Hoffer Flow Controls CAT1 Series Bedienungsanleitung

Microprocessor Controlled Two-Wire 4-20mA
Loop Powered Transmitter
Model: CAT1
HP-310
February 2008
USER’S MANUAL
HP-310
April 2009
107 Kitty Hawk Lane, P.O. Box 2145, Elizabeth City, NC 27906-2145
800-628-4584 252-331-1997 FAX 252-331-2886
www.hofferflow.com E-mail: info@hofferflow.com


HFC 9708
Notice HOFFER FLOW CONTROLS, INC. MAKES NO WARRANTY OF
ANYKINDWITHREGARDTOTHISMATERIAL,INCLUDING,BUT
NOT LIMITED TO, THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE.
This manual has been provided as an aid in installing, connecting,
calibrating, operating, and servicing this unit. Every precaution for
accuracy has been taken in the preparation of this manual; however,
HOFFER FLOW CONTROLS, INC. neither assumes responsibility for
any omissions or errors that may appear nor assumes liability for any
damages that may result from the use of products in accordance with
information contained in the manual.
HOFFERFLOWCONTROLS’ policyistoprovideausermanualforeach
item supplied. Therefore, all applicable user manuals should be examined
before attempting to install or otherwise connect a number of related
subsystems.
Duringinstallation,care mustbetakentoselectthecorrectinterconnecting
wiringdrawing. Thechoiceofanincorrectconnection drawingmayresult
in damage to the system and/or one of the components.
Please review the complete model of each itemto be connected and locate
the appropriate manual(s) and/or drawing(s). Identify all model numbers
exactly before making any connections. A number of options and
accessories may be added to the main instrument, which are not shown on
the basic user wiring. Consult the appropriate option or accessory user
manual before connecting itto the system. In many cases, a systemwiring
drawing is available and may be requested from HOFFER FLOW
CONTROLS.
This document contains proprietary information, which is protected by
copyright. All rights are reserved. No part of this document may be
photocopied, reproduced, or translated to another language without the
prior consent of HOFFER FLOW CONTROLS, INC.
HOFFER FLOW CONTROLS’ policy is to make running changes, not
model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering. The information
contained in this document is subject to change without notice.
RETURN REQUESTS/INQUIRIES
Direct all warrantyand repair requests/inquiries to the Hoffer Flow Controls Customer Service
Department, telephone number (252) 331-1997 or 1-800-628-4584. BEFORE RETURNING
ANY PRODUCT(S) TO HOFFER FLOW CONTROLS, PURCHASER MUST OBTAIN A
RETURNED MATERIAL AUTHORIZATION (RMS) NUMBER FROM HOFFER FLOW
CONTROLS’ CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned RMA number should then be marked on the outside
of the return package and on any correspondence.
FORWARRANTYRETURNS,pleasehave
thefollowinginformationavailableBEFORE
contacting HOFFER FLOW CONTROLS:
1. P.O. number under which the product
was PURCHASED,
2. Model and serial number of the product
under warranty, and
3. Repair instructions and/or specific
problems relative to the product.
FOR NON-WARRANTY REPAIRS
OR CALIBRATIONS, consult
HOFFER FLOW CONTROLS for
currentrepair/calibrationcharges. Have
the following information available
BEFORE contacting HOFFER FLOW
CONTROLS:
1. P.O. number to cover the COST of
the repair/calibration,
2. Model and serial number of the
product, and
3. Repair instructions and/or specific
problems relative to the product.

HFC 9708
LIMITED WARRANTY
HOFFERFLOW CONTROLS,INC. (“HFC”)warrantsHFC’sproducts(“goods”)described in
the specifications incorporated in this manual to be free from defects in material and
workmanship undernormal useand service, but only if such goods have been properly selected
fortheserviceintended,properlyinstalledandproperlyoperatedandmaintained. Thiswarranty
shall extend for a period of (1) year from the date of delivery to the original purchaser (or
eighteen (18) months if the delivery to the original purchaser occurred outside the continental
United States). This warranty is extended only to the original purchaser (“Purchaser”).
Purchaser’ssoleandexclusiveremedyistherepairand/orreplacementofnonconforminggoods
as provided in the following paragraphs.
In the event Purchaser believes the goods are defective, the goods must be returned to HFC,
transportation prepaid by Purchaser, within twelve (12) months after delivery of goods (or
eighteen (18) months for goods delivered outside the continental United States) for inspection
by HFC. If HFC’s inspection determines that the workmanship or materials are defective, the
goodswillbe either repaired or replaced,atHFC’s sole determination,freeof additional charge,
and the goods will be returned, transportation paid by HFC, using the lowest cost transportation
available.
Prior to returning the goods to HFC, Purchaser must obtain a Returned Material Authorization
(RMA) Number from HFC’s Customer Service Department within 30 days after discovery of
a purported breach of warranty, but no later than the warranty period; otherwise, such claims
shall be deemed waived. See the Return Requests/Inquiries Section of this manual.
If HFC’s inspection reveals the goods are free of defects in material and workmanship or such
inspection reveals the goods were improperly used, improperly installed, and/or improperly
selectedfor serviceintended, HFCwill notifythe purchaserin writingandwilldeliverthegoods
back to purchaser upon (i) receipt of Purchaser’s written instructions and (ii) the cost of
transportation. If Purchaser does not respond within 30 days after notice from HFC, the goods
will be disposed of in HFC’s discretion.
HFC does not warrant these goods to meet the requirements of any safety code of any state,
municipality, or any other jurisdiction, and purchaser assumes all risk and liability whatsoever
resulting from the use thereof, whether used singly or in combination with other machines or
apparatus.
This warranty shall not apply to any HFC goods or parts thereof, which have bee repaired
outside HFC’s factory or altered in any way, or have been subject to misuse, negligence, or
accident, or have not been operated in accordance with HFC’s printed instructions or have been
operated under conditions more severe than, or otherwise exceeding, those set forth in the
specifications for such goods.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES,
EXPRESSED OR IMPLIED, INCLUDING ANY IMPLIED WARRANTLY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. HFC SHALL
NOT BE LIABLE FOR ANY LOSS OR DAMAGE RESULTING, DIRECTLY OR
INDIRECTLY, FROM THE USE OF LOSS OF USE OF THE GOODS. WITHOUT
LIMITING THE GENERALITY OF THE FOREGOING, THIS EXCLUSION FROM
LIABILITYEMBRACESTHEPURCHASER’SEXPENSESFORDOWNTIME,DAMAGES
FORWHICHTHEPURCHASERMAYBELIABLETOOTHERPERSONS,DAMAGESTO
PROPERTY,AND INJURY TOOR DEATHOF ANYPERSON. HFCNEITHERASSUMES
NOR AUTHORIZES ANY PERSON TO ASSUME FOR IT ANY OTHER LIABILITY IN
CONNECTION WITH THE SALE OR USE OF HFC’S GOODS, AND THERE ARE NO
AGREEMENTS OR WARRANTIES COLLATERAL TO OR AFFECTING THE
AGREEMENT. PURCHASER’SSOLEANDEXCLUSIVEREMEDYISTHEREPAIRAND/OR
REPLACEMENT OF NONCONFORMING GOODS AS PROVIDED IN THE PRECEDING
PARAGRAPHS. HFCSHALLNOTBELIABLEFORANYOTHERDAMAGES WHATSOEVER
INCLUDING INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES.
Disclaimer:
Specifications are subject to change without notice.
Some pages are left intentionally blank.

HP-310
CONTENTS
1. Introduction------------------------------------------------------------ 1
1-1 Model Number Designation ------------------------------------- 2
2. Specifications----------------------------------------------------------- 5
3. Principle of Operation ----------------------------------------------- 7
3-1 Functional Blocks------------------------------------------------- 7
3-1-1 Preamplifier -------------------------------------------------- 7
3-1-2 Microcontroller ---------------------------------------------- 8
3-1-3 Loop Driver -------------------------------------------------- 8
3-1-4 Communications Interface --------------------------------- 8
3-2 System Response Time------------------------------------------- 9
4. Installation-------------------------------------------------------------11
4-1 Typical Connections---------------------------------------------11
4-2 Communications Connections----------------------------------12
4-3 Wiring -------------------------------------------------------------12
Appendix A – Default Configuration----------------------------------13
Appendix B – Communications-----------------------------------------15
Message Format And Timeout -----------------------------------------15
Messages ------------------------------------------------------------------17


Introduction 1
HP-310
1. Introduction
The CAT1 is a microprocessor based loop powered transmitter. The
transmitter accepts a low-level frequency signal on the input and
provides a 4-20mA analog output proportional to the flow rate. CAT1
is compatible with all Hoffer turbine flowmeters as well as the H.O.G.
series positive displacement flowmeters.
The CAT1-L model provides for 20-point linearization of the flow
input signal and outputs a linearized analog current. CAT1 is fully
configurable via an RS232 communications port located under the top
plate. CAT configuration software is a Windows based application
that provides the interface for entering K-factors, frequencies, the
timebase for rate measurement, and calibration of the analog output.
Configuration and remote monitoring can also be performed using any
PC based communications program (e.g., HyperTerminal) or ASCII
terminal.
The standard unit is packaged in an extruded aluminum enclosure for
wall mounting or may be mounted directly on a flowmeter using an
optional NEMA 4X or EX enclosure. An optional bracket is also
available for mounting on standard DIN rail.
This instrument is designed to conform to the EMC-Directive of the
Council of European Communities 89/336/EEC and the following
standards:
Generic Emission Standard EN 50081-1
Residential, Commercial & Light Industry Environment.
Generic Emission Standard EN 50081-2
Industrial Environment.
Generic Immunity Standard EN 50082-1
Residential, Commercial & Light Industry Environment.
Generic Immunity Standard EN 50082-2
Industrial Environment.

2 Introduction
HP-310
1-1 Model Number Designation
MODEL CAT1-( A)-( B)-( C)-( D)
ENCLOSURE STYLE
LINEARIZED ANALOG OUTPUT
INPUT POWER
SPECIAL FEATURES
ENCLOSURE STYLE
MODEL CAT1-( A)-( )-( )-( )
OPTION ( A )
(1) GENERAL PURPOSE.
2.6"L X 2.6"H X 2.6"W MINIMUM MOUNTING SPACE.
(D) 2" LONG DIN RAIL MOUNT SINGLE UNIT.
UP TO 20 CAT1 UNITS CAN BE MOUNTED ON A SINGLE RAIL.
ADD 2" PER UNIT.
(3/O) MEETS CLASS 1, DIV. 1 AND 2, GROUPS C, D
CLASS II, GROUPS E, F, G
CLASS III
NEMA 4X WITH ‘O’ RING
CERTIFIED CSA, UL
BODY KILARK #GECCT-3, STOCK #200-0945
FLAT COVER, STOCK #200-0533, KILARK #GECBC
(3B/O) MEETS CLASS I, DIV. 1 AND 2, GROUPS A, B, C, D
CLASS 1, ZONES 1 AND 2, GROUPS IIB + H2, IIA
CLASS II, DIV. 1 AND 2, GROUPS E, F, G
CLASS III
NEMA 3, 4, 7 (B, C, D), 9 (E, F, G)
CERTIFIED CENELEC, CSA, UL, FM
BODY KILARK #HKB, STOCK #200-0406
FLAT COVER , STOCK #200-0773, KILARK #HKB-B.
(3B/O-ATEX) EExd II C ENCLOSURE. ATEX-APPROVED 3/4" FNPT
CABLE ENTRIES.

Introduction 3
HP-310
LINEARIZED ANALOG OUTPUT
MODEL CAT1-( )-( B)-( )-( )
OPTION ( B )
(7) 4 TO 20 MA UP TO 20 POINTS.
ACCURACY +/-0.02% OF FULL SCALE.
INPUT POWER
MODEL CAT1-( )-( )-( C)-( )
OPTION (C )
(D) 8 TO 24 VDC LOOP POWERED.
SPECIAL FEATURES
MODEL CAT1-( )-( )-( )-( D)
OPTION ( D )
(CE) MARK REQUIRED FOR EUROPE
(SP) ANY SPECIAL FEATURES THAT ARE NOT COVERED IN THE
MODEL NUMBER, USE A WRITTEN DESCRIPTION OF THE -SP.
NOTES: 1. INPUTS: ACCEPTS MAGNETIC COIL ONLY.
2. WINDOWS® BASED SETUP DISC AND 6 FOOT COMMUNICATION
CABLE. IF THREE OR MORE UNITS ARE ORDERED ON THE SAME
PURCHASE ORDER ONE SET IS SUPPLIED AT NO CHARGE.

4 Introduction
HP-310
This page intentionally left blank.
Andere Handbücher für CAT1 Series
1
Inhaltsverzeichnis
Andere Hoffer Flow Controls Sender Handbücher
Beliebte Sender Handbücher anderer Marken

Dejero
Dejero EnGo 3x Bedienungsanleitung

Rosemount
Rosemount 4600 Bedienungsanleitung

Speaka Professional
Speaka Professional 2342740 Bedienungsanleitung

trubomat
trubomat GAB 1000 Bedienungsanleitung

Teledyne Analytical Instruments
Teledyne Analytical Instruments LXT-380 Bedienungsanleitung

Rondish
Rondish UT-11 Bedienungsanleitung