SECTION II: INSTALLATION ANDMAINTENANCE
oThe following is memorised for each alarm:
date and time of intervention (if the KSC accessory ispresent);
in/out water temperature values as soon as the alarm istriggered;
the condensation pressure values at the time of the alarm
alarm delay from when the connected device is switched on;
compressor status at the time of the alarm;
oAdvanced functions:
Hi-Pressure Prevent function with forced cooling capacity
partialisation for a high outdoor temperature (in summermode),
set-up for serial connection (KRS485, KFTT10, KRS232, KUSB
accessory);
possibility to have a digital input for remote management of the
double Set point (see the Pre-sales Department);
possibility to have an analogue input for the shifting Set-point via a
4-20mA remote signal (contact Pre-sales Department);
set-up for management of time bands and operating parameters with
the possibility of daily/weekly operating programs (KSC accessory);
check-up and verification of the scheduled maintenancestatus;
computer-assisted machine testing;
self-diagnosis with continuous monitoring of the machine operating
status.
II.2
ACCESSORIES
II.2.1
Factory fitted accessories
P1 –Installation with pump.
P2 –Installation with increased head pump.
DP1 –Installation with double pump, one of which in standby with
automatic activation.
DP2 –Installation with increased head double pump, one of which in
standby with automatic activation.
ASP1 –Installation with pump and storage tank.
ASP2 –Installation with increased head pump and storage tank.
ASDP1 –Installation with double pump, one of which in standby with
automatic activation and storage tank.
ASDP2 –Installation with increased head double pump, one of which in
standby with automatic activation and storage tank.
INS–Soundproofed compressors with noise-absorbing ear muff
(solution that reduced the noise of the compressors).
RA –Evaporator anti-freeze resistance, prevents the risk of ice
formation inside the exchanger when the machine is switched off
(provided the unit remains powered).
RDR –Desuperheater/recovery unit anti-freeze resistance (DS or
RC100), prevents the risk of ice formation inside the recovery unit
exchanger when the machine is switched off (provided the unit remains
powered).
RAS –300W storage tank anti-freeze resistance (available for ASP1-
ASDP1- ASP2-ASDP2 set-ups); prevents the risk of ice formation inside
the exchanger tank when the machine is switched off (provided the unit
remains powered).
RAE 1 –27W electric pump anti-freeze resistance (available for P1-
DP1-ASP1-ASDP1 set-ups); prevents the risk of the water inside the
pump becoming ice when the machine is switched off (provided the unit
remains powered).
RAE 2 –27W double electric pump anti-freeze resistance (available for
P2-DP2-ASP2-ASDP2 set-ups); prevents the risk of the water inside the
pumps becoming ice when the machine is switched off (provided the
unit remains powered).
DS –Desuperheater; it is not active during heat pump operation.
RC100 –Heat recovery unit with 100% recovery; the accessory is
complete with a differential pressure switch on the recovery unit
exchanger. It does not work as a heat pump.
GM –Cooling circuit high and low pressure gauges.
SFS –Soft-Start device to reduce the peak current in the start-up phase
(weight 40 Kg).
FTT10 –FTT10 serial interface board for connection to supervision
systems (LonWorks® system compliant with Lonmark® 8090-10 protocol
with chiller profile).
SS –RS485 serial interface board to create dialogue networks between
boards (maximum: 200 units for a max. distance of 1000 m) and the
building automation or external supervision systems.
CR –Power factor correction capacitors (cosΦ > 0.91).
EEV –Electronic thermostatic valve.
RAP –Unit with copper/pre-painted aluminium coils.
BRR –Unit with copper/copper coils.
DSP –Double Set-point via digital consensus (incompatible with the CS
accessory).
BT –low temperature of water produced (only for models 270÷2160).
CS –4-20 mA analogue signal for shifting Set-point (incompatible with
the DSP accessory). The EEV accessory may have to be also installed,
depending on the required values.
RPB –Coil protection mesh with accident-prevention function.
IMB –Protective packaging.
II.2.2
Accessories supplied separately
KFA - Water filter (only for models 233÷265).
KRAS - Fitting for connection to the inlet duct.
KRMA - Antivibration fitting for connection to the outlet duct.
KSA –Rubber antivibration mountings.
KRIT –Additional electrical resistance heater for heat pump only for
233÷265.
KEAP –Outdoor air temperature probe for Set-point compensation
(incompatible with the CS accessory).
KTR –Remote control keyboard with backlit LCD display (same
functions as that on the machine).
KSC –Clock card to display the date/time and machine time band
management with daily and weekly start/stop time bands, with the
possibility of changing the Set-points.
KRS485 –RS485 serial interface board to create dialogue networks
between boards (maximum: 200 units for a max. distance of 1000 m)
and the building automation or external supervision systems.
KFTT10 –FTT10 serial interface board for connection to supervision
systems (LonWorks® system compliant with Lonmark® 8090-10 protocol
with chiller profile).
KISI –CAN bus serial interface (Controller Area Network).
KRS232 –RS485/RS232 serial converter for interconnection between
the RS485 serial network and supervision systems with serial
connection to the PC via the RS232 serial port (RS232 cable supplied).
KUSB –RS485/USB serial converter for interconnection between the
RS485 serial network and supervision systems with serial connection to
the PC via the USB port (USB cable supplied).
KMDM –GSM 900-1800 modem kit to be connected to the unit for
remote management of the parameters and any alarm signals. The kit
consists of a GSM modem with relative RS232 board. A SIM data card,
not supplied must be purchased.
KRS –Supervision software for the monitoring and remote
management of the units. The kit consists of a CD-Rom and hardware
key.