VFCO relay
maintained (fail safe)unfused.
Max 3A @ 30vdc
Programmable O/P
Programmable O/P
Alert (pulses sounders)
Precint/class change (activates sounders)
Switched -ve inputs
Switched -ve outputs
Max load 40mA
To 0 volts
Relay Coil
Conventional monitored
sounder circuits, fused @ 500mA
Conventional re zone circuits, fused @ 500mA
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3 4 5 6
ON

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
7
ABOUT THIS PANEL
ZONE CARD TERMINALS
+ -
+ -- - + -
+ - + - + -
ZONE A ZONE B ZONE C ZONE D
1 2 3 4
ON
D
C
B
A
TWIN
OPA OPB AUX SNDR A SNDR B
CNO
Conventionalre zone circuits,
fused @ 500mA
Relay Coil
Relay Coil
Programmable O/P
Programmable O/P
Programmable relay O/P unfused.
Max 3A @ 30vdc
28v
28v
Switched -ve outputs
Max load 40mA
Conventional monitored
sounder circuits, fused @ 500mA
Drawing shows the high spec version of the
zone extension PCB (TPCA04-H).
The std version does not contain the additional
outputs or sounder circuits shown at the
bottom.

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
8
ABOUT THIS PANEL
TECHNICAL SPECIFICATION
Electrical Specication Inputs & Outputs - TPCA01-X2/X4 Main PCB
Terminal capacity 0.5mm2 to 2.5mm2solid or stranded wire.
PSU @ output Power supply voltage control line. For temperature compensation control.
PSU Input + - 28vdc supply input. Diode protected for
reversal and independent short circuit.
Max current 3 amps.
Max input current 3 amps. Input voltage
22vdc to 32vdc.
28v+, 0v- power output 28vdc supply output for re alarm
accessory relays etc. Max continuous
use = 400mA.
Fused @ 500mA. Fuse = 500mA
resettable fuse.
Common re relay Fire relay contact. Clean C/O.
Max 3A @ 30vdc.
Unfused
Common fault relay Maintained fault relay contact. Clean C/O
Max 3A @ 30vdc.
Unfused
Outputs; FR, FLT Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52vdc.
Current limited 680R. Max load = 40mA
Inputs; CC, PUL Switched -ve inputs, connect to 0v to
trigger. Max input voltage = 28vdc. Non
latching, max resistance 100R.
Protected via 10K Ohm impedance, 3v6
zener diode.
SNDR 1 - 2 28vdc polarity reversal monitored
sounder outputs to re alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 2.4A is not
exceeded.
Zone 1 - 4 Conventionally wired re alarm zone
circuits. 4K7 Ohm 5% 0.25W EOL
resistor.
Maximum detector load 3.5mA per zone,
Typical qty 40-50 Apollo marine optical
detectors, Note:- Max 32 detectors with
line continuity diode bases tted
Electrical Specication Inputs & Outputs - TPCA04-S/H zone cards
Terminal capacity 0.5mm2 to 2.5mm2solid or stranded wire.
Zone A - D Conventionally wired re alarm zone
circuits. 4K7 Ohm 5% 0.25W EOL
resistor.
Maximum detector load 3.5mA per zone,
Typical qty 40-50 Apollo marine optical
detectors, Note:- Max 32 detectors with
line continuity diode bases tted
Programmable outputs OP A & OP B Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52vdc.
Current limited 680R. Max load = 40mA
Programmable relay ouput Fire relay contact. Clean C/O, C & N/O
Max 3A @ 30vdc.
Unfused
SNDR A - B 28vdc polarity reversal monitored
sounder outputs to re alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 2.4A is not
exceeded.
Electrical Specication Inputs & Outputs - TPCA05 comms PCB
Comms A - B RS485 Repeater Comms, fused @ 20mA
28v Supply output Fused @ 500mA
Programmable outputs 1 - 6 Switched -ve outputs Overload voltage protected to 52vdc
Current limited 680R
Max load = 40mA
Dieses Handbuch passt für folgende Modelle
2
Inhaltsverzeichnis
Andere Haes Bedienfeld Handbücher

Haes
Haes ESPRIT-G Leitfaden

Haes
Haes AlarmSense Leitfaden

Haes
Haes FUSION 0832-CPD-1431 Bedienungsanleitung

Haes
Haes AOV Series Leitfaden

Haes
Haes ELAN HS-5000 Series Bedienungsanleitung

Haes
Haes ESG-2001 Leitfaden

Haes
Haes SZAOV Leitfaden

Haes
Haes Excel-EN Leitfaden

Haes
Haes MZAOV-1001 Leitfaden

Haes
Haes ELAN HS-5200 Montageanleitung